MN04002001E
7
March 2006
Step 4 — Parameter Groups & Default Values (Continued)
30 — INPUTS
Modbus
Groups
Description
Range
Default
User
Settings
0100H
30.01
Minimum reference
value (0 – 10V)
0.0 to 10.0V
0.0
0101H
30.02
Maximum reference
value (0 – 10V)
0.0 to 10.0V
10.0
0102H
30.03
Invert reference
signal (0 – 10V)
00: Not inverted
00
01: Inverted
0103H
30.04
Minimum reference
value (4 – 20 mA)
0.0 to 20.0 mA
4.0
0104H
30.05
Maximum reference
value (4 – 20 mA)
0.0 to 20.0 mA
20.0
0105H
30.06
Invert reference
signal (4 – 20 mA)
00: Not inverted
00
01: Inverted
0106H
30.07
Potentiometer Offset
0.0 to 100.0%
0.0
0107H
30.08
Potentiometer Bias
Polarity
00: Positive, 01: Negative
00
0108H
30.09
Potentiometer Slope
0.1 to 300.0%
100.0
0109H
30.10
Potentiometer
Direction
00: Forward Motion Only
00
01: Reverse Motion Enable
010AH
30.11
Digital Input Terminal
(DI1, DI2)
01: DI1-FWD / STOP, DI2-REV / STOP
02
02: DI1-RUN / STOP, DI2-REV / FWD
03: DI1 - RUN momentary (NO), DI2 -
REV / FWD, DI3 - STOP momentary
(NC)
010BH
010CH
010DH
010EH
30.12
30.13
30.14
30.15
Digital Input Terminal
(DI3)
Digital Input Terminal
(DI4)
Digital Input Terminal
(DI5)
Digital Input Terminal
(DI6)
00: Not used
05
06
07
03
01: External Fault (NO)
02: External Fault (NC)
03: External Reset (NO)
04: External Reset (NC)
05: Multi-Speed 1
06: Multi-Speed 2
07: Multi-Speed 3
08: Jog
09: Second Acceleration/
Deceleration Time
10: Control Place: I/O Terminal
11: Control Place: Keypad
12: Control Place: Communication
13: Increase Speed during RUN
command
14: Decrease Speed during RUN
command
15: Forward/Reverse
16: Parameter Lock
17: Acceleration/Deceleration l
Prohibit
18: Run Enable
19: Base Block (NO)
20: Base Block (NC)
21: PID Disable
22: Run PLC Program
23: Pause PLC Program
24: Counter Trigger signal
25: Counter Reset
26: First/second Source of Master
Frequency
27: Increase speed during RUN or
STOP state
28: Decrease speed during RUN or
STOP state