2
Technical Data
TD150029EN
Effective November 2020
PXM4/6/8K meter color touchscreen
display quick start guide
EATON www.eaton.com
Installation
1. Disconnect and lockout all power to the enclosure.
2. Inspect the enclosure door to determine the best mounting loca-
tion for the PXM4/6/8K meter color touchscreen display.
ote:
N
A minimum clearance of 1.18 in. (30.0 mm) must be maintained
between the ventilation holes in the back of the display and any other
component within the enclosure.
3. Use the mounting template to mark the cutout area on the enclo-
sure door. Cut out the marked area.
Figure 3. Cut out dimensions.
4. Ensure proper gasket placement on the PXM4/6/8K meter color
touchscreen display.
5. Insert the PXM4/6/8K meter color touchscreen display through
the cutout.
6. Fit the supplied threaded pins in the retaining brackets. The tips
of the threaded pins must point towards the wider ends of the
retaining brackets. Clip on the retaining brackets in the recesses
provided for them on the device.
Figure 4. Mounting the PXM4/6/8K meter display.
7. Check for proper alignment of the PXM4/6/8K meter color touch-
screen display. Then fix the device by torquing the threaded pins
to 0.1 Nm (0.86 lb-in) with a 2 mm hexagonal screwdriver. The
front of the display should be flush with the surface of the control
cabinet at the fixing points.
Figure 5. Power and COM port connections for the PXM4/6/8K meter display touch screen display.
PXM display power cable
PXMCM
COM 1 RS485
Display connection
PXM display data cable
PIN 2
PIN 1
RED
WHITE
BLACK&BARE
PIN 3
PHOENIX CONN.
TERMINATION
PIN 2
PIN 3
PIN 1
PHOENIX CONN.
TERMINATION
RED
WHITE
BLACK&BARE
H11 (XV)
PXM468K-DISP-6-XV
Eaton P/N 67A2180Hx1
YY-MM-DD
1.5"
1.5"
72.0"
PIN 1
PIN 1
Eaton P/N 67A2181HXX
YY-MM-DD
1.5"
72.0"
PIN 1
PIN 2
PIN 3
RED
WHITE
BLACK&BARE
PIN 1
PHOENIX CONN.
TERMINATION
PIN 3
PIN 5
PIN 7
RED
BLACK
WHITE
DB9 SHELL
DB9 TERMINATION
H11 (XV)
SHIELD WIRE TERMINATED to
CM3
CM4
67A2181H11
67A2180H11