UPS Installation Plan and Unpacking
3-32
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual
P-164000501—Rev 09
www.eaton.com/powerquality
Table 3-23. 415V Power Cable Conduit Requirements
UPS Model
Voltage
Terminal
Number of Wires
in Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Eaton 9395P-900/825
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
8
3
8
AC Input to Bypass and Output
(A, B, C, Ground)
6
3
6
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
10
3.5
5
Eaton 9395P-900/750
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
8
3
8
AC Input to Bypass and Output
(A, B, C, Ground)
6
3
6
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
8
3.5
4
Eaton 9395P-900/675
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
6
3
6
AC Input to Bypass and Output
(A, B, C, Ground)
5
3
5
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
8
3.5
4
Eaton 9395P-900/600
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
6
3
6
AC Input to Bypass and Output
(A, B, C, Ground)
5
3
5
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
8
3
8
Eaton 9395P-900/550
Eaton 9395P-900/500
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
5
3
5
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
4
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
6
3
6
Eaton 9395P-900/450
See Note 1
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output
(A, B, C, Ground)
3
3
3
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
6
3
6
All models
DC
(Separate Battery -
per UPM)
Battery
(Positive, Negative, Ground)
7
4
1
NOTE 1
V
Because of the future upgradability to a fully rated 415V 825 kVA UPS with the addition of the FI-UPM, these conduit sizes are specified
for an 825 kVA UPS.
NOTE 2
V
Bypass conduit data is not applicable to IOM configurations.
Battery Conductor Routing
Summary of Contents for Power Xpert 9395P-900 Series
Page 2: ......
Page 8: ...This page intentionally left blank...
Page 33: ...Section I Installation...
Page 34: ......
Page 139: ...Section II Operation...
Page 140: ......
Page 231: ......
Page 232: ...P 164000501 6 P 164000501 9...