2

 

POWERXL DM1 SERIES ADJUSTABLE FREQUENCY DRIVES

 PUB53696—August 2020   www.eaton.com

Connection options

Table 1. Connection options - main keypad.

Connection 

method

Port

Upgrade 

firmware

Connects to 

PC tool

Communication settings

RS-485

Modbus serial 

terminals

DM1 PRO   

ST

O terminals

Relay terminals

I/O terminals

15   STO_COM
16   STO2
17   STO1

18   RY1NO
19   RY1CM
20   RY1NC
21   RY2NO
22   RY2CM

8   AI1+
9   AI1-

10   GND
11   AO1+
12   GND
13   +10 V
14   +24 V

1   DIN1
2   DIN2
3   DIN3
4   DIN4
5   CMA
6   A+
7   B-

                 DM1

RS-485 Comm Set: Settable in RS-485 communication parameter group.

(Default modbus RTU).

Note:

 If set to BACnet MSTP, PC Tool will not communicate.

Slave address: Settable in RS-485 communication parameter group (Default 1).
Baud rate: Settable in RS-485 communication parameter group (Default 19,200).
Parity: Settable in RS-485 communication parameter group (Default even).
Data bits: Not settable, 8 data bit.
Stop bits: Not settable, 1 stop bit.

Keypad port

       

Slave address: Not settable, set to modbus ID 18.
Baud rate: Not settable, set to 38,400 Kbaud.
Parity: Not settable, set to even.
Data bits: Not settable, 8 data bit.
Stop bits: Not settable, 1 stop bit.

Ethernet

Ethernet port

---

    

IP address mode: Settable in ethernet communication parameter group.

(Default DHCP with AutoIP).

Note:

 Most facilities require a static IP.  Change the static IP address before changing.  After 

changing this parameter, a reset or power cycle is required.
Active IP address: Set depending on IP address assigned static or DHCP.
Active subnet mask: Set depending on IP address assigned static or DHCP.
Active default gateway: Set depending on IP address assigned static or DHCP.
Static IP address: Settable in ethernet communication parameters group.

(Default 192.168.1.245).
Static subnet mask: Settable in ethernet communication parameters group.

(Default 255.255.255.0).
Static default gateway: Settable in ethernet communication parameters group.

(Default 192.168.1.1).

Relay terminals

I/O terminals

18   R

Y1NO

19   R

Y1CM

20   R

Y1NC

1   DIN1

2   DIN2

3   DIN3

4   DIN4

5   CMA

6   

A+

7   B-

8   

AI1+

9   

AI1

-

10   GND

11   

AO1+

12   GND

13   +1

0 V

14   +24 

V

RJ45 port
for Keypad/PC

DM1 PRO 

Only

Ethernet port

Summary of Contents for PowerXL DM1 Series

Page 1: ...erXL DM1 Series VFD Effective August 2020 Supersedes March 2020 Quick start guide Go to Eaton com DM1 DocumentsTab User manuals for DM1 SoftwareTab To download Power Xpert inControl and software suppo...

Page 2: ...www eaton com Contents Step 1 Ratings 1 Step 2 PowerXL DM1 connection process to PowerXpert inControl PC tool 3 Step 3 Keypad overview 16 Step 4 Start up 25 Step 5 Standard application 29 Step 6 Faul...

Page 3: ...1 Ratings POWERXL DM1 SERIES ADJUSTABLE FREQUENCY DRIVES PUB53696 August 2020 www eaton com Step 1 Ratings Rating label Figure 1 Housing rating label Carton labels U S and Europe Figure 2 Carton ratin...

Page 4: ...table set to modbus ID 18 Baud rate Not settable set to 38 400 Kbaud Parity Not settable set to even Data bits Not settable 8 data bit Stop bits Not settable 1 stop bit Ethernet Ethernet port IP addre...

Page 5: ...aton currently supports modbus serial and modbus TCP communication protocols for connecting to its devices Creating a network The framework will show the installed communication modules that are insta...

Page 6: ...www eaton com Click on the green next to the communication protocol or right click on the Network Name and select Add Follow the steps to add the desired network Figure 5 Adding the desired network ot...

Page 7: ...ew project 4 Begin creating the network topology by adding Modbus TCP DTM located on the device catalog 5 6 Configure the modbus TCP settings to match that of the drive The default values loaded into...

Page 8: ...ode and then select Connect or click the Connect button on the top toolbar The online parameter window will open when once connected 9 The user should now be connected to the drive and have the abilit...

Page 9: ...d BLE Communication DTM using One Installer DM1 Bluetooth Parameters P11 22 Blue Tooth Enable Enabled P11 6 1 on keypad P11 48 Blue Broadcast Mode On P11 6 2 on keypad Power Xpert inControl Open inCon...

Page 10: ...ABLE FREQUENCY DRIVES PUB53696 August 2020 www eaton com Eaton BLE Comm DTM will go to Online mode Power XL DM1 starts the connection process Scan dialog will be displayed to see the devices available...

Page 11: ...etected attempt a Refresh Note Scanning will detect only DM1 DM1 Pro products All others are filtered Four digit PIN dialog is generated and displayed on local the keypad and remote keypad Note It is...

Page 12: ...IES ADJUSTABLE FREQUENCY DRIVES PUB53696 August 2020 www eaton com If PIN verification succeeds PowerXL DM1 device DTM instance goes to Online connected state and Online parameters page is loaded Para...

Page 13: ...as used to add communication DTM to add the device Once the device is added depending on the communication device selected a window will pop up to set slave address or IP address of the device refer t...

Page 14: ...current rating of the drive in which it is going to be installed Motor Line Frequency will correspond to the line frequency of the facility in which it is being put Drive Application will select the...

Page 15: ...ble in the Start Up Wizard The Start Up Wizard will walk through the most used parameter required to get the drive programmed and running As the screens come up by selecting Next it will advance you t...

Page 16: ...iptions If further support is needed the Support button will provide technical support contacts for the Region required More details on these buttons are described below Online The Online mode is when...

Page 17: ...n open the application window by double clicking on the device you would like to view and edit The tab indicator will show that you are in an online window To disconnect from a device there are the sa...

Page 18: ...gation buttons With the control keypad it is possible to control the speed of a motor to supervise the state of the equipment and to set the frequency converter s parameters see Figure 14 Figure 14 Ma...

Page 19: ...rol source Motor stop from the keypad Up Down Up and Down arrows Move either up or down a menu list to select the desired menu item Editing a parameter bit by bit while the active digit is scrolled In...

Page 20: ...le edit mode when this parameter can be written Enter parameter group mode Enter parameter mode from group mode Main keypad display The main keypad LCD display indicates the status of the motor and th...

Page 21: ...ic Settings P2 2 Digital Input P2 3 Preset Speed P2 4 AI Settings P3 Outputs P3 1 RO1 Function P3 3 Analog Output P4 Drive Control P4 1 Basic Settings P5 Motor Control P5 1 Basic Settings P6 Protectio...

Page 22: ...ith the control keypad it is possible to control the speed of a motor to supervise the state of the equipment and to set the frequency converter s parameters Figure 17 Remote keypad and display Increa...

Page 23: ...his button more than 2 seconds in any page Hold Stop and Back Reset for 5 seconds to return drive to factory default At Main Menu page pressing Back Reset takes the user to the Default page Local Remo...

Page 24: ...conds in any page This button is used in the parameter edit mode to save the parameter setting To confirm the start up list at the end of the Start Up Wizard To confirm the comparison item in paramete...

Page 25: ...ready or does not have a signal FIM is displayed to indicate it is in Fire Mode and the drive is in a Run state TFM is displayed when in the Fire Mode Test Mode and the drive is in a Run State FWD RE...

Page 26: ...ADJUSTABLE FREQUENCY DRIVES PUB53696 August 2020 www eaton com Menu navigation remote keypad This section provides basic instruction on navigating each section in the menu structure from the remote ke...

Page 27: ...be prompted to enter a password before application changes parameter value changes or password changes By default the password function is not in use If you want to activate the password change the va...

Page 28: ...value on the rating plate of the motor P1 9a Motor nominal voltage ID 487 Minimum value 180 V Maximum value 690 V Default value 487 V Description Motor nominal nameplate base voltage Find this value o...

