32
Commissioning and start-up
OperatiOnal manual
MN156001EN October 2015 www.eaton.com
Reactive Mode—Reacte:
Reactive mode provides leading
or lagging kVAR based on the Reactive Target. React Mode
does not require the installation of CTs.
Reactive Target
can be set either based on kVAR or
amperes. Reactive Target can be set remotely through
MODBUS
Load Balancinge:
When ON, the unit corrects for load
imbalance (negative sequence current). CTs are required
when Load Balancing is selected.
Admin password setup
For security purposes, we recommend changing the
Admin password from the default password. To change the
password:
1.
Touch the Password field to open an alpha keypad.
2.
Enter a new password for the Admin User.
The password must be between 6 and 32 characters
with any combination of letters or numbers. Passwords
are case sensitive.
3.
Enter it again in the Confirm field.
4.
Press Change Password. Or, if you prefer to keep the
default password, just press Next.
Test Run
When you initiate the Test Run, the unit operates briefly
providing data on the unit or system performance.
otee:
N
If this is a parallel system, perform this step after
all other units in the system have been properly
commissioned and are ready to run or you might
see a reduction in performance.
To perform the Test Run, do the following:
1.
Press Yes.
2.
Press Start.
When the test run has completed, the unit or system
performance results are displayed. You should see a
significant reduction in THDi between Unit On versus
Unit Off.