EtherNet/IP On-Board Communications
PowerXL DG1 Series VFD
MN040010EN—May 2014 www.eaton.com
39
Process Data In (Master to Slave)
Control word, Reference and Process Data are used with
different PowerXL applications as follows.
Table 66. Standard and Multi-Pump
Table 67. Multipurpose Control
Table 68. PID Control
Data
Value
Data Type
Unit
Scale
Default
FBFixedControlWord
Start/Stop/Fault reset Command
UINT
—
—
—
Reference
Speed Reference
UINT
%
0.01%
0
PD1–PD8
Not used
—
—
—
—
Data
Value
Data Type
Unit
Scale
Default
FBFixedControlWord
Start/Stop/Fault reset Command
UINT
—
—
—
Reference
Speed Reference
UINT
%
0.01%
0
Process Data IN1
Torque Reference
UINT
%
0.10%
0
Process Data IN2
Reference for PID1 controller
UINT
%
0.01%
0
Process Data IN3
Actual Value 1 to PID1 controller
UINT
%
0.01%
0
Process Data IN4
Actual Value 2 to PID1 controller
UINT
%
0.01%
0
Process Data IN5
Reference for PID2 controller
UINT
%
0.01%
0
Process Data IN6
Actual Value 1 to PID2 controller
UINT
%
0.01%
0
Process Data IN7
Actual Value 2 to PID2 controller
UINT
%
0.01%
0
Process Data IN8
Not used
—
—
—
—
Data
Value
Data Type
Unit
Scale
Default
FBFixedControlWord
Start/Stop/Fault reset Command
UINT
—
—
—
Reference
Speed Reference
UINT
%
0.01%
0
Process Data IN1
Not used
—
—
—
—
Process Data IN2
Reference for PID1 controller
UINT
%
0.01%
0
Process Data IN3
Actual Value 1 to PID1 controller
UINT
%
0.01%
0
Process Data IN4
Actual Value 2 to PID1 controller
UINT
%
0.01%
0
Process Data IN5
Reference for PID2 controller
UINT
%
0.01%
0
Process Data IN6
Actual Value 1 to PID2 controller
UINT
%
0.01%
0
Process Data IN7
Actual Value 2 to PID2 controller
UINT
%
0.01%
0
Process Data IN8
Not Used
—
—
—
—
Summary of Contents for PowerXL DG1 Series VFD
Page 1: ...PowerXL DG1 Series VFD Communication Manual Effective May 2014 New Information...
Page 2: ......
Page 148: ...Appendix A Parameter ID List 134 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Page 149: ...Appendix A Parameter ID List PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com 135...
Page 150: ...Appendix A Parameter ID List 136 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Page 151: ......