3
Instruction Booklet
IB02601014E
Effective December 2012
Enclosed meter—
PXM 4000/6000/8000
eaton Corporation
www.eaton.com
receiving, handling, and storage
Receiving and handling
Every effort is made to ensure that the Enclosed PXM equipment
arrives at its destination undamaged and ready for installation .
Crating and packing are designed to protect internal components
as well as the enclosure . Do not remove protective packing until
the equipment is ready for installation .
When the equipment reaches its destination, the customer should
inspect the shipping container for any obvious signs of rough
handling and/or external damage that occurred during transportation .
Record any external and internal damage for reporting to the
transportation carrier and Eaton, once a thorough inspection is
complete . All claims should be as specific as possible and include
general order numbers .
A plastic bag of instruction booklets and/or CDs will be found in the
shipping container . Store these documents in a safe place .
Storage
Although well packaged, this equipment is not suitable for storage
outdoors . And if the equipment is to be stored indoors for any period
of time, it should be stored with its protective packaging in place .
Refer to the
Power Xpert PXM 4000/6000/8000 User and Installation
Manual
IM02601004E for suitable conditions for these devices .
installation and wiring
General
Enclosed PXM devices are factory wired and tested . Installation
requires solidly mounting the enclosed unit and connecting field
wiring . Included in this booklet are diagrams of the factory wiring
and various field wiring options . Review and understand the
appropriate diagrams for the catalog number of the unit you
have ordered .
The system voltage application is assumed to be a three-phase,
four-wire system for both the models with and without a CPT . For
a model with a CPT, the primary voltage is assumed to be 480 Vac
with a secondary voltage of 120 Vac . It is also assumed that there
will be five CTs used in the application for monitoring the current of
the system . For applications that are three-phase, three-wire, and
different CT configurations, please see Chapter 3 of the
User and
Installation Manual
IM02601004E for further details and configuration
options . All models containing an I/O card and RJ45 communications
connections will be required to have the external wires connected
directly to the PXM device .
Mounting location
Choose a location that offers a flat, rigid mounting surface capable of
supporting the weight of the equipment (
Figure 1
through
Figure 3
) .
Units will weigh 85 lbs (38 .6 kg) maximum . Mount the equipment
in a suitable environment . These enclosures are designed for
NEMA 12, 3R, and 4X environments . The catalog number identifies
the enclosure . If there are any doubts as to location suitability,
discuss them with your Eaton representative . Check to make
certain that there are no pipes, wires, or other mounting hazards
in the immediate mounting area that could create a problem .
Carefully remove all packing material from the unit . Even though
an equipment inspection was made when the equipment was
received, make another careful inspection of the enclosure and the
devices inside as packing material is removed . Be especially alert for
distorted metal, loose wires, or damaged components .
Mounting procedure
The enclosures are provided with four elongated mounting holes,
two at the top mounting flange and two at the bottom .
Knockout procedure
Use an appropriate knockout punching tool for incoming power
connections . In addition, the use of an appropriate NEMA-rated
hub is required to maintain enclosure NEMA rating .
Top View
20.00
(508.0)
12.00
(304.8)
Left Side View
Front View
Bottom View
Right Side View
External Rear View
Front View (Door Removed)
1/4-Turn
Padlocking Latch
22.50
(571.5)
Mounting
Height
18.50 (469.9)
Mounting Width
0.75
(19.1)
0.75
(19.1)
4xø0.44
24.00
(609.6)
21.00
(533.4)
Subpanel
Height
16.94 (430.3)
Subpanel Width
Figure 1. Dimensions of Enclosed PXM —NEMA 12