background image

IB01602046E

For more information visit: www.eaton.com

Instruction Booklet

Effective: July 2010

Page

 

13

2-Position Contactor Based 

Non-Automatic Transfer Switch

4.4 Power Cable Connections

Test all power cables prior to connection to the unit to ensure 

that the conductors or cable insulation have not been damaged 

while being pulled into position.

Power cables are to be connected to solderless screw type lugs 

located on the non-automatic transfer switch switching devices.  

Refer to the separate Customer Wiring Booklet supplied with the 

non-automatic transfer switch equipment for power termina-

tion.  Verify that the lugs supplied will accommodate the power 

cables being used.  Also verify that the cables comply with local 

electrical codes.  Standard non-automatic transfer switch equip-

ment, as supplied from the factory, will accommodate the wire 

sizes shown in Table 4.

Carefully strip the insulation from the power cables to avoid nick-

ing or ringing of the conductor strands.  Prepare the stripped con-

ductor termination end by cleaning it with a wire brush.  If 

aluminum conductors are used, apply an appropriate joint com-

pound to the clean conductor surface area.

Tighten the cable lugs to the torque identified on the label affixed 

to the door of the unit.

4.5 Wiring

Power sources, load conductors, and control wiring should be 

connected to locations as indicated in the Customer Wiring Book-

let supplied with the non-automatic transfer switch equipment.

Once the non-automatic transfer switch equipment has been 

installed and wired, perform the initial mechanical and electrical 

procedures as outlined in Section 6 to verify that the equipment 

is installed and operating properly.

Table 4. Transfer Switch Equipment Wire Sizes

  

WARNING

POWER CONDUCTORS MAY HAVE VOLTAGE PRESENT THAT CAN 

CAUSE SEVERE PERSONAL INJURY OR DEATH.  DE-ENERGIZE ALL 

POWER OR CONTROL CIRCUIT CONDUCTORS TO BE CONNECTED 

TO THE NON-AUTOMATIC TRANSFER SWITCH EQUIPMENT 

BEFORE BEGINNING TO WORK WITH THE CONDUCTORS AND/OR 

TERMINATING THEM TO THE EQUIPMENT.

  

CAUTION

USE OF CABLE LUGS NOT DESIGNED FOR THE NON-AUTOMATIC 

TRANSFER SWITCH MAY CAUSE HEATING PROBLEMS.

 

 

CAUTION

TO HELP PREVENT COMPONENT DAMAGE OR FUTURE MALFUNC-

TIONS, USE EXTREME CARE TO KEEP CONTAMINANTS OUT OF 

THE NON-AUTOMATIC TRANSFER SWITCH EQUIPMENT WHEN 

MAKING POWER CABLE CONNECTIONS.

  

CAUTION

RUN THE POWER CABLE THROUGH THE GUTTER SPACE PROVIDED 

TO THE RIGHT OR LEFT OF POWER PANEL.

 

WARNING

IMPROPER POWER CABLE CONNECTIONS CAN CAUSE EXCESSIVE 

HEAT AND SUBSEQUENT EQUIPMENT FAILURE.

  

WARNING

POWER CONDUCTORS AND CONTROL WIRING MAY HAVE VOLT-

AGE PRESENT THAT CAN CAUSE SEVERE PERSONAL INJURY OR 

DEATH.  DEENERGIZE ALL POWER OR CONTROL CIRCUIT CON-

DUCTORS BEFORE BEGINNING TO PERFORM ANY WIRING ACTIV-

ITY TO OR WITHIN THE NON-AUTOMATIC TRANSFER SWITCH 

EQUIPMENT.

CAUTION

ENSURE THE NON-AUTOMATIC TRANSFER SWITCH VOLTAGE IS 

SET CORRECTLY.  IT SHOULD BE THE SAME AS THE SOURCE 1 

AND SOURCE 2 LINE VOLTAGES.  OPERATING THE EQUIPMENT ON 

IMPROPER VOLTAGE CAN CAUSE EQUIPMENT DAMAGE.

TRANSFER SWITCH AMPERE RATING

WIRE SIZE RANGES

NUMBER OF CABLES PER PHASE

TERMINAL TEMPERATURE RATING °C (°F)

100

#14-2/0

1

75 (167)

200

#6-250 KCMIL

1

75 (167)

320

#4-600 KCMIL or (2) 1/0-250 KCMIL

1 or 2 - depending on wire size used

75 (167)

400

#4-600 KCMIL or (2) 1/0-250 KCMIL

1 or 2 - depending on wire size used

75 (167)

600

#2-600 KCMIL

2

75 (167)

Summary of Contents for NTCEC2X20400WRU

Page 1: ...utomatic Transfer Switch Instruction Booklet Description Page Introduction 2 Receiving Handling and Storage 6 Equipment Description 7 Installation and Wiring 11 Operation 16 Testing and Problem Solvin...

Page 2: ...llation application or main tenance activity please contact an authorized Eaton sales repre sentative or the installing contractor 1 1 1 Warranty and Liability Information No warranties expressed or i...

Page 3: ...ically electrical operation Conversely if con nected to Source 2 and Source 2 power source fails non auto matic transfer switch will remain connected to the Source 2 power source When Source 1 power s...

Page 4: ...ficant amount of relevant information that pertains to a particular piece of equipment The Catalog Number Identification Table Table 2 provides the required interpretation information An example is of...

Page 5: ...nection Re Transfer Re transfer is defined as a change of the load connection from the Source 2 to the Source 1 Source 1 Source 1 is the primary source normal source normal power source or normal Sour...

Page 6: ...dy for installation Once the top packaging is removed from the shipment the enclosure door can be opened A plastic bag of documents will be found in the enclosure usually attached to the inside of the...

Page 7: ...nd disconnect the load to and from the different power sources The power contactor is mechanically and electrically interlocked to prevent the two sets of main contacts from being closed simultaneousl...

Page 8: ...hown Connected to the 480 Vac Taps 3 4 Logic Panel The logic panel provides ability to transfer from Source 1 to Source 2 when Source 2 is at sufficient voltage and frequency Conversely it also provid...

Page 9: ...ontact This feature provides 1 dry form C contact that indicates the position of the Source 1 power switching device 15F Source 2 Position Indication Contact This feature provides 1 dry form C contact...

Page 10: ...480VAC by providing a low imped ance surge path to ground while supporting rated volt age It provides LED indication 3 6 Enclosure The rugged steel non automatic transfer switch enclosure is sup plie...

Page 11: ...on requires solidly mounting the enclosed unit and connecting power cables and auxiliary pilot circuits Physi cal mounting procedures and power cable connections are cov ered in this section All other...

Page 12: ...s securing the har ness to the inside of the door Carefully remove the hinge pins then the door from the enclosure Step 2 Install the required upper and lower mounting bolt anchors and the two upper m...

Page 13: ...lectrical procedures as outlined in Section 6 to verify that the equipment is installed and operating properly Table 4 Transfer Switch Equipment Wire Sizes WARNING POWER CONDUCTORS MAY HAVE VOLTAGE PR...

Page 14: ...ormers contained in a steel case mounted in the enclosure To change the voltage from the factory default 600 Vac follow the steps detailed below Step 1 Loosen the six screws securing the cover of the...

Page 15: ...inserting a small flathead screwdriver into the square tool hole with the flat surface of the screw driver against the back wall of the hole With a little bit of force push the screwdriver in on a sli...

Page 16: ...peration is accomplished by adding required indication lights and push buttons located on the front device panel to the operating mechanism of the 2 position contactor With the transfer switch connect...

Page 17: ...ddress etc 4 Company name 5 Name and position of individual representing company 6 Basic description of situation as it exists 7 Any results of problem solving steps taken and or readings taken Sectio...

Page 18: ...HIS EQUIPMENT DISCONNECT THE LINE POWER FROM THEN LOCK OUT IF POSSIBLE THE NEXT HIGHEST DISCONNECT DEVICE FAILURE TO FOLLOW THIS PROCEDURE COULD CAUSE SEVERE PERSONAL INJURY AND OR DEATH STEP ACTION a...

Page 19: ...tic Switch 480VAC 4 Pole Cat 68C8471G13 200A AG Switch up to 240VAC 2 Pole Cat 68C8471G01 200A AG Switch up to 240VAC 3 Pole Cat 68C8471G02 200A AG Switch up to 240VAC 4 Pole Cat 68C8471G03 400A Domes...

Page 20: ...ator Supply E1 E2 E3 For 4 pole transfer switches connect the load cables TN Source 1 or utility supply NN and Source 2 or generator supply EN Refer to Figure 22 for the location of all parts discusse...

Page 21: ...oltage on load terminals Step 5 Turn 2 position selector switch to Source 1 position and verify that Source 1 ON light should turn ON Step 6 Turn the Utility Source 1 power OFF Step 7 Start the genera...

Page 22: ...For more information visit www eaton com IB01602046E Instruction Booklet Page 22 Effective July 2010 2 Position Contactor Based Non Automatic Transfer Switch Notes...

Page 23: ...IB01602046E For more information visit www eaton com Instruction Booklet Effective July 2010 Page 23 2 Position Contactor Based Non Automatic Transfer Switch Notes...

Page 24: ...ION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Eaton be responsible to the purchaser or user in contract in tort including negligence strict liability or otherwise for any spec...

Reviews: