References are 16-bit words containing a sign bit and a 15-bit
integer. A negative reference is formed by calculating the 2’s
complement from the corresponding positive reference.
Table 111. References
Actual Values
Actual values are 16-bit words containing information on the
operation of the drive. The function to be monitored are
selected by a drive parameter. The scaling of the integers
sent to the master as Actual Values depends on the selected
function.
14
1
Device Specific
N/A
0
Device Specific
N/A
15
1
Device Specific
N/A
0
Device Specific
N/A
Table 110. Application Status Word PROFIdrive, continued
Bit
Value
Significance
Comments
SN
N2 Data Type
Hex
N2 Data Type
Decimal
N2 Data Type
Percentage
Frequency in
Decimal
1
4000
16384
100
50
2
3000
12288
74
37
3
2000
8192
50
25
4
1000
4096
24
12
5
0
0
0
0
6
F000
61440
–25
12
7
E000
57344
–50
25
8
D000
53248
–75
37
9
C000
49152
–100
50
Summary of Contents for PowerXL DG1 Series VFD
Page 1: ...PowerXL DG1 Series VFD Communication Manual Effective May 2014 New Information...
Page 2: ......
Page 148: ...Appendix A Parameter ID List 134 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Page 149: ...Appendix A Parameter ID List PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com 135...
Page 150: ...Appendix A Parameter ID List 136 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Page 151: ......