Parallel communication
For parallel operation, the units communicate through the RJ-45
connectors labeled 1P and 2P on the Control Board. This is a
unique communication protocol that is only to be used for parallel
communication. The 2P jack has an RJ-45 termination plug installed
at the factory.
NOTICE
EXCESSIVE NOISE IN THE COMMUNICATION CIRCUIT.
WHEN THE UNIT IS SET TO OPERATE IN PARALLEL MODE, THE
TERMINATION PLUG MUST BE INSTALLED IN ANY RJ-45 JACKS THAT
ARE NOT USED FOR PARALLEL COMMUNICATION WIRING. SEE THE
WIRING DIAGRAMS IN THIS SECTION.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN
COMMUNICATION ERRORS.
CAT5e cable with all 8 conductors terminated at the RJ-45
connections is required for parallel communication. It is
recommended that shielded CAT5e cable be used. Ensure that
the total cable length does not exceed 76 meters (250 feet).
Figure 46 . Control board and CT board detail
1P and 2P