Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications
20
Powerware 9910-E30
2100 Watt/3000 VA, 208-240 Vac UPS
Features and Benefits
•
Isolates connected equipment from all incoming power problems to provide
the highest degree of protection with rugged, online design
•
Conserves valuable rack space with compact 2U form factor
•
Significantly increases battery service life and gives you advanced warning
of the end of useful battery life with ABM technology
•
Prolongs backup time with 2U Extended Battery Modules
•
Optional interface/communication cards expand control of application
•
Tested and approved by IBM to assure out-of-box usability
•
Includes premium IBM warranty
E30 Model Guide
Model
Number
IBM
Number
Power Out
(Watts/VA)
Input
Connection
Output Connections
Dimensions
(HxWxD, in/mm)
Unit
Weight
(lb/kg)
208-240 Vac; 50/60 Hz auto-sensing
9910-E30
42R8069
2100/3000
Varies
1
(4) IEC-320-C13,
(1) IEC-320-C19
3.5 x 17 x 19.4/
89 x 432 x 493
34/15
9910-E30
+ FC 6570
4
42R4 320
2100/3000 Varies
(4) 6-20R,
(2) 5-20R,
(2) L6-15R
7 x 17 x 19.4/
178 x 432 x 493
68/31
Extended Battery Module
9910-6644
42R8071
— — —
3.5 x 17 x 19.4/
89 x 432 x 493
65/29.5
1. E30 input (mains) connection varies by country. Optional input (mains) connection type IEC-309 P+N+G 32 Amp (FC
2976) available. See Line Cord Options table.
E30 Battery Runtimes Chart (in Minutes)
Load
UPS Internal Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
875W/1250 VA
16
57 90 150
200
1050W/1500 VA
13
55 72 120
160
1750W/2000 VA
7
28 48 68
88
2100W/3000 VA
5
25 38 54
70
Note:This guide provides typical application information. Battery times are approximate and may vary with equipment,
configuration, disk access, battery age, temperature, etc.
E30 UPS Rear Panel