background image

5

Instruction Booklet 

IB022003EN

Effective April 2018

Revision #3

Instructions for installation, operation, and

maintenance of Type MVS-ND, metal-enclosed

switchgear assemblies: 4.76 kV or 15.0 kV class

EATON 

 www.eaton.com

Safety precautions

 WARNING

ONLY QUALIFIED ELECTRICAL WORKERS WITH TRAINING AND 

EXPERIENCE ON HIGH VOLTAGE CIRCUITS SHOULD BE PERMITTED  

TO WORK ON THIS EQUIPMENT. THEY SHOULD BE FAMILIAR WITH  

THE WORK TO BE PERFORMED, THE SAFETY EQUIPMENT REQUIRED,  

AND THE HAZARDS INVOLVED. 

1. 

Read and understand these instructions before attempting  

any assembly, operation, or maintenance of an MVS-ND 

switchgear assembly .

2. 

Disconnect all low voltage and medium voltage power sources 

before working on the equipment per Occupational Safety and 

Health Act (OSHA) and local lockout and tagout procedures . 

Verify voltages have been removed, ground both load and 

line side connections . Observe the National Fire Protection 

Association’s (NFPA

T

) Publication #70 that is commonly known 

as the National Electrical Code (NEC

T

), OSHA, and local 

procedures and standards . This includes visual inspections 

while the vertical section door is open, making any adjustments 

inside or outside the switchgear vertical section, performing 

maintenance, or installing replacement parts .

3. 

The vertical section door cannot be opened with the switch in 

the CLOSED position . In addition, the switch cannot be closed 

with the vertical section door open .

4. 

Before opening the door of the vertical section, look through the 

window on the door to ensure that all three main blades and 

flicker blades are OPEN . If necessary, use an additional suitable 

light source .

 

WARNING

DEFEATING OR DISENGAGING SAFETY INTERLOCKS ON AN MVS-ND 

SWITCH THAT IS PROPERLY INSTALLED IN AN MVS-ND SWITCHGEAR 

ASSEMBLY AND CONNECTED TO A POWER SOURCE MAY RESULT IN 

PROPERTY DAMAGE, BODILY INJURY, OR DEATH. DO NOT DEFEAT OR 

DISENGAGE ANY SAFETY INTERLOCKS WHEN THE SWITCHGEAR IS  

IN SERVICE.

Before energizing the switchgear assembly:

5. 

Make sure the MVS-ND switchgear assembly is securely 

fastened to a true and level surface according to the floor plan of 

the customer drawings .

6. 

Always be sure that all hardware is in place and secured by 

tightening or using safety fasteners before putting an MVS-ND 

switch into operation . See Duplex switchgear configuration  

on Page 13 .

7. 

Confirm that all arc chutes and barriers are installed .

8. 

Confirm that no tools or other objects are left inside the  

vertical section .

9. 

Confirm that all devices, doors, and covers are in place .

10. 

Before start up, perform a field power frequency withstand 

(Hi-Pot) test, using test voltages given in Table 1 .

Table 1.  Power  Frequency Withstand Test Voltages.

Rated Maximum Voltage (kV)

Power-Frequency Withstand (rms) (kV)

4.76

14.25

8.25

27

15.0

27

27.0

45

38.0

60

Switchgear identification

A nameplate is located inside the small access door of each type 

MVS-ND switchgear vertical section (see Figure 1) . Contained on 

this nameplate are the Eaton master parts list number and all the 

necessary switchgear ratings . This information should be given to 

the Eaton sales office if a question should arise concerning the 

switchgear or if renewal parts are required . This information is 

sufficient for Eaton to find the manufacturing information for  

the switchgear .

Figure 1. Typical Nameplate.

 

WARNING

EXCEEDING NAMEPLATE RATINGS OF MVS-ND SWITCHGEAR COULD 

CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH. MVS-ND 

SWITCHGEAR MUST BE OPERATED WITHIN ITS NAMEPLATE RATINGS. 

Safety features

Type MVS-ND load interrupter switchgear has several built-in features 

to reduce hazards and to provide proper operating sequences .

1. 

A door interlock prevents opening the enclosure’s front door 

while the load interrupter switch is in the closed position .

2. 

A switch interlock prevents manual operation of the switch’s 

operating mechanism with the door open .

3. 

A viewing window is provided to visually verify the switch 

contact position .

4. 

Provisions for padlocking the switch in the open or  

closed position .

5. 

Provisions for padlocking the main door handles closed .

6. 

Mechanical indicators show whether the switch mechanism is 

open or closed .

7. 

Key interlocks, when provided, force a sequence of operation .

Summary of Contents for Indoor MVS-ND

Page 1: ...VS ND switchgear bolt tightness for bus connections 13 MVS ND switchgear field taping procedure 5 15 kV 14 Effective April 2018 Revision 3 Instruction Booklet IB022003EN Instructions for installation operation and maintenance of Type MVS ND metal enclosed switchgear assemblies 4 76 kV or 15 0 kV class Indoor MVS ND Switchgear Assembly Outdoor MVS ND Switchgear Assembly ...

Page 2: ...uction Booklet IB022003EN Effective April 2018 Revision 3 Instructions for installation operation and maintenance ofType MVS ND metal enclosed switchgear assemblies 4 76 kV or 15 0 kV class EATON www eaton com ...

Page 3: ...contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM THE COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HE...

Page 4: ...hat may arise during installation operation or maintenance of this equipment If further information is desired by the purchaser regarding this particular installation or application information contact the local Eaton sales office see the appropriate section of Eaton s Consulting Application Guide and review the appropriate industry standards Description and application The type MVS ND metal enclo...

Page 5: ...S ND switchgear assembly is securely fastened to a true and level surface according to the floor plan of the customer drawings 6 Always be sure that all hardware is in place and secured by tightening or using safety fasteners before putting an MVS ND switch into operation See Duplex switchgear configuration on Page 13 7 Confirm that all arc chutes and barriers are installed 8 Confirm that no tools...

Page 6: ...eceiving handling storing and installation of the equipment please reference the Instructions for receiving handling storing and installation of medium voltage switchgear in addition to customer drawing package Refer to shipping list for location of the bus hardware and all other joining and installation material Floor requirements The finished foundation surface shall be flat and level within 0 0...

Page 7: ...will face the transformer to the matching holes in the transformer case Minor misalignment may be corrected with a tapered guiding rod of some kind Insert the hardware and tighten Use extreme caution in moving the MVS ND switchgear to prevent damage Outdoor throat connection liquid filled transformers Step 1 Remove the sealing ring flange from MVS ND switchgear throat and set it aside Step 2 The s...

Page 8: ...on For outgoing circuits the terminals are beneath the switch Each terminal pad has a two hole pattern suitable for either a single hole terminal or a terminal with a two hole National Electrical Manufacturers Association NEMA drilling pattern The terminal lugs for the cable if purchased with the switchgear will be bolted to the switchgear terminals If the terminal lugs are not there then they are...

Page 9: ...N SOURCES CONSULT YOUR SAFETY DEPARTMENT BEFORE USING Securing MVS ND switchgear assemblies to foundations If the switchgear assembly was purchased for seismic applications follow the instructions on the specific drawings provided for the switchgear assembly that address the anchoring details Another drawing addresses the load bearing requirements Indoor or outdoor vertical sections are secured us...

Page 10: ...OVED CLEANERS FOR THIS EQUIPMENT m CAUTION ISOPROPYL ALCOHOL IS FLAMMABLE PROVIDE ADEQUATE VENTILATION AND KEEP AWAY FROM FLAMES AND OTHER IGNITION SOURCES CONSULT YOUR SAFETY DEPARTMENT BEFORE USING Step 4 A final thorough inspection should be made to ensure that no tools or other objects are accidentally left inside the enclosure m WARNING DEFEATING OR DISENGAGING SAFETY INTERLOCKS ON AN MVS ND ...

Page 11: ... any dust or dirt that may have accumulated inside each switchgear vertical section paying close attention to insulators and insulating material If the bus is insulated see Electrical parts and insulation check and cleaning for cleaning procedures Insulation and conductor maintenance Insulated bus coverings made from NORYL Insulated bus coverings are made from NORYL a high performance engineering ...

Page 12: ...HGEAR ASSEMBLY FROM ALL POWER SOURCES PRIOR TO INSPECTION MAY RESULT IN SEVERE INJURY OR DEATH THE SWITCHGEAR ASSEMBLY MUST BE COMPLETELY DISCONNECTED FROM ALL POWER SOURCES AND GROUNDED BEFORE PERFORMING ANY INSPECTION m WARNING WHEN ACCESSING FUSES FAILURE TO ASSURE THAT THE FUSES ARE DE ENERGIZED MAY RESULT IN EQUIPMENT DAMAGE BODILY INJURY OR DEATH MAKE SURE THAT ALL POWER SOURCES ARE DE ENERG...

Page 13: ...d Each of the locks is keyed alike and only one key must be available to operating personnel Since the key is retained in its lock when a switch is closed or when a door is opened two things are assured Only one switch may be closed at a time to prevent paralleling of incoming lines Both switches must be locked in the open position to unlock either main door preventing access to energized load sid...

Page 14: ... tape material Trade name Scotch 130C for all cable termination insulation Refer to 3M s taping method instructions Tape Method for Insulating Bus Bar Connections 5 35 kV to Meet ANSI C37 20 Requirements for installation techniques when using this tape Figure 8 DWG NO MODEL REV SHEET OF TITLE ALL REV NOTES LISTED ON SHT 1 REV MODEL FILENAME T BLK REV 4 C 7819C35 2 2 3 JOINT TAPING THRU JOINTS WITH...

Page 15: ... THE INSULATION ENDS METHODS GENERAL 1 ELONGATE INSULATING TAPE 10 TO 25 PERCENT DURING APPLICATION TO INSURE A SMOOTH TIGHT FIT ON PADS ELONGATE CORNERS ONLY 2 SHOULD A TAPE ROLL EXPIRE START THE NEW ROLL BY OVERLAPPING THE PREVIOUS END BY 5 TURN T JOINTS WITH HARDWARE 1 CLEAN AREA OF DIRT AND FOREIGN MATTER 2 WIPE PREINSULATION WITH ISOPROPYL ALCOHOL IF NECESSARY 3 APPLY FILLER OVER BARE CONDUCT...

Page 16: ...lead must be carried through the Zero Sequence current transformer and solid ly ground ed on the load sid e of the ct as shown Use 6 wire with 600V insulation Power Cables Cond uit when used Cable connections to switchgear terminals when used with Insulated Pothead Cond uit must be terminated and solid ly ground ed on the load sid e of the current transformer Zero Sequence transformer Electrical j...

Page 17: ...on Booklet IB022003EN Effective April 2018 Revision 3 Instructions for installation operation and maintenance ofType MVS ND metal enclosed switchgear assemblies 4 76 kV or 15 0 kV class EATON www eaton com Notes N ...

Page 18: ...on Booklet IB022003EN Effective April 2018 Revision 3 Instructions for installation operation and maintenance ofType MVS ND metal enclosed switchgear assemblies 4 76 kV or 15 0 kV class EATON www eaton com Notes N ...

Page 19: ...on Booklet IB022003EN Effective April 2018 Revision 3 Instructions for installation operation and maintenance ofType MVS ND metal enclosed switchgear assemblies 4 76 kV or 15 0 kV class EATON www eaton com Notes N ...

Page 20: ...ved Printed in USA Publication No IB022003EN TBG001292 April 2018 Eaton is a registered trademark All other trademarks are property of their respective owners Instruction Booklet IB022003EN Effective April 2018 Instructions for installation operation and maintenance ofType MVS ND metal enclosed switchgear assemblies 4 76 kV or 15 0 kV class ...

Reviews: