OPERATION
Eaton 5125 Tower UPS (1000–2200 VA) User's Guide
S
05147304 Rev C
www.eaton.com/powerquality
30
Turning the UPS Off
NOTE
Pressing the Off
button while the UPS is in Battery mode causes the UPS to shut
down immediately.
To turn off the UPS:
1.
Prepare your equipment for shutdown.
2.
Press and hold the Off
button until the long beep ceases
(approximately five seconds). The
indicator begins to flash. The
UPS transfers to Standby mode (if utility power is available) and
removes power from your equipment.
3.
Unplug the UPS.
If you do not unplug the UPS, it remains in Standby mode.
Initiating the Self‐Test
NOTE
The batteries must be fully charged to perform the self‐test.
Press and hold the
button for three seconds to initiate the self‐test.
During the test, individual indicators illuminate as various parts of the
UPS are checked. If the alarm beeps or a UPS alarm indicator stays on,
see Table 9 on page 54.