Step 4 — Parameter Groups & Default Values (Continued)

50 — DRIVE CONTROL (Continued)

Modbus

Groups

Description

Range

Default

User

Settings

032AH

50.43

PID Set Point

0.0 to 400.0 Hz (100.0%)

0.0

032BH

50.44

PLC Operation Mode

00: Disable PLC performing

00

01: Execute one program cycle

02: Continuously execute program 
cycles

03: Execute one program cycle step 
by step 

04: Continuously execute program 
cycles step by step

032CH

50.45

PLC Forward/Reserve 
Motion

00 to 127

00

032DH

50.46

Time Duration of 1st 
Preset Speed

0 to 9999

0

032EH

50.47

Time Duration of 2nd 
Preset Speed

0 to 9999

0

032FH

50.48

Time Duration of 3rd 
Preset Speed

0 to 9999

0

0330H

50.49

Time Duration of 4th 
Preset Speed

0 to 9999

0

0331H

50.50

Time Duration of 5th 
Preset Speed

0 to 9999

0

0332H

50.51

Time Duration of 6th 
Preset Speed

0 to 9999

0

0333H

50.52

Time Duration of 7th 
Preset Speed

0 to 9999

0

0334H

50.53

Auto Acceleration/
Deceleration

00: Linear Acceleration/Deceleration

00

01: Auto Acceleration, Linear 
Deceleration

02: Linear Acceleration/Auto 
Deceleration

03: Auto Acceleration/Deceleration

04: Auto Acceleration/Deceleration 
Stall Prevention (Limited by 50.12 to 
50.15)

0335H

50.54

Sleep Frequency

0.0: Disabled

0.0

0.1 to 400 Hz Enabled

0336H

50.55

Wake Frequency

0.1 to 400 Hz (0.0 = Disable)

0.0

0337H

50.56

Sleep Time Delay

0.0 to 600 sec.

1.0

0338H

50.57

Second Source of 
Master Frequency

00: Master Frequency determined 
by digital keypad up/down

00

01: Master Frequency determined 
by keypad potentiometer

02: Master Frequency determined 
by 0 to +10V input on AI terminal 
with jumpers

03: Master Frequency determined 
by 4 to 20 mA input on AI terminal 
with jumpers

04: Master Frequency determined 
by RS-485 communication interface

0339H

50.58

Zero Speed Output 
Selection

00: Standby
01: Zero Speed Output

00

033AH

50.59

Zero Speed Holding 
Torque

0.0 to 30.0%

5.0%

 

MN04002001E.fm  Page 11  Thursday, April 13, 2006  11:11 AM

Summary of Contents for MVX9000 Series

Page 1: ...MN04002001E March 2006 Quick Start Guide For MVX9000 AF Drives March 2006 Supersedes November 2004 EQ01 5011626001 MN04002001E fm Page 0 Thursday April 13 2006 11 11 AM...

Page 2: ...hase MVX001A0 1 1 phase 115V AC 1 4 hp 115V AC 1 2 hp 115V AC 1 hp 6 1 6 9 2 5 16 4 2 12 14 12 14 12 14 MVXF50A0 2 1 phase MVXF50A0 2 3 phase 240V AC 1 2 hp 240V AC 1 2 hp 6 3 2 5 3 2 2 5 12 14 12 14...

Page 3: ...nal Name Remarks R01 R02 Digital Output Relay Refer to 40 04 Relay output contact RO1 RO2 NC Contact RO3 RO2 NO Contact R03 R02 Digital Output Relay D01 DCM Digital photocouple output Refer to 40 03 R...

Page 4: ...anel active control place has to be selected at Panel RESET used for active fault resetting fault history is reset if ENTER is pressed on the Fault History menu group in Main Menu or if ENTER is press...

Page 5: ...ecreasing of reference value on the keyboard when selected SPEED POT increase decrease reference value on the keypad when selected Displayed Message Descriptions The AC drive Input Frequency Reference...

Page 6: ...enter the programming mode The displayed parameter will flash indicating the parameter can be changed Parameter Changes Use the up and down keys to change the parameter setting Press ENTER to enter t...

Page 7: ...r 02 Master frequency determined by 0 to 10V input on AI terminal 03 Master frequency determined by 4 to 20 mA input on AI terminal 04 Master frequency determined by RS 485 communication interface 000...

Page 8: ...WD STOP DI2 REV STOP 02 02 DI1 RUN STOP DI2 REV FWD 03 DI1 RUN momentary NO DI2 REV FWD DI3 STOP momentary NC 010BH 010CH 010DH 010EH 30 12 30 13 30 14 30 15 Digital Input Terminal DI3 Digital Input T...

Page 9: ...to 400 0 Hz 100 0 0 0 0117H 30 24 7th Preset Speed 0 0 to 400 0 Hz 100 0 0 0 0118H 30 25 Display Hz or 00 Frequency Hz 00 01 Percentage 02 User Definition by 0 000 max unit 0119H 30 26 Extension Input...

Page 10: ...485 communication interface 0301H 50 02 Source of Operation Command 00 Operation command determined by digital keypad 00 01 Operation command determined by external control terminals keypad STOP is ef...

Page 11: ...um Speed 0317H 50 24 Maximum Allowable Power Loss Time 0 3 to 5 0 sec 2 0 0318H 50 25 Pause Time after Momentary Power Loss 0 3 to 10 0 sec 0 5 0319H 50 26 Maximum Speed Search Current Level 30 to 200...

Page 12: ...ation of 7th Preset Speed 0 to 9999 0 0334H 50 53 Auto Acceleration Deceleration 00 Linear Acceleration Deceleration 00 01 Auto Acceleration Linear Deceleration 02 Linear Acceleration Auto Deceleratio...

Page 13: ...OV Fault During Stop State 00 Disable 00 01 Enable Modbus Groups Description Range Default User Settings 0400H 60 01 Motor Rated Current 30 to 120 FLA 0401H 60 02 Motor No Load Current 00 to 99 0 4 FL...

Page 14: ...1 to 10 0 sec 0 1 0506H 70 07 Electronic Thermal Overload Relay 00 Constant Torque 01 01 Variable Torque 02 Inactive 0507H 70 08 Electronic Thermal Motor Overload Time 30 to 300 sec 60 0508H 70 09 Au...

Page 15: ...575V 3ph 5 hp 54 MVX007 0 5 575V 3ph 7 1 2 hp 55 MVX010 0 5 575V 3ph 10 hp 0603H 80 04 Present Fault Record 00 No Fault occurred 00 0604H 80 05 Second Most Recent Fault Record 01 Over current oc 00 0...

Page 16: ...he factory defaults 060AH 80 11 Elapsed Time Run Day 0 to 65535 show 6553 0 060BH 80 12 Elapsed Time Run Minutes 0 to 65535 show 6553 0 060CH 80 13 Elapsed Time Power on Day 0 to 65535 show 6553 0 060...

Page 17: ...voltage may also be caused by motor regeneration Either increase the deceleration time or add an optional braking resistor 4 Check whether the required braking power is within the specified limits Th...

Page 18: ...er the input voltage falls within the rated AC drive input voltage Switch the AC drive back on Internal memory cannot be read 1 Check the connections between the main control board and the power board...

Reviews: