Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06
77
Table 20. Pull-Chain Wiring Terminations with MOBs
From
To
Function
UPS 1 CAN Bridge Card J3–1 (Alarm)
MOB 1 Aux 1 NC
MOB Open Alarm
UPS 1 CAN Bridge Card J3–2 (Alarm
Return)
MOB 1 Aux 1 Com
UPS 1 TB2–1 (Pull Chain)
MOB 1 Aux 2 NO
Pull Chain
UPS 2 TB2–2 (Pull Chain Common)
UPS 2 TB2–2 (Pull Chain Common)
Pull Chain Common
UPS 2 CAN Bridge Card J3–1 (Alarm)
MOB 2 Aux 1 NC
MOB Open Alarm
UPS 2 CAN Bridge Card J3–2 (Alarm
Return)
MOB 2 Aux 1 Com
UPS 2 TB2–1 (Pull Chain)
MOB 2 Aux 2 NO
Pull Chain
UPS 2 TB2–2 (Pull Chain Common)
UPS 3 TB2–2 (Pull Chain Common)
Pull Chain Common
UPS 3 CAN Bridge Card J3–1 (Alarm)
MOB 3 Aux 1 NC
MOB Open Alarm
UPS 3 CAN Bridge Card J3–2 (Alarm
Return)
MOB 3 Aux 1 Com
UPS 3 TB2–1 (Pull Chain)
MOB 3 Aux 2 NO
Pull Chain
UPS 3 TB2–2 (Pull Chain Common)
UPS 4 TB2–2 (Pull Chain Common)
Pull Chain Common
UPS 4 CAN Bridge Card J3–1 (Alarm)
MOB 4 Aux 1 NC
MOB Open Alarm
UPS 4 CAN Bridge Card J3–2 (Alarm
Return)
MOB 4 Aux 1 Com
UPS 4 TB2–1 (Pull Chain)
MOB 4 Aux 2 NO
Pull Chain
MOB 1 Aux 2 Com
MOB 2 Aux 2 Com
Pull Chain MOB Common
MOB 2 Aux 2 Com
MOB 3 Aux 2 Com
MOB 3 Aux 2 Com
MOB 4 Aux 2 Com
55..33
IInnssttaalllliinngg aann O
Oppttiioonnaall R
Reem
moottee M
Moonniittoorr P
Paanneell IIII
To install RMP II wiring:
1.
Verify the UPS system is turned off and all power sources are removed. See
for shutdown instructions.
2.
Perform the procedure listed in paragraph
Installing an Optional Powerware Hot Sync CAN Bridge Card
NOTE
If mounting to a hollow wall, secure the enclosure to a wood or metal stud within the
wall. Do not use hollow wall anchors.