UPS SYSTEM INSTALLATION
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
4-33
4.9.3
X-Slot Connections
NOTE
LAN drops for use with X-Slot cards must be provided by the customer.
NOTE
When installing external wiring to X-Slot cards, conduit must be installed to the UPS cabinet. When
installing internal wiring to X-Slot terminals, route the wiring through the internal opening in the X-Slot
communication bay.
For installation and setup of an X-Slot card, contact an Eaton service representative
(see page 1-10).
To install wiring to connections:
1.
If not already installed, install the LAN drops.
2.
Unfasten the front door latch and swing the door open (see Figure 4‐1).
3.
Remove the right interface entry conduit landing plate to drill or punch holes (see
Figure 4‐16).
4.
Reinstall the interface entry plate and install the conduit.
5.
Route and install the LAN and other cables to the appropriate X-Slot cards. See
Figure 4‐21 and Figure 4‐27 for X-Slot communication bay locations.
6.
Close the door and secure the latch.
7.
Refer to the manual supplied with the X-Slot card for operator instructions.
X-Slot Communication Bay 1
X-Slot Communication Bay 2
X-Slot Communication Bay 3
X-Slot Communication Bay 4
Figure 4‐27. X-Slot Communication Bays