36
Cabinet dimensions
Instruction manual
IM1002004E September 2015 www.powerquality.eaton.com
Cabinet dimensions
Table 6. Power-Sure 700 unit cabinet sizes
kVA
rating
Bypass
Metering
Cabinet size
H x W x D (in)
BTUs/Hr
Weight (Lb)
10
Yes
No
30.2 x 22.2 x 29.0
1,025
440
10
Yes
Yes
44.2 x 22.2 x 29.0
1,205
520
15
Yes
No
30.2 x 22.2 x 29.0
1,540
465
15
Yes
Yes
44.2 x 22.2 x 29.0
1,540
700
25
Yes
Yes
44.2 x 22.2 x 29.0
2,560
700
30
Yes
Yes
44.2 x 22.2 x 29.0
3,090
720
45
Yes
Yes
44.3 x 45.9 x 29.0
4,600
950
50
Yes
Yes
66.0 x 29.0 x 35.5
7,332
1,176
75
Yes
Yes
76.0 x 34.4 x 35.5
9,514
1,575
100
Yes
Yes
76.0 x 34.4 x 35.5
11,833
2,014
125
Yes
Yes
76.0 x 34.4 x 35.5
14,748
2,137
150
Yes
Yes
76.0 x 34.4 x 35.5
17,698
2,240
225
Yes
Yes
77.4 x 56.0 x 41.5
23,000
3,300
300
Yes
Yes
77.4 x 56.0 x 41.5
30,750
4,000
500
Yes
Yes
77.0 x 72.4 x 48.4
51,250
5,500
Manual bypass switch
The manual bypass switch is a break-before-make switch
located on the Power-Sure 700. The manual bypass switch
is used to bypass all power electronics in case of failure.
Bypass is standard on 50 kVA and larger units and an option
on 45 kVA and smaller units.
otes:
N
This switch may be added in the field.
Normal mode
With the switch in the normal position, the Power-Sure 700
will provide clean and regulated power to the critical loads.
The Power-Sure 700 should have the switch in the normal
position unless a failure has occurred.
These units are sold in accordance to Eaton
Selling Policy 25-000.