UPS Installation Plan and Unpacking
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
www.eaton.com/powerquality
3-37
Table 3-28. Recommended DC Input Battery Disconnect Ratings – Separate Battery
UPS Model
Input Rating
(each UPM)
480V
Eaton 9395P-900/900*
Eaton 9395P-900/600*
800A
Eaton 9395P-900/900
Eaton 9395P-900/825
Eaton 9395P-900/750
Eaton 9395P-900/675
Eaton 9395P-900/600
Eaton 9395P-900/550
Eaton 9395P-900/500
Eaton 9395P-900/450
700A
NOTE Because of the future upgradability to a fully rated 900 kVA UPS with the addition of the
FI-UPM, these breaker sizes are specified for a 900 kVA UPS.