![Eaton Liquid-Cooled Drives LCX9000 User Manual Download Page 48](http://html1.mh-extra.com/html/eaton/liquid-cooled-drives-lcx9000/liquid-cooled-drives-lcx9000_user-manual_3699462048.webp)
LCX9000 Liquid-Cooled Drives User Manual
3-2
For more information visit:
www.EatonElectrical.com
MN04005001E
January 2007
Table 3-1: Cable Types Required to Meet Standards
Cable Data
Table 3-2: Cable Sizes 400 – 500V
Number of bolt connections = 2.
Number of bolt connections = 4.
See Main Terminal Cable Size.
Cable Type
Level N/T
Mains Cable
Power cable intended for fixed installation and the specific mains voltage.
Shielded cable not required.
Motor Cable
Power cable intended for fixed installation and the specific mains voltage.
Shielded cable not required.
Control Cable
Screened cable equipped with compact low-impedance shield.
Chassis
Catalog
Number
I
th
Mains and
Motor Cable
Cu (mm
2
)
Terminal Cable Size
Max. Number of
Cables/Bolt Size
Main Terminal
(mm
2
), Max.
Ground Terminal
(mm
2
)
CH3
LCX016A0-4
16
3x2.5+2.5
50
1 – 10
LCX022A0-4
22
3x4+4
50
1 – 10
LCX031A0-4
31
3x6+6
50
1 – 10
LCX038A0-4
LCX045A0-4
38 – 45 3x10+10
50 Cu
50 Al
6 – 35
LCX061A0-4
61
3x16+16
50 Cu
50 Al
6 – 35
CH4
LCX072A0-4
72
3x25+16
50 Cu
50 Al
6 – 70
1/M8
LCX087A0-4
87
3x35+16
50 Cu
50 Al
6 – 70
1/M8
LCX105A0-4
105
3x50+25
50 Cu
50 Al
6 – 70
1/M8
LCX140A0-4
140
3x70+35
95 Cu/Al
25 – 95
1/M8
CH5
LCX168A0-4
168
3x95+50
185 Cu/Al
25 – 95
2/M10
LCX205A0-4
205
3x150+70
185 Cu/Al
25 – 95
2/M10
LCX261A0-4
261
3x185+95 or
2x(3x120+70)
185 Cu/Al 2
25 – 95
2/M10
CH61
LCX300A0-4
300
3x240+120
25 – 185
2/M12
LCX385A0-4
385
2x(3x120+70)
25 – 185
2/M12
CH62/72
LCX460A0-4
460
2x(3x150+70)
25 – 185
4/M12
LCX520A0-4
520
2x(3x185+95)
25 – 185
4/M12
LCX590A0-4
LCX650A0-4
590
650
3x(3x150+70)
25 – 185
4/M12
LCX730A0-4
730
3x(3x150+70)
25 – 185
4/M12