O & M Manual IM05805020K
EATON LMR Plus
Effective September 2013
Electric Fire Pump Controllers
PUMP STOPPED
The pump has stopped after a stop sequence has been initiated
REMOTE START
The pump has stated via a remote start signal
ROOM TEMPERATURE OK
The low room temperature alarm has cleared
RPT TIMED OUT
The running period timer has finished its timing cycle
SEQ START DELAY
A start sequence has been started, however, it is delayed due to the programmed
sequential start timer
SST STOPPED
The sequential start timer has stopped timing
SYSTEM STARTUP
Power has been reapplied to the system and a successful system boot has been
completed
TRANSDUCER FAILURE
The controller has detected that the transducer has failed
TRANSDUCER OK
The controller has detected that the transducer is in good working condition
UV PHASE AB
The voltage measured between phases A and B has dropped below the programmed
undervoltage set point
UV PHASE BC
The voltage measured between phases B and C has dropped below the programmed
undervoltage set point
UV PHASE CA
The voltage measured between phases C and A has dropped below the programmed
undervoltage set point
WEEKLY TEST DONE
The weekly test has been completed
WEEKLY TEST START
The pump has started on a weekly test
WEEKLY TEST STOP
The pump has stopped after a weekly test cycle
Message
Description