To use the REPO pushbutton switch:
1.
Firmly push the red pushbutton until it locks into place. The switch latches into the activated state (see
The input, output, and bypass backfeed contactors open, the battery breaker or disconnect is tripped, and
the power module is turned off immediately, without asking for verification on all UPSs.
Do not attempt to restart the system after the REPO until the cause of the shutdown has been identified and
cleared.
2.
To deactivate the REPO switch in preparation for restarting the UPS, insert the supplied key and rotate
clockwise until the red pushbutton releases (see
). To remove the key, rotate the key back to
the vertical position.
3.
Restart the UPSs by by following the procedure in paragraph
Starting the Distributed Bypass System in Online Mode
or
Starting the Distributed Bypass System in Bypass Mode
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
77..55
C
Coolloorr TToouucchhssccrreeeenn C
Coonnttrrooll P
Paanneell
This section describes how the various screens are used to control and monitor UPS operation.
shows the location of the color touchscreen control panel on the front door of the UPS. Descriptions of the
control panel functions follow. For a description of the UPS control panel functions, see paragraph