Page 29: ...ency Accel Time 1 Decel Time 1 t1 t2 Min Frequency P1 13b Remote control place ID 135 Minimum value N A Maximum value N A Default value 0 Options 0 IO terminal 1 Fieldbus or 3 Keypad Description Selec...

Page 30: ...ight By default the password function is not in use If you want to activate the password change the value of this parameter to any number between 1 and 9999 To deactivate the password reset the parame...

Page 31: ...scaling inversion offset and range Selectable analog output function PID control Start source local remote control function Reference source Flying start Volts per Hertz control Real time clock funct...

Page 32: ...ound Analog input 1 common ground 10 GND I O signal ground I O ground for reference and control 11 AO1 Analog output 1 Output frequency Shows output frequency to motor 0 60 Hz 4 mA to 20 mA 12 GND I O...

Page 33: ...nimum value Hz Maximum value Hz Default value Hz Description Reference frequency Hz M1 3 Motor speed ID 2 Minimum value rpm Maximum value rpm Default value rpm Description Motor output speed rpm M1 4...

Page 34: ...value V Description Keypad potentiometer measured value Vdc DM1 PRO only M2 3 Analog output ID 25 Minimum value Varies Maximum value Varies Default value Varies Description Analog output 1 measured va...

Page 35: ...lue then by going up and down Table 9 Operate mode O Code Parameter Min Max Unit Default ID Note O1 Output frequency Hz 1 O2 Freq reference Hz 24 O3 Motor speed rpm 2 O4 Motor current A 3 O5 Motor tor...

Page 36: ...from maximum frequency to zero frequency P1 6a Motor nom current ID 486 Minimum value DriveNomCurrCT 1 10 A Maximum value DriveNomCurrCT 2 A Default value DriveNomCurrCT A Description Motor nameplate...

Page 37: ...ped b Parameter value will be set to be default when changing macros Table 11 Inputs Cont P2 1 Basic settings P2 1 3ab IO terminal Start Stop logic ID 143 Minimum value N A Maximum value N A Default v...

Page 38: ...DIN1 and start reverse DIN2 signals are active simultaneously the start forward signal DIN1 has priority 1 P3 2 DI closed contact start open contact stop P3 3 DI closed contact reverse open contact fo...

Page 39: ...gic Start Stop ID191 Start Signal 2 DigIN 2 ID143 StartStopLogic Forward Reverse 15 3 Three wire connection pulse control P3 2 DI changes from open to closed start pulse P3 3 DI changes from closed to...

Page 40: ...no action 1 IO terminal start signal 1 when the control source is set to IO terminal this input when closed will perform the action defined by P2 1 3 2 IO terminal start signal 2 when the control sou...

Page 41: ...nimum value 0 00 Hz Maximum value MaxFreq Hz Default value 35 00 Hz Description Preset speed is selected with digital inputs using a binary input P2 4 AI settings P2 4 1 AI mode ID 222 Minimum value N...

Page 42: ...un drive is running 3 Fault drive is faulted 4 Fault invert drive is not faulted 5 Warning drive has a warning message 6 Reverse drive is outputting reverse phase rotation 7 At speed output frequency...

Page 43: ...ypad reference value P4 1 3b Keypad stop ID 114 Minimum value N A Maximum value N A Default value 1 Options 0 Enabled keypad operation In this mode the keypad stop will only operate when the control s...

Page 44: ...the acceleration and deceleration ramps can be smoothed with these parameters Setting a value of 0 00 seconds gives a linear ramp shape that causes acceleration and deceleration to react immediately...

Page 45: ...int and weakening point A programmable V Hz curve can be used if the other settings do not satisfy the needs of the application 3 Linear with flux optimization the drive starts to search for the minim...

Page 46: ...motor not the drive s nominal output current The motor s nominal current is the current that the motor can withstand in direct on line use without being overheated If you change the parameter nominal...

Page 47: ...ing 2 Fault or 3 Warning preset frequency P6 2 13 Description This parameter defines the function of the PI feedback analog input loss response If the AI feedback is lost based off the programed AI fe...

Page 48: ...ros Table 16 PI Controller Cont P7 1 Basic settings P7 1 1b PI control gain ID 1294 Minimum value 0 00 Maximum value 200 00 Default value 100 00 Description Defines the gain of the PI Controller It ad...

