Instruction Leaflet IL040016EN
Effective March 2014
PowerXL DG1 Series VFD
EATON
www.eaton.com
5
Mounting—Montaje—Montage—Montaggio—Montering—
ȉȠʌȠșȑIJȘıȘ
—Montagem—Asennus—
Montáž—Paigaldamine—Felszerelése—
Mont
Ɨ
ža
—Montavimas—
Monta
Ī
—Montaža—
Ɇɨɧɬɚɠ
—
Montarea—
Ɇɨɧɬɚɠ
—
ᆹ㻵
Notes
1
Minimum clearances A and B for drives with Type 12 (IP54) enclosure is 0 mm (in).
2
kW ratings are at 400V / 50 Hz.
The above guidelines apply unless testing has been completed to validate a design outside of these recommendations.
3
FR6 and 575 Vac available in 2015.
Frame
Size
Voltage
hp (CT/I
H
)
kW
2
Amperes
A
1
In (mm)
B
1
In (mm)
C
In (mm)
D
In (mm)
Cooling Air
Required
CFM (m
3
/h)
FR1 230
Vac
0.75–3
0.55–2.2
3.7–11 0.79
(20)
0.79
(20)
3.94
(100)
1.97
(50)
22
(38)
480 Vac
1–5
0.75–3.7
2.2–7.6
575 Vac
3
2–5
1.5–3.7
3.3–7.5
FR2 230
Vac
4–7.5 3–5.5 12.5–25 1.18
(30)
1.18
(30)
6.30
(160)
2.36
(60)
55
(94)
480
Vac 7.5–15 5.5–11 12–23
575 Vac
3
7.5–15
5.5–11
10–18
FR3 230
Vac
10–15 7.5–11
31–48 1.97
(50)
1.97
(50)
7.87
(200)
3.15
(80)
126
(214)
480
Vac
20–30 15–22 31–46
575 Vac
3
20–30
15–22
22–34
FR4 230
Vac
20–30 15–22 61–88 3.15
(80)
3.15
(80)
11.81
(300)
3.94
(100)
153
(260)
480
Vac
40–60 30–45 61–87
575 Vac
3
40–60
30–45
41–62
FR5 230
Vac
40–60 30–45 114–170 3.15
(80)
3.15
(80)
11.81
(300)
7.87
(200)
366
(622)
480 Vac
75–125
55–90
105–170
575 Vac
3
75–125
55–90
80–125
FR6
3
230 Vac
75–100
55–75
211–261
3
3
3
3
3
480 Vac
150–200
110–150
205–261
575 Vac
3
150–200
110–160
144–208
A
C
D
B
B
A