background image

Installation 

i-on30EXL/EXDL 

Page 28 

Step 9. Fit a Plug-By 
Communicator 

The control unit can be connected to a separate 
communicator or speech dialler (for example, the 
Scantronic 8400, 8440, 660 or RedCare STU). 
Figure 55 shows the connections provided by the 
communications wiring harness. Note that the 
output types shown in Figure 55 are the Factory 
default types. See the 

i-on Range Engineering 

Guide

 for details on how to change the defaults. 

Brown O/P1 (Fire)

Orange O/P 2 (Hold Up Alarm)

Yellow O/P 3 (Burglar Alarm)

Green O/P 4 (Open/Close)

Blue O/P 5 (Zone Omit (System))

Purple O/P 6 (Tamper)

White O/P 7 (Confirmed)

Grey O/P 8 (General Fault)

White/Brown Line Fault input

White/Orange Tell Back input

Black 0V

Red 12V

Brown O/P 9 (AC Fail)

Orange O/P 10 (Battery Fault)

Yellow O/P 11 (Technical Alarm)

Green O/P 12 (Alarm Abort)

Com Connector Cable,
Part number 485210

Con 7

Con 8

Com Connector Cable,
Part number 11960058

 

Figure 55 Plug-By Communicator Wiring 

Note:  Comms O/P4 will be active when the 
system is unset. This is normal. 

To fit a communicator, follow the instructions 
below. 

Caution: Follow the instructions in the order 

shown, or you may damage the 
control unit and/or communicator. 

1.  Disconnect mains power from the control unit, 

remove the case lid, and disconnect the 
battery (if the system has already been 
installed). 

2.  Make any necessary connections from the 

communicator to the communication wiring 
harness. The default is a 12V positive voltage 
when the output is inactive. 

 

Refer to the next section if you are using a 
dual-path communicator. 

3.  Plug the Communication Wiring Harness onto 

the communications connector on the main 
PCB. 

If the system has already been installed: 

4.  Re-connect the battery. 

5.  Fit the case lid. 

6.  Apply mains power. 

7.  Test communicator operation. 

Note: You will need to speak to the ARC in order 
to confirm that the communicator has worked 
correctly. 

Line Fail Input 

This input is designed to allow a plug by 
communicator to indicate to the control unit that 
the communications link has failed. The 
communicator should have an output capable of 
ap12V to the Line Fail input while a line 
fault is present and 0V when the fault is absent. 

Tell Back Input 

This input is designed to allow a plug by 
communicator to indicate to the control unit that 
the user can reset the system after a system 
tamper. The communicator should have an output 
that, when triggered remotely, can apply +12V for 
at least 100ms 

to the input. See “Remote Reset 

(Redcare Reset)” in the i-on Engineering Guide 
for more information. 

Line Monitoring for a Dual-Path Communicator 

If a standalone dual-path (landline and mobile) 
communication device, such as a RedCARE STU, 
is connected to the plug-by connector, you need 
to do the following to obtain correct line fault 
reporting that complies with BSIA Form No.175, 
April 2005 (this is not necessary if you are using a 
plug-on module): 

1.  Reprogram one of the plug by outputs to type 

“ATS Test” and wire that output to the ATS 
Test input of the communicator. 

2.  Wire the Line Fault output of the 

communicator to the Line Fault input of the 
plug-by connector. The communicator must 
p12Vdc to indicate a line fault (for 
example, if the Line Fault output at the 
communicator uses a relay, connect the 
common terminal of the relay to +12Vdc and 
the normally-open terminal to the Line Fault 
input of the plug-by connector). 

The control unit will generate an "ATE L.F. Single" 
alert if only one of the networks is not available, or 
"ATE L.F. All" if both networks are not available. 

Summary of Contents for i-on30EXL

Page 1: ...i on30EXL i on30EXDL Security System Installation Guide Issue 3...

Page 2: ...l passages alerting you to potential problems or hazards Each of these are marked by the words Note Caution or WARNING Note Describes conditions that may affect the proper functioning of the equipment...

Page 3: ...Connect Control Unit to Mains 21 Mains Cabling 21 Step 6 Connect Wired Zones 21 Four Wire Closed Circuit Connections 21 Two Wire Closed Circuit Connections 22 Fully Supervised Loop Connections 22 Step...

Page 4: ...i on30EXL EXDL Page iv This page is intentionally blank...

Page 5: ...ion with the wireless expanders The range includes a door contact universal transmitter a passive infra red detector smoke detector external siren 4 button remote control and remote radio keypad This...

Page 6: ...ecify all the operating parameters for an individual installation If you wish you can also connect a PC or laptop to the mini USB port on the control unit PCB and use Eaton s Security Business s Downl...

Page 7: ...heir original position can all affect the signal from a transmitter Please read Eaton s Security Business publication Guidance Notes for Wireless Alarm System Installations obtainable from www coopers...

Page 8: ...rticularly poor at transmitting radio waves Guided Tour CAUTION All printed circuit boards for the i on30EXL EXDL its expanders and keypads have been tested for Electromagnetic Compatibility EMC Howev...

Page 9: ...ray Figure 2 Control Unit 0V 12V A B OP1 0V 12V AUX LS STB BELL TR Z0 Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9 A B PSTN 12V BELL 0V 1 11 9 10 8 13 15 14 16 4 17 18 3 2 6 5 7 12 1 Connectors for system bus 2 Zone ou...

Page 10: ...XDL Page 6 1 Built in communicator telephone line connector i on30EXDL only 2 Siren and strobe 3 Loudspeaker 4 Bus cable connector 5 Output transistorised 6 Aux power 7 Wired zone connectors Figure 4...

Page 11: ...type B ACE fixed To open the keypad first gently prise off the trim on the front and remove the two screws Next carefully lever the front of the keypad containing the PCB and display away from the ke...

Page 12: ...n with the end of a small screwdriver to start them Remove the two screws hidden underneath see Figure 9 Gently swing the lower side of the front out from the back box by about 10mm and then slide the...

Page 13: ...onnector for KEY EP Terminals for zones 4 Sounder volume control 5 Connector for data bus and output terminal 6 Jumpers for addressing and LED function 6a Addressing not used in i onEX control units 6...

Page 14: ...ne connectors 16 Bus address display 17 Aux power 18 Loudspeaker connectors 19 Outputs Figure 15 EXP W10 Wired Expander 1 1 2 3 1 8 7 5 6 4 10 9 11 12 13 10 1 16 15 14 1 17 18 19 1 Cable entry also be...

Page 15: ...a 3 Central keyhole 4 PCB 5 Link to enable disable front rear tamper switch 6 Lid tamper rear tamper behind PCB 7 Bus termination jumper 8 Addressing button 9 Fixing holes 10 Engineering keypad connec...

Page 16: ...the example system and would meet the Grade 2 requirements Note All current drawn from the Aux terminals 12V must be included in the overall calculation CAUTION Ensure that the system does not demand...

Page 17: ...n a star configuration If there are only two arms on the star then this is the same as a daisy chain configuration see Daisy Chain 1 in Figure 18 If required fit the termination jumper at the devices...

Page 18: ...46V 4 03V 4 61V 5 18V 5 76V 380mA 0 61V 1 22V 1 82V 2 43V 3 04V 3 65V 4 26V 4 86V 5 47V 6 08V 400mA 0 64V 1 28V 1 92V 2 56V 3 20V 3 84V 4 48V 5 12V 5 76V 6 40V Reducing Voltage Drop Method 1 Double up...

Page 19: ...There must be enough space around this point to fit the supplied tamper shroud see Figure 21 Fitting Plastic Feet and Tamper Sleeve The control unit is supplied from the factory with four plastic feet...

Page 20: ...Securing Screw When the PCB is in place connect the wires from the transformer to the 20Vac connector on the PCB 11 in Figure 3 Installing the Lid Back Tamper Figure 25 Lid Back Tamper Fit combined li...

Page 21: ...KEY EP or prox readers used by other systems for example access control systems If you mount prox readers closer together than one meter including on the other side of walls then the two prox readers...

Page 22: ...vigation Key LEDs You can set the function of the backlights in either of two ways a Use the Installer Menu Detectors Devices Wired Keypads Edit Keypad Keypad n Backlight option See the Engineering Gu...

Page 23: ...disabled and will not glow for any fault reports MENU STATUS FLT LED 4 Leave local programming mode and save your changes see below To Leave Local Programming Mode and Save Changes EITHER Press OR Cl...

Page 24: ...ader cable clear of cables supplying sounders or extension loudspeakers Figure 32 shows the wiring connections at the keypad Figure 32 Connecting the External Prox Reader Tone Volume All Keypads To al...

Page 25: ...Installer Menu Step 5 Connect Control Unit to Mains WARNING ENSURE THAT THE MAINS SUPPLY IS DISCONNECTED AND ISOLATED BEFORE MAKING ANY MAINS CONNECTIONS All mains electrical connections must be carr...

Page 26: ...Z01 Figure 39 KEY KPZ01 CCL Zone Wiring Two Wire Closed Circuit Connections With version 4 02 software you can connect two wire CCL detectors to each pair of zone terminals To specify the zone wiring...

Page 27: ...les KEY KPZ01 Zone 0 Zone 1 2K2 EOL 4K7 Alarm contacts Tamper contacts 2K2 EOL 4K7 Alarm contacts Tamper contacts 100 Ohms Figure 43 Wiring FSL Zones on KEY KPZ01 When programming select the FSL resis...

Page 28: ...This prevents the control unit reporting Bell Tamper unnecessarily Wired Outputs on Expanders Each EXP W10 wired expander provides connections for up to four transistor driven outputs Each output has...

Page 29: ...s using FSL wiring as described above Figure 50 Wiring TR from External Sounder to a Zone on the Expander Remote Loudspeakers Optional If you wish to add a 16 Ohm wired Loudspeaker unit then connect i...

Page 30: ...TMF tone dialling b PABX exchanges with or without secondary proceed indication Note The built in communicator is not suitable for connection as an extension to a pay phone or to 1 1 carrier systems A...

Page 31: ...to the authorised maintainer To connect the telephone line see Figure 53 i Using a two core telephone cable strip off 5mm and feed the cable through one of the entries marked 10 in Fig 2 in the rear o...

Page 32: ...eady been installed 4 Re connect the battery 5 Fit the case lid 6 Apply mains power 7 Test communicator operation Note You will need to speak to the ARC in order to confirm that the communicator has w...

Page 33: ...ED on the control unit PCB see 13 on Fig 3 starts flashing The navigation keys on any attached keypad start flashing All connected keypads briefly show the software revision of the keypad itself follo...

Page 34: ...isited all the connected bus devices go back to the keypad and press The display shows 15 Replace the control unit lid making sure that the lid tamper closes 16 At this point you should leave the Inst...

Page 35: ...er Menu you may see the red LEDs around the navigation key glowing A common cause of this alert is that there is no telephone line connected to the built in communicator If you do not intend to use th...

Page 36: ...en If they glow red then there may be an alert for a missing battery that needs acknowledgement To force the control unit to check the battery 11 Press key in 1234 press again The navigation key LEDs...

Page 37: ...on Range Engineering Guide for a more detailed description Note make sure that you allocate keypads correctly to partitions For more information see Assigning Wired Keypads to Partitions in the i on R...

Page 38: ...User Access HUA keys active Quick set Quick omit User code reqd 2 Way Replies 2 Way Set Instant Duress Enable User reset Zone alarms 6 Zone tampers System tampers Confirmation UK Confirmation Mode Bas...

Page 39: ...y when Static Test call disabled 17 Appears only when Dynamic Test Call is disabled 18 Appears only if Report Mode Fast Format AND Confirmation Mode Basic 19 Shows None on i on30EXDL 20 Must be activa...

Page 40: ...er you can employ the Test Locate Bus Device option in the Installer Menu Use this option to make a selected bus device give a continuous tone from its sounder Once you have found the bus device you c...

Page 41: ...red in EEPROM memory available for at least 10 years without power Internal Clock 10 minutes over one year depending on the accuracy of the mains supply frequency User Codes 50 plus installer code Rem...

Page 42: ...tage range 10 0 5V to 13 8V 12V Aux output voltage range 10 0 5V to 13 8V 12V Bell output voltage range 10 0 5V to 13 8V Max p to p ripple voltage 0 5V Standby Battery 12V 7Ah sealed lead acid not sup...

Page 43: ...6662 2010 at grade 2 When fitted with radio devices the i on30EXL is capable of compliance with EN50131 at Grade 2 The built in communicator is compliant with EN50136 1 as an ATS2 communicator At Gra...

Page 44: ...ypad with internal prox reader but without zones or external prox reader KEY EP External prox reader for KEY KPZ01 KP01 KEY K01 keypad KEY KP01 keypad with internal prox reader and terminals for exter...

Reviews: