3
Programming
Parameter
Name
Default
Value
0
1
2
3
HHIR-PROG Handset
Graphics
Description
Button Activation
On / Raise
On
Turn lights on.
Off / Lower
Off
Turn lights off.
Walk test
Off
On
Off
When set to On this causes a red LED to
flash on the sensor when it detects
movement. Use this feature to check for
adequate sensitivity levels.
Time Out
(Time
adjustment)
10 mins
1, 10 &
20
minutes
5, 15 &
30
minutes
Once the detector is turned on, this value
sets how long the lights will stay on once
movement has ceased.
Lux on level
(Switch
level on)
9
2, 5 & 7
4, 6 & 9
Lux level setting to prevent the luminaires
being switched on if the ambient light level
is sufficient (adjustable between 1
and 9). The luminaires will always be
switched on at level 9.
Lux off level
(Switch
level off)
9
2, 5 & 7
4, 6 & 9
Lux level setting to switch the luminaires off
during occupancy if the ambient light level
goes above the setting (adjustable between
1 and 9). Level 9 will always keep the lights
on. This setting can be used for “window
row switching”.
Sensitivity
9
1, 5 & 9
3, 6 & 8
Sensitivity level for detecting movement.
1 = low sensitivity
9 = high sensitivity
Defaults
D
Returns the unit to the default settings.
Shift
Use this button to select the settings in red
and blue signified by the ‘Shift 1’ and ‘Shift
2’ LEDs
Number of Shift key presses
The functionality of the MPD-C-EXT 12-24V is controlled by a number of parameters which
can be changed or programmed by any of the following devices:
HHIR-PROG
Infrared Handset. See below for programmable functions.
HHIR-LCD-PROG
Infrared Handset (with LCD). See user guide for full
programming details.
For most basic programming operations the HHIR-PROG handset can be used and the
following procedures are based on using this device.
Point the handset at the Sensor and send the required programming commands to the unit
as shown below.
Valid commands will be indicated by a red LED flash. See page 1 for details of other LED
responses.
Note: other functions on the HHIR-PROG which are not shown below are not applicable to
this product.
SHIFT 1 SHIFT 2
SHIFT 1 SHIFT 2
SHIFT 1 SHIFT 2
SHIFT 1 SHIFT 2