![Eaton Powerware 9910-E64 Handbook Download Page 19](http://html1.mh-extra.com/html/eaton/powerware-9910-e64/powerware-9910-e64_handbook_4274884019.webp)
Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications
18
P16 Technical Specifications*
Electrical Input
Nominal Voltage
230 Vac
Input Voltage Ranges
150–288V (without using batteries)
Input Power Factor
>0.95 typical
Frequency 50/60
Hz,
auto-sensing
Frequency Range
46–65 Hz
Electrical Output
On Utility Voltage Regulation
±3% of nominal
On Battery Voltage Regulation
±3% of nominal
Efficiency
89–92% depending on load
Frequency Regulation
±3 Hz online; ±1 Hz on battery
Load Crest Factor
3 to 1 ratio
Communications
Communication Port
Relay port standard; optional X-Slot cards available
Communication Cable
6-ft AS/400 communication cable included
Battery
UPS Internal Battery Type
9 Ah, sealed, maintenance-free lead-acid
UPS Internal Battery Type
9 Ah, sealed, maintenance-free lead-acid
Battery Runtime
See Battery Runtime Chart
Battery Replacement
Hot-swappable UPS internal batteries and external batteries modules
Recharge Time
<2 hours from complete discharge to 80% capacity at nominal line conditions
Start-On-Battery
Allows start of UPS without utility input
General
Topology
True online, double-conversion
Diagnostics
Full system self-test on power up
UPS Bypass
Automatic on overload or UPS failure
Dimensions and Weight
See Model Guide
Environmental and Safety
Ambient Operating Temperature
0°C to 40°C (32°F to 104°F) 0°C to 25°C (32°F to 77°F)
Heat Dissipation
645 BTU/hr maximum
Leakage Current
<0.6 mA typical
Storage Temperature
0°C to 25°C (32°F to 77°F)
Relative Humidity
0% to 90% noncondensing
Audible Noise
<45 dBA typical
Safety Markings
CSA, VDE, CE, S, D, N, FI, B NOM, R
EMC Compliance
FCC Class B and VCCI Class II, 3000 FCC Class A
Surge Suppression
IEEE/ANSI C62.41 Category B (formerly 587)
REPO Port
Meets NEC code 645-11 intent and UL requirements
Network Transient Protector
In and out jack for models only or 10BaseT network cable protection. UL497A tested
* Due to continuing product improvement programs, specifications subject to change without notice.