
7
Instructional Leaflet
IL66A7508H09
Effective October 2016
mMINT—Modbus translator module—
installation and use
EATON
www.eaton.com
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Register 42701/424833 (0A8C
16
/6100
16
)
0 = Reserved
1 = Timeout on INCOM
1 = Overrun Error
1 = BCH Error
0 = Data Msg/1 = Control Msg
Status Byte of INCOM
Response Msg 0
Byte 0 of INCOM Response Msg 0
Register 42702/424834 (0A8D
16
/6101
16
)
Byte 1 of INCOM
Response Msg 0
Byte 2 of INCOM
Response Msg 0
Register 42703/424835 (0A8E
16
/6102
16
)
Status Byte of INCOM
Response Msg 1
Byte 0 of INCOM
Response Msg 1
Register 42704/424836 (0A8F
16
/6103
16
)
Byte 1 of INCOM
Response Msg 1
Byte 2 of INCOM
Response Msg 1
Register 42701/ (2 * nn))
Status Byte of INCOM
Response Msg nn
Byte 0 of INCOM
Response Msg nn
Register 42702/ (2 * nn))
Byte 1 of INCOM
Response Msg nn
Byte 2 of INCOM
Response Msg nn
Figure 7. Pass-through to INCOM product response
data format
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Register 42901/425089 (0B54
16
/6200
16
)
Slave Action Byte 1
Slave Action Byte 0
Register 42902/425090 (0B55
16
/6201
16
)
1’s Complement of Slave Action Byte 0
Slave Action Byte 2
Register 42903/425091 (0B56
16
/6202
16
)
1’s Complement of Slave Action Byte 2
1’s Complement of
Slave Action Byte 1
Figure 8. Control to INCOM product data format
Energy format
Energy objects in the mMINT are supported in 2-register fixed point
object format and a 4-register power/mantissa format . These objects
do not support IEEE floating point format .
The 2-register format is presented in units of Kwatthours and
is valid for INCOM products reporting energy in watthours or
Kwatthours only . Products reporting in units greater than Kwatthours
(e .g ., Mwatthours) could not guarantee consistent Kwatthour
resolution up to and through their rollover values .
All products reporting energy (independent of energy units) support
the energy objects occupying four registers—register 3 through
register 0 . Register 3 is the high order register and register 0 is the
low order register .
Register 3 high byte contains a value corresponding to Engineering
Units (power of 10 signed exponent) . Register 3 low byte contains a
Mantissa Multiplier value (power of 2 signed exponent) .
Register 2 through register 0 contains a 48-bit energy mantissa in
units of watthours . Net and total energy objects are signed values .
All other energy objects are unsigned values .
The data format of these four registers is given in
Figure 9
.
Energy = 2
Mantissa Multiplier
x (48-bit energy value) x 10
Engineering Units
.