Page 49: ...7 1 4b PI process unit minimum ID 1298 Minimum value 99999 99 varies Maximum value PID1_ProcessUnitMax varies Default value 0 00 varies Description Defines the minimum process unit value P7 1 5b PI pr...

Page 50: ...setpoint value the drive uses This can either be an internal preset value keypad setpoint analog signal or fieldbus message P7 2 2 2a PI setpoint 1 sleep enable ID 1315 Minimum value N A Maximum valu...

Page 51: ...m cycle time ID 1843 Minimum value 0 00 s Maximum value 3 600 00 s Default value 300 00 s Description Defines the maximum time for sleep over cycle checking a Parameter value can only be changed after...

Page 52: ...Minimum value N A Maximum value N A Default value 0 Options 0 Only in fieldbus control mode When fieldbus is the control place and fieldbus fault is active the drive will fault on loss of communicatio...

Page 53: ...ion for BACnet MSTP communication P11 3 8 MSTP maximum master ID 1537 Minimum value 1 Maximum value 127 Default value 127 Description Defines the maximum number of masters that can establish connectio...

Page 54: ...eldbus 2 Mixed interface 4 NET local on fault or 5 Dual mode Description PNU928 which specifies the control priority of the device for cyclic communication P11 5 3 Fault situation counter ID 2632 Mini...

Page 55: ...um value N A Default value N A Description Reads the current active IP address P12 1 3 Active subnet mask ID 1509 Minimum value N A Maximum value N A Default value N A Description Reads the current ac...

Page 56: ...TCP unit identifier number ID 610 Minimum value N A Maximum value N A Default value 1 Description Unit identifier unit value for modbus TCP P12 3 4 Modbus TCP protocol status ID 612 Minimum value N A...

Page 57: ...AC2 47811 BAC3 47812 BAC4 47813 BAC5 47814 BAC6 47815 BAC7 47816 BAC8 47817 BAC9 47818 BACA 47819 BACB 47820 BACC 47821 BACD 47822 BACE or 47823 BACF Description Defines the BACnet UDP port number P12...

Page 58: ...sponse will occur Description Defines the fieldbus fault condition for BACnet IP communication P12 5 9a BACnet IP instance number ID 1742 Minimum value 0 00 Maximum value 4 194 302 Default value 0 Des...

Page 59: ...you to reload the factory default parameter values and to store and load two customized parameter sets P13 1 4 Up to keypad ID 620 Minimum value N A Maximum value N A Default value N A Options 0 No o...

Page 60: ...timeout time setting defines the time after which the keypad display returns to the Default Page Note If the default page value is 0 the timeout time setting has no effect P13 2 5 Contrast adjust ID 6...

Page 61: ...isplay three actual monitored values at the same time This parameter determines if the operator is allowed to replace the values monitored with other values P13 5 3 Keypad lock PIN ID 75 Minimum value...

Page 62: ...Over voltage Fault The DC link voltage has exceeded the limits defined Too short a deceleration time Brake chopper is disabled High overvoltage spikes in supply Start stop sequence too fast Make decel...

Page 63: ...e change Warning Power board or option card change Alarm will reset 38 Device added Warning Power board or option board added Device is ready for use Old parameter settings will be used 39 Device remo...

Page 64: ...action Check RS485 communication wiring Verify drive parameters are set correctly Check BACnet master configuration programming to verify proper addressing 86 Fieldbus fault Fault Configurable Loss o...

Page 65: ...ot stable Check why the drive sleeps and wakes up frequently 118 Broken pipe Warning Configurable PID feedback is less than broken pipe level and the drive output frequency is more than broke pipe fre...

Page 66: ...64 Step 6 Faults and warning codes POWERXL DM1 SERIES ADJUSTABLE FREQUENCY DRIVES PUB53696 August 2020 www eaton com Notes...

Page 67: ...65 POWERXL DM1 SERIES ADJUSTABLE FREQUENCY DRIVES PUB53696 August 2020 www eaton com Notes...

Page 68: ...hing people do Technology transportation energy and infrastructure these are things the world relies on every day That is why Eaton is dedicated to helping our customers find new ways to manage electr...

Reviews: