2
Type NR oil switch installation and operation instructions
INSTALLATION AND OPERATION INSTRUCTIONS
MN230008EN November 2016
Ratings and specifications
Table 1 . Electrical data (control)
Description
Rating
Nominal operating voltage (50/60 Hz only) (Vac)
120
240
Operating voltage range (Vac)
95 – 130
190 – 260
Closing-motor current (amp)
1.9
.7
Switch response time, opening (sec)
4.0
4.0
Switch response time, closing (sec)
0.5
0.5
Table 2 . Voltage and current ratings
Description
Standard
15 kV with
17" creepage
15 kV with
125 kV BIL
22 kV
Maximum Design Voltage, kV
15.0
15.0
15.0
22.0
Nominal Operating Voltage, kV
2.4-14.4
2.4-14.4
2.4-14.4
20.0
Basic Insulation Level (BIL), kV
95
95
125
125
60 Hertz withstand voltage, kV
Dry, one minute
Wet, ten seconds
35
30
35
30
42
36
60
50
Continuous current rating, Amps
200
200
200
60
Load interrupting ability (inductive), symmetric Amps
75-100% power factor
50-75% power factor
< 50% power factor
200
100
50A
200
100
100A
200
100
50A
60
60
60
Maximum capacitive current, amps (parallel bank-max)
200
200
200*
60*
High frequency transient current, Amps
12000
12000
12000
12000
Transient frequency, Hz
6000
6000
6000
6000
High frequency damping factor
.40 -.55
.40 -.55
.40 -.55
.40 -.55
Momentary rating, Amps asym.
9000
9000
9000
9000
Short time current Amps
1/2 second,sym.
1 second, sym.
6000
4500
6000
4500
6000
4500
6000
4500
Close and latch rating, Amps asym.
9000
9000
9000
9000
*The 125 kV BIL switch and the 22.0 kV switch are rated for single bank switching only.