Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
41
Table 18. Recommended Input Circuit Breaker Ratings (Continued)
UPS Model
Input Rating
Load Rating
400V
480V
Power Xpert 9395-825/450
Power Xpert 9395-825/500
Power Xpert 9395-825/550
See Note
80% Rated
2000A
1600A
100% Rated
1600A
1200A
NOTE Because of the future upgradability to a fully rated 825 kVA UPS with the addition of the FI-UPM, these breaker sizes are
specified for an 825 kVA UPS.
Table 19. Separate Rectifier Input Recommended Input Circuit Breaker Ratings
UPS Model
Input Rating
Load Rating
400V
480V
Power Xpert 9395-825/650
Power Xpert 9395-825/750
Power Xpert 9395-825/825
80% Rated
600A
500A
100% Rated
500A
400A
Power Xpert 9395-825/450
Power Xpert 9395-825/500
Power Xpert 9395-825/550
80% Rated
600A
500A
100% Rated
500A
400A
NOTE Because of the future upgradability to a fully rated 825 kVA UPS with the addition of the FI-UPM, these breaker sizes are
specified for an 825 kVA UPS.
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings
from
in accordance with NEC ANSI/NFPA 70.
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values
for AC output to critical load shown in
. The recommended line-to-line load
unbalance is 50% or less.
Bypass and output overcurrent protection and bypass and output disconnect switches are to be provided by
the customer. Module Output Breakers (MOBs) are to be provided by the customer.
lists the
recommended rating for bypass, output, and MOB circuit breakers. Bypass breakers are not required for IOM
configurations.