8
Instruction Leaflet
IL012002EN
Effective March 2013
Instruction Leaflet for Modbus Power Monitoring/
Metering Module (PM3) for FD, JG, and KD/LG
Circuit Breakers and Motor Circuit Protectors
EATON CORPORATION
www.eaton.com
Figure 10. PM3 Breaker Status Wiring Diagram (KD/LG PM3).
Breaker Status:
Breaker status is brought to the unit through a 5-pin Phoenix
RA-series connector, part number 1844249. Figure 10 shows the pin
assignments for this connector.
CAUTION
FOR WYE SYSTEM, A NEUTRAL IS REQUIRED TO BE CONNECTED TO THE
PM3 ON THE RIGHT PHOENIX CONNECTOR. IF NEUTRAL IS NOT AVAIL-
ABLE, THE METER WILL CALCULATE A VIRTUAL NEUTRAL BASED ON THE
PHASE-TO-PHASE RMS VOLTAGE. THE SYSTEM MUST BE BALANCED FOR
THIS TO BE ACCURATE.
Combination
Auxiliary/alarm
Switch Kit
Red
Bell
Alarm
Black
Blue
Aux
Alarm
Black
Red
Bell
Alarm
No Connect
V
Neutral
Earth
Ground
+24
VDC
DC Common
Com B
A