Table 17. Model Specifications for Universal Power Modules (XXXXX-Model/03 and ASY-0674) (continued)
Nine- and Twelve-Slot Cabinet
CAUTION
Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
Heat
Dissipation
Recommended
Input Service
Output Current for
200/208/220/230/240V
Input Current for
200/208/220/230/240V
UPS
kVA/Watts
Optional
Chargers
4
9/6300
102A**
45/43.5/42/39/37.5A
125A
1995W
(6.75 kBTU/hr)
0
12/8400
56/54/52/50/48A
60/58/56/52/50A
80A
1145W
(3.90 kBTU/hr)
1
12/8400
72/70/68/66/64A
60/58/56/52/50A
100A
1430W
(4.88 kBTU/hr)
2
12/8400
88/86/84/82/80A
60/58/56/52/50A
125A
1720W
(5.85 kBTU/hr)
3
12/8400
102/102/100/98/96A**
60/58/56/52/50A
125A
1995W
(6.75 kBTU/hr)
0
15/10500
70/67.5/65/62.5/60A
75/72.5/70/65/62.5A
100A
1430W
(4.88 kBTU/hr)
1
15/10500
86/83.5/81/78.5/76A
75/72.5/70/65/62.5A
125A
1720W
(5.85 kBTU/hr)
2
15/10500
102/99.5/97/94.5/92A**
75/72.5/70/65/62.5A
125A
1995W
(6.75 kBTU/hr)
0
18/12600
84/81/78/75/72A
90/87/84/78/75A
125A
1720W
(5.85 kBTU/hr)
1
18/12600
100/97/94/91/88A**
90/87/84/78/75A
125A
1995W
(6.75 kBTU/hr)
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional
redundant power module.
** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external
battery cabinet XXXXX-Model/Batt4.