background image

Menvier40/100 

Installation 

Page 31 

line of the display shows the first in the list of 
found and lost devices. Press 

 to see any 

other items in the list. 

4. 

Either:

 Press 

 to go back into Installer Menu 

(so that you can go and check that all the bus 
devices you have installed are connected, 
powered up and addressed correctly). 

Note: To check an expander address remove the 
lid and briefly press the addressing button. The 
two digit display will show the bus address for a 
few seconds. 

 

OR:

 Press 

 to make the control unit update 

its internal record of devices attached to the 
bus. The display shows: 





5.  Press 

 to accept the change to the bus. (You can 

still press 

 to return to the installer menu if you do 

not want to change the number of devices on the 
bus.) 

Note:  If you attempt to leave the Installer Menu 
when a detector/device tamper is active then the 
keypad displays a fault message telling you which 

detector/device is causing the problem. Press 

 

to return to the Installer Menu. You must either 
close the detector/device tamper or delete it from 
the system before you can leave the Installer 
Menu. 

Important! 
Saving Changes 

When you make changes to the Installer Menu the 
control unit holds those changes in temporary 
memory until you leave the Installer Menu. As you 
leave the Installer Menu the control unit writes 
those changes into a permanent store. If you 
remove all power BEFORE you leave the Installer 
Menu then the control unit will lose your changes. 
Note that this does not apply if you restore 
Factory Defaults, that change takes place 
immediately. 

Re-Entering the Installer Menu 

When you enter the Installer Menu from a keypad, 
the alarm system is effectively disabled. While the 
system is in Installer Menu: 

 

Any other user trying to set the system from a 
keypad will see the message “Installer on 
Site”. 

 

All Hold Up Devices (including radio HUDs), 
fire alarm zones, 24 hour zones and tampers 
are disabled.  

Note that this does not apply if you are using the 
web browser interface from a PC. If you have 
logged into the system from a PC then the alarm 
system is active. 

If you need to re-enter the Installer Menu: 

1.  Make sure the system is unset and showing 

the standby screen (time and date). 

2.  Key in the Installer access code. At Security 

Grade 2 the default Installer access code is 
“1234”. 

 

At Security Grade 3 the default Install access 
code is “123400”. 
As you start to key in the code the display 
shows: 





When you key in the last digit of the Installer 
access code the display shows:  





Notes: 
1. You will see this screen the first time you enter 
the Installer menu on a new control unit, or if you 
have restored Factory Defaults. You can disable 
this feature by using the Installer menu option 

System Options - User Access – User Code Required

2. If you set 

User Code Required

 to NO then the 

control unit no longer complies with EN50131. 
This option complies with BS8243 only if the user 
has given written consent. 
3. If you key in an access code incorrectly, the 
display shows four “stars”. Key in the code again. 
If you key in a total of four incorrect codes then 
the system locks you out for 90 seconds. 

3.  Key in the default user code (see Note 

below). 

 

At Security Grade 2 the default user access 
code is “5678”. At Security Grade 3 the code 
is “567800”. 
The display shows: 





4.  Press 

 or 

 to display more items from the 

menu. 

Each item appears on the bottom line of the 
display in turn, for example: 





5.  Press 

 to select that item of the menu. 

The option you selected now appears on the 
top line. If there are any sub-options for that 
selection, then the first of them appears on 
the bottom line, for example: 





You can press 

 or 

 to display the other 

sub-options. 

Defaulting Access Codes 

If the User 1 and/or Installer codes are lost then 
you must restore all user information to its factory 
defaults. All prox tags, remotes and radio HUDs 
will be deleted. 

1.  If possible, enter the Installer menu. 

Summary of Contents for menvier100

Page 1: ...Menvier40 Menvier100 Security System Installation Guide Issue 3 ...

Page 2: ...d by the words Note Caution or WARNING Note Describes conditions that may affect the proper functioning of the equipment but will not damage the equipment Caution Describes actions that will physically damage the equipment and prevent its proper function WARNING Describes actions that are hazardous to health or cause injury or death Please pay particular attention to these marked passages Other Pu...

Page 3: ...p 6 Connect Wired Zones 22 Four Wire Closed Circuit Connections 22 Two Wire Closed Circuit Connections 22 Fully Supervised Loop Connections 22 Step 7 Connect Wired Outputs 24 Control Unit Wired Outputs 24 Wired External Sounders Optional 24 Auxiliary Tamper 24 Wired Outputs on Expanders 24 Wired External Sounders on Expanders 25 Remote Loudspeakers Optional 25 Output on KEY KPZ01 26 Step 8 Connect...

Page 4: ...Menvier40 100 Page iv This page is intentionally blank ...

Page 5: ...t and an external prox reader KEY EP A range of wireless peripherals is available for operation with the wireless expanders These include a door contact universal transmitter a passive infra red detector smoke detector external siren 4 button remote control and remote radio keypad This control unit is designed and approved to be used as part of a Security Grade 3 system The control unit is also ap...

Page 6: ...setting the time and date is a user function If you wish you can also program the system from a PC or laptop connected to the Ethernet port on the control unit PCB The control unit contains a web page server and you can use any web browser to see a complete version of the Installer menu Please see the Web Server Setup Guide for more instructions In addition it is possible to connect a PC or laptop...

Page 7: ...all affect the signal from a transmitter Please read Eaton s Security Business publication Guidance Notes for Wireless Alarm System Installations obtainable from www coopersecurity co uk for more information about the factors affecting radio signal strength Siting the Control Unit and Wired Zone Expanders WARNING Ensure that the fixings are strong enough to support the weight of the control unit i...

Page 8: ...r conducting films These glasses are particularly poor at transmitting radio waves Guided Tour CAUTION All printed circuit boards for the control unit its expanders and keypads have been tested for Electromagnetic Compatibility EMC However when handling the PCBs you must take the standard precautions for handling static sensitive devices Opening the Control Unit Case To gain access to the interior...

Page 9: ...2 Control Unit 1 PSTN Connector for on board communicator 2 Lid tamper connector 3 RS485 terminator 4 Engineering keypad connector 5 USB socket Mini B 6 Heartbeat LED 7 Zone output and Aux power connectors 8 Sounder for locating panel 9 Battery connector 10 Kickstart pins 11 20Vac connector 12 Connectors for loudspeakers sirens and strobes 13 Ethernet activity 14 Ethernet speed 15 Ethernet socket ...

Page 10: ...0 Page 6 1 Bus cable connector 2 Aux power 3 Wired zone connectors 4 Aux power 5 Outputs relay and transistorised 6 12V Siren Bell supply 7 Siren strobe and TR 8 Auxiliary tamper 9 Loudspeaker Figure 4 Control Unit Main Connectors ...

Page 11: ...pe B ACE fixed To open the keypad first gently prise off the trim on the front and remove the two screws Next carefully lever the front of the keypad containing the PCB and display away from the keypad rear housing 1 2 3 4 Figure 6 Opening the Keypad 2 4 3 3 1 1 Central keyhole 2 Rear tamper shroud 3 Cable entry 4 Fixing holes Figure 7 Keypad Rear Housing 1 Sounder 2 Sounder volume control 3 Tampe...

Page 12: ...ront You may need to gently push the bottom edge of the caps in with the end of a small screwdriver to start them Remove the two screws hidden underneath see Figure 9 Gently swing the lower side of the front out from the back box by about 10mm and then slide the front upwards to disengage the top catches Be careful not to pull the lower side of the front more than about 25mm away from the back whi...

Page 13: ...EXT READER Z1 Z2 OP 1 6a 6b 3 4 5 6 2 1 Tamper switch 2 Sounder 3 Connector for KEY EP Terminals for zones 4 Sounder volume control 5 Connector for control unit data bus and output terminal 6 Jumpers for addressing and LED function 6a Addressing not used 6b LED functions and RS485 bus termination Figure 14 KEY KPZ01 Keypad PCB Expanders To open any of the expander cases undo the single screw pull ...

Page 14: ...one connectors 16 Bus address display 17 Aux power 18 Loudspeaker connectors 19 Outputs Figure 15 EXP W10 Wired Expander 1 1 2 3 1 8 7 5 6 4 10 9 11 12 13 10 1 16 15 14 1 17 18 19 1 Cable entry also behind PCB 2 Central keyhole 3 PCB 4 Relay card i rc01 connector 5 Aux power 6 Link to enable disable front rear tamper switch 7 Lid tamper rear tamper behind pcb 8 Zone connectors 9 Bus termination ju...

Page 15: ...a 3 Central keyhole 4 PCB 5 Link to enable disable front rear tamper switch 6 Lid tamper rear tamper behind PCB 7 Bus termination jumper 8 Addressing button 9 Fixing holes 10 Engineering keypad connector 11 Bus cable connector 12 Sounder 13 Loudspeaker terminals 14 Bus address display Figure 17 EXP R10 R30 Radio Expander ...

Page 16: ...n the overall calculation CAUTION Ensure that the system does not demand more than the maximum current available from the control unit during an alarm see page 38 Bus Cabling Requirements Cable Type In general the control unit requires standard 7 0 2 un screened four core alarm cable for wiring the bus For maximum performance in harsh environments use twisted pair cable with a characteristic imped...

Page 17: ...e are only two arms on the star then this is the same as a daisy chain configuration see Daisy Chain 1 in Figure 18 If required fit the termination jumper at the devices on the end of each arm If there are more than two arms AND two cables are long while the remaining cables are short less than 10m then it is possible to terminate at the two devices on the ends of the long cables If there are more...

Page 18: ... 0 74V 1 47V 2 21V 2 94V 3 68V 4 42V 5 15V 5 89V 6 62V 7 36V 480mA 0 79V 1 54V 2 30V 3 07V 3 84V 4 61V 5 38V 6 14V 6 91V 7 68V 500mA 0 80V 1 60V 2 40V 3 20V 4 00V 4 80V 5 60V 6 40V 7 20V 8 00V 520mA 0 83V 1 66V 2 50V 3 33V 4 16V 4 99V 5 82V 6 66V 7 49V 8 32V 540mA 0 86V 1 73V 2 59V 3 46V 4 32V 5 18V 6 05V 6 92V 7 78V 8 64V 560mA 0 90V 1 79V 2 69V 3 58V 4 48V 5 38V 6 27V 7 17V 8 06V 8 96V 580mA 0 9...

Page 19: ...s the wall There must be enough space around this point to fit the supplied tamper shroud see Figure 21 Fitting Plastic Feet and Tamper Sleeve The control unit is supplied from the factory with four plastic feet and one plastic tamper sleeve Fit these onto the outside of the case back as shown in Figure 20 Fit feet only to the fixing holes that you intend to use Fitting tamper Shroud The tamper sh...

Page 20: ...e 20Vac connector on the PCB 11 in Figure 3 Installing the Lid Back Tamper Figure 25 Lid Back Tamper Fit combined lid back tamper bracket and switch provided Ensure that the switch is oriented as shown in Figure 25 Connect the lead from the switch to the back tamper connector on the PCB see 2 in Figure 3 Note that to be approved at Security Grade 3 you must fit the lid back tamper ...

Page 21: ...priate plastic sections Use 4mm x 25mm countersunk screws with a thread suitable for the wall material in at least three fixing holes when mounting the back of the keypad on the wall i KP01 For i KP01 keypads on Grade 3 systems drill out the hole for the back tamper using a 7mm bit see Figure 26 Figure 26 Screw i KP01 Back Box to Wall KEY K01 KP01 KPZ01 For KEY K01 KP01 KPZ01 Security Grade 3 inst...

Page 22: ...with EN50131 1 2006 at Grade 3 disable the ABCD LEDs Backlight Control for KEY K01 KP01 KPZ01 You can control the brightness of the keypad backlights by fitting links over the BRIGHT jumper on the keypad pcb see 1b in Figure 12 or 6b in Figure 14 Jumper OFF The keypad backlights glow at normal intensity Jumper ON The keypad backlights glow extra bright To program whether the backlights are on or o...

Page 23: ...he following Status OK LED ON MENU STATUS OK LED Status OK LED OFF The green status LED under the navigation key will glow for 20 seconds after the last press this may be useful when the keypad is placed in bedrooms that should be completely dark at night MENU STATUS OK LED 4 Leave local programming mode and save your changes To Disable Enable the Status Fault LED 1 Enter Local Programming mode ME...

Page 24: ... the single retaining screw 2 Tilt the edge of the fixing plate and then slide it a short distance parallel to the body of the prox reader 3 Slide the fixing plate away from the reader body along the cable Figure 30 Opening External Prox Reader Figure 31 shows the details of the external prox reader backplate 1 1 2 3 1 Fixing hole 2 Cable entry 3 Anchor for retaining screw Figure 31 External Prox ...

Page 25: ...ng Expanders Addressing Expanders The control unit assigns addresses to all devices connected to the bus cable You must start this process off from the Installer Menu during the initial power up See page 29 for instructions Expander Loudspeakers During normal operation loudspeakers on expanders repeat setting and entry tones for the ward that the expander is allocated to During an alarm the loudsp...

Page 26: ...the wiring for CCL zones on the EXP WCC wired expander Note that the EXP WCC provides connectors for a total of ten separate 4 wire CCL detectors and that there are separate terminals for both alarm and tamper Tamper Zone 1 Alarm Zone 1 Tamper Zone 0 Alarm Zone 0 Figure 37 EXP WCC CCL Zone Wiring Figure 38 shows the wiring for CCL zones on the KEY KPZ01 Tamper Zone 1 Alarm Zone 1 KEY KPZ01 Figure ...

Page 27: ...red Expander 4K7 Alarmcontacts Tamper contacts 2K2 EOL 4K7 Alarmcontacts Tamper contacts 100 Ohms Figure 41 FSL Zone Wiring EXP WCC The allowed values for Alarm Contact End of Line are the same as for the EXP W10 Figure 42 shows the wiring connections for FSL zones on a KEY KPZ01 Note that the resistance values shows are examples KEY KPZ01 Zone 0 Zone 1 2K2 EOL 4K7 Alarm contacts Tamper contacts 2...

Page 28: ... methods of connection Figure 46 shows an example of a general method of using the outputs to connect a wired sounder It is possible to program the TR terminal on the control unit see item 7 in Figure 4 as either CC or FSL Use Installer Menu System Options Panel Tamper Rtn By default the terminal is CC If you program the TR terminal as FSL then make sure you connect a 2k2 resistor in series with t...

Page 29: ...ion at the expander FSL wiring Connect TR to the left terminal of a zone connector see Figure 49 The left hand terminal is the one next to the Z on the terminal label The maximum length of wire is 50m when using 2k2 4k7 or 4k7 4k7 FSL wiring and a single core of standard 6 core alarm cable Fit EITHER a 2k2 resistor if using 2k2 4k7 FSL OR a 4k7 resistor if using 4k7 4k7 FSL Do not use any other FS...

Page 30: ...he Line Fault Response selected in the Installer Menu Test Calls The control unit can be programmed to make test report calls to an ARC Static test calls can be programmed to occur at set times or intervals Dynamic test calls occur 24 hours after the last call made by the unit See the Menvier40 100 300 Engineering Guide for details on how to program these functions Statutory Information Applicatio...

Page 31: ...cting a line in the UK The internal communicator must be connected to the telephone network by a If the wiring is owned by British Telecom British Telecom b If the wiring is not owned by British Telecom one of i British Telecom ii The authorised maintainer iii A professional Installer after 14 days written notice to the authorised maintainer To connect the telephone line see Figure 52 i Using a tw...

Page 32: ...e using a dual path communicator 3 Plug the Communication Wiring Harness onto the communications connector on the main PCB If the system has already been installed 4 Re connect the battery 5 Fit the case lid 6 Apply mains power 7 Test communicator operation Note You will need to speak to the ARC in order to confirm that the communicator has worked correctly Line Fail Input This input is designed t...

Page 33: ... control unit PCB item 6 in Figure 3 starts flashing The navigation keys on any attached keypad start flashing All connected keypads briefly show the software revision of the keypad itself followed by the words Please wait for several seconds while the control unit scans the bus When the control unit has finished scanning the bus the keypads show 2 Press and hold keys A and simultaneously on the k...

Page 34: ...ou should leave the Installer Menu to save the changes you have made see below Diagnostic LED on Expanders You may notice the DIAGNOSTIC LED flashing on an expander PCB The LED gives one two three or four flashes a second Each of these sequences has the following meaning No Flashes Meaning One Communication with control unit over bus is OK Two No communication over the bus in the last 10 seconds T...

Page 35: ... including radio HUDs fire alarm zones 24 hour zones and tampers are disabled Note that this does not apply if you are using the web browser interface from a PC If you have logged into the system from a PC then the alarm system is active If you need to re enter the Installer Menu 1 Make sure the system is unset and showing the standby screen time and date 2 Key in the Installer access code At Secu...

Page 36: ...hould now glow green Note The log is protected and cannot be erased by the Installer Restoring Factory Defaults Only If you wish to restore all factory default options without defaulting the user and installer access codes then 1 From the Installer Menu select System Options Restore Defaults Factory Defaults The display shows 2 EITHER Press to go back to the Installer Menu without changing default...

Page 37: ...of any other peripherals Program the System Program the system to suit user requirements Page 34 is a summary of the Installer Menu on the control unit Please see the Menvier40 100 300 Engineering Guide for a more detailed description Note make sure that you allocate keypads correctly to wards For more information see Assigning Wired Keypads to Wards in the Menvier40 100 300 Engineering Guide Asse...

Page 38: ...active Quick set Quick omit User code reqd 2 Way Replies 2 Way Set Instant Duress Enable User reset Zone alarms 6 Zone tampers System tampers Confirmation Confirmation Mode Basic DD243 BS8243 Confirmation time 7 After entry 7 Entry keypad lock 7 Sounder on Siren on Unconfirmed reset 7 Confirmed reset 7 HUA Confirm Time 8 Tamper as Tamper only 8 Masking Mask Override 9 Shunt Groups 10 Restore defau...

Page 39: ...ic Test call disabled 16 Appears only when Dynamic Test call is disabled 17 Appears only when Report Type Fast Format and Confirmation Mode Basic 18 Shows None if no module fitted 19 Must be activated by a Eaton s Security Business External Support Manager 20 Appears only on control units with Ethernet connector or with a suitable module fitted Table 2 Menu Options Available with Communications Mo...

Page 40: ...wish to find the location of any keypad or expander you can employ the Test Locate Bus Device option in the Installer Menu Use this option to make a selected bus device give a continuous tone from its sounder Once you have found the bus device you can silence the tone by opening the case and so activating the device s tamper Replacing or Removing Wired Keypads If you need to remove or replace a wi...

Page 41: ...can connect any combination of these devices to the bus Capacities Menvier100 Zones 100 max with expanders Outputs 100 max with expanders Expanders and Wired Keypads 45 max devices see note Radio Keypads 10 max two per radio expander External Radio Sirens 10 max two per radio expander WAMs 10 max two per radio expander repeater mode only Wards 10 Calendar Set Timers 10 max Log capacity Up to 1 250...

Page 42: ...h may have its own power supply For Security Grade 2 the required battery standby time is 12 hours However the total average current available over 12 hours from the 17Ah battery is limited by the power supply to 750mA The current is limited to 750mA because when mains is present the 1 5A power supply reserves 750mA to recharge batteries leaving 750mA available to supply the system The table below...

Page 43: ... 868 6625MHz Narrowband EN 300 220 3 EN 300 330 2 Transmitter range The range of the transmitters compatible with this control unit depends on the environment in which they are installed As a guideline most transmitters will work up 200m range in free space conditions Compliance Statements The Menvier40 and Menvier100 are compliant with EN50130 5 environmental class II The Menvier40 and Menvier100...

Page 44: ...ypad with internal prox reader but without zones or external prox reader key ep External prox reader for KEY KPZ01 KP01 KEY K01 keypad KEY KP01 keypad with internal prox reader and terminals for external prox reader KEY KPZ01 keypad with internal prox reader two zones one output and terminals for external prox reader Setting Unsetting Fobs FOB 2W 4B Two way keyfob i fb01 Four button remote control...

Reviews: