background image

 

 

 

  KT TESTER 

Handle Test Kit for Trip 

Unit(PXR4.1,PXR6.1) 

 

 

 

Instruction Manual 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

Summary of Contents for IZM6-TEST-KIT

Page 1: ...KT TESTER Handle Test Kit for Trip Unit PXR4 1 PXR6 1 Instruction Manual...

Page 2: ...erating parameters 3 3 1 Parameters of Adapter 3 3 2 Parameters of Tester 3 Section 4 Operating instructions 3 4 1 Panel layout 4 4 2 Tester connection 4 4 2 1 Test connection with the individual trip...

Page 3: ...ectly powered by the battery during the test KT TESTER generates the AC voltage signal that simulates the output of CT current transformer and loads it to the test port of the trip unit Through the se...

Page 4: ...Table 1 Working parameters of tester NO Name Signal Range Unit Note Min Max 1 Voltage of Power supply Vcc 21 28 V 2 Current of Power supply Icc 1 A 3 Power output voltage DC24V Pout 22 26 V 4 Voltage...

Page 5: ...terminal Connect the 4 5 cables of KT TESTER Figure 5 with the 4 5 out cables from the trip unit for detecting the tripping time It can not be connected without measuring the tripping time 1 Test cab...

Page 6: ...ng the tripping time It can be disconnected without measuring the tripping time 4 3 Operating steps NO Steps Diagrams 1 Turn on the power and enter the default interface Note 1 When there is no operat...

Page 7: ...hen adjust the parameter to the corresponding value through and See Table 2 3 Press ENTER to confirm the setting and exit or press EXIT to cancel the setting and exit 5 2 SELECT TEST PHASE 1 Move to t...

Page 8: ...bles are connected KT TESTER will monitor whether the trip unit trips during the test automatically stop after capturing the trip signal and display the time If the 4 5 cables are not connected the te...

Page 9: ...x Ii Current setting of Instantaneous Trip 20 Earth fault Test 1 1 x Ig Current setting of Earth fault Trip after delaying the setting time tg 10 Note 1 Because the setting value of the grounding pro...

Page 10: ...of the tester in order to avoid battery power loss There are lithium batteries inside Please use them under specified conditions to avoid safety problems such as overheating explosion fire etc When sc...

Reviews: