Instructional Leaflet 

IL66A7508H09

Effective October 2016

mMINT—Modbus translator module—  

installation and use 

  

EATON

 www.eaton.com

INCOM connections

INCOM connector: 

This 3-pin connector provides the interface to 

the INCOM network . Refer to 

Table 2

 .

Table 2.  INCOM connector pin outs

Pin number

Input/output signal

1

INCOM carrier network

2

INCOM carrier network

3

Shield

Connect shield wire to ground at master device end only . 

Interconnect shielding where devices are daisy chained .

Modbus connections

Modbus RS-485 Connector:

 This 4-pin connector provides the 

interface to the Modbus RTU network . The polarity is “critically” 

important . Refer to 

Table 3

 .

Table 3.  Modbus RS-485 connector pin outs

Pin number

Input/output signal

1

RS-485 Network-A (non-inverting)

2

RS-485 Network-B (inverting)

3

Common

4

Shield

RS-485 Network-A is the non-inverting differential connection for the 

Modbus RTU network . RS-485 Network-B is the inverting differential 

connection for the Modbus RTU network .

Figure 4. Indicators

Section 5: Switches and indicator LEDs

Refer to 

Figure 4

 to locate the Status LED for the mMINT module . 

Figure 5

 shows the location of the configuration switches .

SW2 SW3

SW1

Closed

Open

Figure 5. Switches

Modbus RS-485 network Rx LED (green)

The LED will be lighted whenever the module is receiving from the 

Modbus RTU network .

Modbus RS-485 network Tx LED (green)

The LED will be lighted whenever the module is transmitting on the 

Modbus RTU network .

INCOM network Rx LED (green)

The LED will be lighted whenever the module is receiving from the 

INCOM network .

INCOM network Tx LED (green)

The LED will be lighted whenever the module is transmitting on the 

INCOM network .

Status LED (green)

This indicator will be flashing whenever the module is powered up 

and the microcontroller is executing instructions . The flashing rate is 

approximately 1 second ON / 1 second OFF . However, detection of 

a communications error on either the Modbus or INCOM network 

will result in an increased flashing rate approximately 1/2 second ON 

/ 1/2 second OFF . The rate will return to normal when the network’s 

diagnostic reset subfunction (clear UART or slave counters, 

respectively) is processed by the mMINT . See Section 6 and 

Table 6

 .

INCOM 100 ohms termination DIP switch (SW1)

This switch should be moved to the ON position only when it is the 

last unit in a chain of units or if it is a single unit .

Modbus RS-485 baud rate DIP switch (SW2)

To configure the data transfer rate for the Modbus RTU network, 

three switches in DIP switch SW2 should be moved to either the 

CLOSE or the OPEN position based on the rate required . Refer to 

Table 4

 . SW2-1 is for mMINT diagnostics .

Summary of Contents for mMINT

Page 1: ...S 485 network Tx LED green 4 INCOM network Rx LED green 4 INCOM network Tx LED green 4 Status LED green 4 INCOM 100 ohms termination DIP switch SW1 4 Modbus RS 485 baud rate DIP switch SW2 4 Unique mM...

Page 2: ...8 Modbus register map in register number order 10 Table 9 Modbus register map in functional order 14 Table 10 Primary status code definitions 17 Table 11 Secondary status code definitions 17 Table 12...

Page 3: ...that it is within an enclosed space Simplified wiring rules INCOM network The following simplified rules apply to a given system consisting of a single daisy chained main cable link between master an...

Page 4: ...network Rx LED green The LED will be lighted whenever the module is receiving from the Modbus RTU network Modbus RS 485 network Tx LED green The LED will be lighted whenever the module is transmittin...

Page 5: ...or the block of registers The block assignments are stored beginning at register 41001 420481 03E816 500016 Only the first object register address is assigned within the block of registers For example...

Page 6: ...s master writes the INCOM product command data using function code 16 1016 beginning at register 42601 424577 0A2816 600016 The data format for passing information through the mMINT to an INCOM produc...

Page 7: ...ction Byte 0 Register 42902 425090 0B5516 620116 1 s Complement of Slave Action Byte 0 Slave Action Byte 2 Register 42903 425091 0B5616 620216 1 s Complement of Slave Action Byte 2 1 s Complement of S...

Page 8: ...T or INCOM addr 12 UART communication error count mMINT or INCOM addr 13 slave exception error count mMINT or INCOM addr 14 slave message count mMINT or INCOM addr 15 slave no response count mMINT or...

Page 9: ...bus is a registered trademark of Schneider Electric 2 mMINT modules use DIN rail mounting 3 Control voltage is 120 Vac 20 or 24 125 Vdc 4 Connectors are plug in types from Phoenix contact 5 Terminal T...

Page 10: ...04621 406157 120C 180C 10 n n n L L voltage VAB V 404623 406159 120E 180E 10 n n n n n n n n VBC V 404625 406161 1210 1810 10 n n n n n n n n VCA V 404627 406163 1212 1812 10 n n n n n n n n VLLavg V...

Page 11: ...6 1 n n apparent B ph VA 404681 406217 1248 1848 1 n n apparent C ph VA 404683 406219 124A 184A 1 n n Power factor displacement A ph pf 404685 406221 124C 184C 100 n n displacement B ph pf 404687 4062...

Page 12: ...n n n n n Motor phase unbalance 404737 406273 1280 1880 100 n thermal capacity 404739 406275 1282 1882 100 n Temperature motor winding 1 C 404741 406277 1284 1884 1 n motor winding 2 C 404743 406279 1...

Page 13: ...Network voltage A ph V 404801 406337 12C0 18C0 10 B ph V 404803 406339 12C2 18C2 10 C ph V 404805 406341 12C4 18C4 10 Transformer voltage A ph V 404807 406343 12C6 18C6 10 B ph V 404809 406345 12C8 18...

Page 14: ...n n n n n n n IN A 404619 406155 120A 180A 10 n n n n n n n n n IAvg A avg 404621 406157 120C 180C 10 n n n peak IA demand A 404641 406177 1220 1820 10 n n n n n n n n n peak IB demand A 404643 40617...

Page 15: ...18D6 10 B ph quadrature V 404825 406361 12D8 18D8 10 C ph direct V 404827 406363 12DA 18DA 10 C ph quadrature V 404829 406365 12DC 18DC 10 pos seq direct V 404831 406367 12DE 18DE 10 pos seq quadratur...

Page 16: ...72 1 n n n n n n n n reverse kWh N A 406261 N A 1874 1 n n n n n n n n total kWh N A 406263 N A 1876 1 n n n n n n n n n apparent kVAh N A 406271 N A 187E 1 n n n n n Energy 4 reg objects forward Wh N...

Page 17: ...neutral overcurrent 44 Diagnostic warning 3 6 Instantaneous residual overcurrent 45 Diagnostic warning 4 7 Phase inverse time overcurrent 46 Diagnostic warning 5 8 Ground inverse time overcurrent 47...

Page 18: ...watt VAR 110 Jam 152 Power 111 Under load Reserved 153 2043 112 Delay ground overcurrent 113 Calibration 114 Emergency 115 Torque limit 116 Deceleration 2044 Product Specific Code 2044 117 Voltage sa...

Page 19: ...ed motor start profile buffer 3 0 9 Relay Control Activate relay output X X relay number 0 255 4 1 X De activate relay output X X relay number 0 255 4 2 X Automatic Transfer Switch Control Initiate AT...

Page 20: ...een Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFIC...

Reviews: