![Eaton Pulsar Evolution 1150/1150 Rack 1U Installation And User Manual Download Page 19](http://html1.mh-extra.com/html/eaton/pulsar-evolution-1150-1150-rack-1u/pulsar-evolution-1150-1150-rack-1u_installation-and-user-manual_527293019.webp)
34008235EN/AC - Page 19
6. Appendices
6.1 Technical specifications
(1) The high and low thresholds can be adjusted using
Personal Solution-Pac
software.
(2) Up to 40 Hz in extended frequency mode (programmable using
Personal Solution-Pac
software).
(3) Adjustable to 200 V (10% derating of output power) / 208 V / 220 V / 230 V / 240 V.
When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16A, 250V which is
IEC/EN 60898-1 standard compliant;
When the appliance is used in America area, use an external circuit breaker in front of line with rating 20A, 250V.
This product is designed for IT power distribution system.
Evolution
650 / 650 Rack
850 / 850 Rack
1150 / 1150 Rack
1550 / 1550 Rack
Output power
650 VA /
420 W
850 VA /
600 W
1150 VA /
770 W
1550 VA /
1100 W
AC input power
◗
Rated input voltage
◗
Input-voltage range
◗
50 Hz input-frequency range
◗
60 Hz input-frequency range
Single phase 220~240 V
160 V to 294 V
(1)
47 Hz to 70 Hz
(2)
56.5 Hz to 70 Hz
(2)
Output on battery power
◗
Voltage
◗
Frequency
230 V (+6% / -10%)
(3)
50/60 Hz ±0.1 Hz
Battery (sealed lead acid,
maintenance free)
◗
Tower model
◗
Rack model
1 x 12 V - 9 Ah
2 x 6 V - 9 Ah
2 x 12 V - 7.2 Ah
4 x 6 V - 7.2 Ah
2 x 12 V - 9 Ah
4 x 6 V - 9 Ah
3 x 12 V - 9 Ah
6 x 6 V - 9 Ah
Environment
◗
Operating temperature range
◗
Storage temperature range
◗
Humidity
◗
Noise level
0 to 35°C
0 to 40°C
-25°C to 40°C
20 to 90% (without condensation)
< 40 dbA
Transformer
AVR
Filter
Charger
Inverter
Battery
Summary of Contents for Pulsar Evolution 1150/1150 Rack 1U
Page 2: ...34008235EN AC Page 2...
Page 21: ...34008235EN AC Page 21 Notes...
Page 22: ...34008235EN AC www eaton com...