Step 5 - Standard application
POWERXL DM1 SERIES ADJUSTABLE FREQUENCY DRIVES
PUB53696—August 2020 www.eaton.com
Table 10. Parameters (Cont.).
P1.12
ab
Local reference
ID 136
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = AI;
1 = drive ref. pot;
4 = maximum frequency;
6 = keypad; or
7 = fieldbus ref.
Description:
Defines the signal location for the speed reference in local mode.
P1.13
b
Remote control place
ID 135
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = IO terminal;
1 = fieldbus; or
3 = keypad.
Description:
Defines the signal location for the start command in remote mode. I/O terminals would be from the digital hard-wired inputs or keypad
for Start/Stop buttons on the drive. Keypad display will indicate which mode is selected.
P1.14
ab
Remote reference
ID 137
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = AI;
1 = drive reference pot;
4 = maximum frequency;
6 = keypad; or
7 = fieldbus reference.
Description:
Defines the signal location for the speed reference in remote mode.
a
Parameter value can only be changed after the drive has stopped.
b
Parameter value will be set to be default when changing macros.
Table 11. Inputs (Cont.).
P2.1 - Basic settings.
P2.1.3
ab
IO terminal Start/Stop logic
ID 143
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Forward - reverse: maintained input on start signal 1 to run forward and a maintained signal on start signal 2 for reverse.
1 = Start - reverse: maintained input on start signal 1 to run forward and a maintained signal on start signal 2 for reverse.
2 = Start - enable: maintained input on start signal 1 to run forward and a maintained signal on start signal 2 to enable the drive to run.
3 = Start pulse - Stop pulse: used for three wire operation. Start signal 1 uses a normally open start and start signal 2 uses a normally
closed stop.
Description:
Defines the functionality for start signal 1 and start signal 2. By default, start signal 1 is DI1 and start signal 2 is DI2.
0 =
P3.2: DI closed contact = start forward P3.3: DI closed contact = start reverse. This would be considered 2-wire control with
either a contact used on the start FWD or start REV commands. When contacts open, the motor stops.
24V+
DIN1
20
DIN2
21
CMA
24
GND
12
ID190 - Start Signal: DigIN:1 ID143 Start Stop Logic: Start Forward
ID191- Start Signal 2: DigIN:2 ID143 Start Stop Logic: Start Reverse
15
.