background image

 

XT-40 & IT-RSS Installation  

IM01005012E

 

Rev. 1 – 2/2007 

 

Page 7 

Figure 2-2. XT-40 & IT-RSS Mounting Dimensions 

2.40

(61.0)

1.77

(45.0)

3.15

(80.0)

2.48

(63.0)

4.17

(105.9)

3.23

(82.0)

4.73

(120.1)

5.58

(141.7)

4.80

(121.9)

3.15

(80.0)

0.25

(6.4)

M ounting

Hole Shafts

M ounting Holes

Under Lid (4)

0.75 (19.0) Internally

Threaded Conduit Fitting

2.87

(73.0)

0.79

(20.1)

1.38

(35.1)

Weight: 3 lb

Dim ensions: Inches (m m )

Note:

 Remove cover to

gain access to the
mounting hole shafts.

 

 

2.7  Wiring SPD to Electrical System 

Important!

 

When connecting the wires from the SPD to the electrical system, cut the 

wires as necessary to keep them as short as possible. In addition, to maximize the SPD’s 
performance, also twist and bind the wires together to reduce the impedance of the wire.  

 

1.  Locate your electrical system’s applicable wiring diagram in Section 2.2 or 2.3. Reference 

this wiring diagram as necessary in Steps 2, 3, and 4. 

2.  Connect the Ground wire (green) from the SPD to the system’s Ground bus bar. 

Important!

 

If the system utilizes an isolated ground, then its ground wire must be 

connected to the system’s isolated Ground bus. 

 

3.  For the XT-40, connect the Neutral wire (white) from the SPD to the system’s Neutral bus 

bar (not required for 3-Phase Delta systems – NN201, NN400, and NN501). 

4.  Connect each Phase wire from the SPD through one of the circuit interrupt devices 

installed in Section 2.4 to the system’s corresponding Phase voltage connection. 

Tip:

 

To ensure that the front panel phase voltage LEDs glow evenly, be sure that the phase wires 

are attached to their associated phase (A to A, B to B, and C to C). The wires or terminals of the 
SPD are marked with the intended phase for the electrical system (A, B, or C). Use a phase 
rotation meter to identify the electrical system’s phase sequence prior to wiring the SPD — DO 
NOT trust existing markings.

 

 

Summary of Contents for IM01005012E

Page 1: ...recautions 2 2 Installation 3 2 1 Before Installation 3 2 2 XT 40 Wiring Diagrams 4 2 3 IT RSS Wiring Diagram 5 2 4 Installing Circuit Interrupt Devices 5 2 5 Conduit Installation 6 2 6 Mounting the S...

Page 2: ...shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing performance or use of this material No part of this document may be reprodu...

Page 3: ...3Y101 Three Phase Wye Star 100 174 110 190 120 208 127 220 1P101 Single Phase 100 110 120 127 XT 40 kA 1P201 Single Phase 200 208 220 230 240 277 1P400 Single Phase 380 400 415 440 480 3Y201 Three Ph...

Page 4: ...e which if not correctly performed or adhered to could result in personal injury or death CAUTION The use of the word CAUTION in this manual denotes a potential hazard associated with the use of this...

Page 5: ...ualified electrician should be consulted to correct the problem 6 The SPD can be mounted in any position If necessary the cover may be rotated 180 degrees to improve readability of the label When remo...

Page 6: ...e entrance or serving isolation transformer XT 40 3 Phase Wye Star 3Y101 3Y201 3Y300 CIRCUIT INTERRUPT DEVICE PHASE A NEUTRAL GROUND PHASE B PHASE C Solid bond between Ground Earth and Neutral at serv...

Page 7: ...visions for multi conductor connections are made according to U S NEC 110 14a or other applicable country codes Avoid using a pre existing breaker that when operated will cause a critical system shut...

Page 8: ...ount the SPD to provide the shortest and straightest possible wire installation from the SPD to the system bus Excessive wire length and sharp bends will degrade suppressor performance therefore avoid...

Page 9: ...ion 2 2 or 2 3 Reference this wiring diagram as necessary in Steps 2 3 and 4 2 Connect the Ground wire green from the SPD to the system s Ground bus bar Important If the system utilizes an isolated gr...

Page 10: ...ge being monitored Should there be a significant difference in brightness check the phase rotation of the panel and ensure that the SPD s Phase wires are connected to the correct phase Slight differen...

Page 11: ...XT 40 IT RSS Installation IM01005012E Rev 1 2 2007 Page 9 Notes...

Page 12: ...kway Moon Township PA 15108 4312 USA http www itvss com 2007 Eaton Corporation For additional information please call All Rights Reserved Power Quality Technical Support Center Publication No IM010050...

Reviews: