background image

Menvier40/100 

Installation 

Page 29 

Step 10. Fit and Connect 
Battery 

Fit a 17Ah Lead Acid battery into the battery 
compartment in the bottom of the control unit. Use 
a battery whose case material has a minimum 
rating of UL94V-2 in order to comply with 
EN60950 (this standard applies because of the 
energy content of 17Ah batteries).  

See Figure 55. See page 12 for example 
calculations of battery requirements. 

WARNING

 

17Ah lead acid batteries weigh 6kg 

each. Do NOT drop.

 Ensure that the fixings of the 

control unit case to the wall, and the wall itself, are 
strong enough to support the weight of the control 
unit, its lid and a 17Ah lead acid battery. The total 
weight of the control unit plus batteries can be up 
to 11kg. 

Connect the battery leads, red to the positive, 
black to the negative terminals of the battery. 
Connect the other ends of the leads to BATT (item 
9 in Figure 3). 

 

Figure 55 Fitting the Batteries 

Note: Connecting the battery without mains power 
will not start the system. (See “Programming 
Before Installation” in the Menvier40/100/300 
Engineering Guide.) 

Step 11. Initial Power-Up 

Please see the 

Menvier40/100/300 Engineering Guide

 

for an explanation of bus addressing. 

WARNING:

 During initial power-up all the keypad 

sounders, internal loudspeakers and wired sirens 
MAY give an alarm tone. If you are working at the 
top of a ladder make sure that the sudden noise 
does not startle you and cause a fall. 

1.  Apply mains power to the control unit. 

The keypads and internal sounder may give 
an alarm tone. The heartbeat LED on the 
control unit PCB (item 6 in Figure 3 ) starts 
flashing. The navigation keys on any attached 
keypad start flashing. 

All connected keypads briefly show the 

software revision of the keypad itself, followed 
by the words “Please wait...” for several 
seconds while the control unit scans the bus. 
When the control unit has finished scanning 
the bus the keypads show: 





2.  Press and hold keys A and 

 simultaneously 

on the keypad that you wish to use for initial 
programming. 

NOTE: Hold the keys down 

for at least three seconds.

 

After a short pause the keypad gives a 
confirmation tone. The display briefly shows 
the bus address of the keypad. If there are no 
other keypads connected to the bus it should 
b

e “b1-d51”(bus 1 device 51). Keypads take 

bus device addresses 51 upwards. 

The keypad display then shows: 





3.  Press A or B to select either a Ward based 

system or a Part Setting system. 

Note: To change between a partition and a part 
setting system at a later date will require a factory 
default. 

The display shows: 





4.  Press 

 or 

 to show the Security Grades 

available, for example: 





5.  Press 

 to select the security grade you 

intend to use for the system. 

The display shows: 





6.  Press 

 or 

 to show the range of zone 

wiring types available, for example: 





7.  Press 

 to select the wiring type you intend to 

use for the wired zones. 

Note: This initial choice fixes the wiring type for 
the control unit and any attached wired 
expanders. If you wish to use a different wiring 
type on the expanders then use 

Installer Menu 

– 

Detectors/Devices 

– Wired Expander

 after the 

initial power up to change the wiring type for each 
expander. 

The display shows: 





Note that the alert LEDs round the navigation 
key glow red. This is because the control unit 
lid is off and the tamper is active.  

8.  Press 

Summary of Contents for menvier40

Page 1: ...Menvier40 Menvier100 Security System Installation Guide Issue 3...

Page 2: ...by the words Note Caution or WARNING Note Describes conditions that may affect the proper functioning of the equipment but will not damage the equipment Caution Describes actions that will physically...

Page 3: ...6 Connect Wired Zones 22 Four Wire Closed Circuit Connections 22 Two Wire Closed Circuit Connections 22 Fully Supervised Loop Connections 22 Step 7 Connect Wired Outputs 24 Control Unit Wired Outputs...

Page 4: ...Menvier40 100 Page iv This page is intentionally blank...

Page 5: ...and an external prox reader KEY EP A range of wireless peripherals is available for operation with the wireless expanders These include a door contact universal transmitter a passive infra red detect...

Page 6: ...etting the time and date is a user function If you wish you can also program the system from a PC or laptop connected to the Ethernet port on the control unit PCB The control unit contains a web page...

Page 7: ...ll affect the signal from a transmitter Please read Eaton s Security Business publication Guidance Notes for Wireless Alarm System Installations obtainable from www coopersecurity co uk for more infor...

Page 8: ...conducting films These glasses are particularly poor at transmitting radio waves Guided Tour CAUTION All printed circuit boards for the control unit its expanders and keypads have been tested for Ele...

Page 9: ...Control Unit 1 PSTN Connector for on board communicator 2 Lid tamper connector 3 RS485 terminator 4 Engineering keypad connector 5 USB socket Mini B 6 Heartbeat LED 7 Zone output and Aux power connec...

Page 10: ...Page 6 1 Bus cable connector 2 Aux power 3 Wired zone connectors 4 Aux power 5 Outputs relay and transistorised 6 12V Siren Bell supply 7 Siren strobe and TR 8 Auxiliary tamper 9 Loudspeaker Figure 4...

Page 11: ...e B ACE fixed To open the keypad first gently prise off the trim on the front and remove the two screws Next carefully lever the front of the keypad containing the PCB and display away from the keypad...

Page 12: ...ont You may need to gently push the bottom edge of the caps in with the end of a small screwdriver to start them Remove the two screws hidden underneath see Figure 9 Gently swing the lower side of the...

Page 13: ...XT READER Z1 Z2 OP 1 6a 6b 3 4 5 6 2 1 Tamper switch 2 Sounder 3 Connector for KEY EP Terminals for zones 4 Sounder volume control 5 Connector for control unit data bus and output terminal 6 Jumpers f...

Page 14: ...ne connectors 16 Bus address display 17 Aux power 18 Loudspeaker connectors 19 Outputs Figure 15 EXP W10 Wired Expander 1 1 2 3 1 8 7 5 6 4 10 9 11 12 13 10 1 16 15 14 1 17 18 19 1 Cable entry also be...

Page 15: ...3 Central keyhole 4 PCB 5 Link to enable disable front rear tamper switch 6 Lid tamper rear tamper behind PCB 7 Bus termination jumper 8 Addressing button 9 Fixing holes 10 Engineering keypad connect...

Page 16: ...the overall calculation CAUTION Ensure that the system does not demand more than the maximum current available from the control unit during an alarm see page 38 Bus Cabling Requirements Cable Type In...

Page 17: ...are only two arms on the star then this is the same as a daisy chain configuration see Daisy Chain 1 in Figure 18 If required fit the termination jumper at the devices on the end of each arm If there...

Page 18: ...0 74V 1 47V 2 21V 2 94V 3 68V 4 42V 5 15V 5 89V 6 62V 7 36V 480mA 0 79V 1 54V 2 30V 3 07V 3 84V 4 61V 5 38V 6 14V 6 91V 7 68V 500mA 0 80V 1 60V 2 40V 3 20V 4 00V 4 80V 5 60V 6 40V 7 20V 8 00V 520mA 0...

Page 19: ...the wall There must be enough space around this point to fit the supplied tamper shroud see Figure 21 Fitting Plastic Feet and Tamper Sleeve The control unit is supplied from the factory with four pl...

Page 20: ...20Vac connector on the PCB 11 in Figure 3 Installing the Lid Back Tamper Figure 25 Lid Back Tamper Fit combined lid back tamper bracket and switch provided Ensure that the switch is oriented as shown...

Page 21: ...riate plastic sections Use 4mm x 25mm countersunk screws with a thread suitable for the wall material in at least three fixing holes when mounting the back of the keypad on the wall i KP01 For i KP01...

Page 22: ...ith EN50131 1 2006 at Grade 3 disable the ABCD LEDs Backlight Control for KEY K01 KP01 KPZ01 You can control the brightness of the keypad backlights by fitting links over the BRIGHT jumper on the keyp...

Page 23: ...e following Status OK LED ON MENU STATUS OK LED Status OK LED OFF The green status LED under the navigation key will glow for 20 seconds after the last press this may be useful when the keypad is plac...

Page 24: ...the single retaining screw 2 Tilt the edge of the fixing plate and then slide it a short distance parallel to the body of the prox reader 3 Slide the fixing plate away from the reader body along the c...

Page 25: ...g Expanders Addressing Expanders The control unit assigns addresses to all devices connected to the bus cable You must start this process off from the Installer Menu during the initial power up See pa...

Page 26: ...he wiring for CCL zones on the EXP WCC wired expander Note that the EXP WCC provides connectors for a total of ten separate 4 wire CCL detectors and that there are separate terminals for both alarm an...

Page 27: ...ed Expander 4K7 Alarmcontacts Tamper contacts 2K2 EOL 4K7 Alarmcontacts Tamper contacts 100 Ohms Figure 41 FSL Zone Wiring EXP WCC The allowed values for Alarm Contact End of Line are the same as for...

Page 28: ...methods of connection Figure 46 shows an example of a general method of using the outputs to connect a wired sounder It is possible to program the TR terminal on the control unit see item 7 in Figure...

Page 29: ...on at the expander FSL wiring Connect TR to the left terminal of a zone connector see Figure 49 The left hand terminal is the one next to the Z on the terminal label The maximum length of wire is 50m...

Page 30: ...e Line Fault Response selected in the Installer Menu Test Calls The control unit can be programmed to make test report calls to an ARC Static test calls can be programmed to occur at set times or inte...

Page 31: ...ting a line in the UK The internal communicator must be connected to the telephone network by a If the wiring is owned by British Telecom British Telecom b If the wiring is not owned by British Teleco...

Page 32: ...using a dual path communicator 3 Plug the Communication Wiring Harness onto the communications connector on the main PCB If the system has already been installed 4 Re connect the battery 5 Fit the ca...

Page 33: ...control unit PCB item 6 in Figure 3 starts flashing The navigation keys on any attached keypad start flashing All connected keypads briefly show the software revision of the keypad itself followed by...

Page 34: ...u should leave the Installer Menu to save the changes you have made see below Diagnostic LED on Expanders You may notice the DIAGNOSTIC LED flashing on an expander PCB The LED gives one two three or f...

Page 35: ...including radio HUDs fire alarm zones 24 hour zones and tampers are disabled Note that this does not apply if you are using the web browser interface from a PC If you have logged into the system from...

Page 36: ...ould now glow green Note The log is protected and cannot be erased by the Installer Restoring Factory Defaults Only If you wish to restore all factory default options without defaulting the user and i...

Page 37: ...f any other peripherals Program the System Program the system to suit user requirements Page 34 is a summary of the Installer Menu on the control unit Please see the Menvier40 100 300 Engineering Guid...

Page 38: ...ctive Quick set Quick omit User code reqd 2 Way Replies 2 Way Set Instant Duress Enable User reset Zone alarms 6 Zone tampers System tampers Confirmation Confirmation Mode Basic DD243 BS8243 Confirmat...

Page 39: ...c Test call disabled 16 Appears only when Dynamic Test call is disabled 17 Appears only when Report Type Fast Format and Confirmation Mode Basic 18 Shows None if no module fitted 19 Must be activated...

Page 40: ...ish to find the location of any keypad or expander you can employ the Test Locate Bus Device option in the Installer Menu Use this option to make a selected bus device give a continuous tone from its...

Page 41: ...an connect any combination of these devices to the bus Capacities Menvier100 Zones 100 max with expanders Outputs 100 max with expanders Expanders and Wired Keypads 45 max devices see note Radio Keypa...

Page 42: ...may have its own power supply For Security Grade 2 the required battery standby time is 12 hours However the total average current available over 12 hours from the 17Ah battery is limited by the powe...