background image

GridAdvisor™ Series II smart sensor installation instructions

IL915001EN

April 2019

Eaton.com

5

Installation procedures 

In cases where a torque wrench is not available; tighten 
the cap until the gasket inside the cap makes contact 
with the battery, turn another 1/2 turn to ensure proper 
tightening.

Figure 1. Battery and SIM card locations

Forcing over the air service provision (OTASP) 
(Verizon 3G only)

If the cellular provider being utilized with GridAdvisor Series II 
smart sensor does not require use of a SIM card as is case 
with the Verizon network, the user must initiate an OTASP 
(over the air service provision). 

This specific action will cause the sensor to actively 
interrogate the network for a proper IP address from which 
the device was activated. Failure to complete this step will 
result in communication failures generally visualized on the 
sensor as simultaneous red blinking LEDs. 

Note:

A Binary Output control point can be set by the SCADA 
system to trigger an OTASP sequence that is delayed 
by 5 minutes to allow time for the new radio 
provisioning to be setup by Verizon.

1.

Ensure that device is powered up and has completed 
initialization as indicated by double green blinking LEDs. 

2.

Reed switch device by placing a strong earth metal 
magnet next to the device as indicated by the symbol 
“R” found on the rear side corner of the upper housing 
opposite of LEDs. 

3.

Reed switch will initiate Bluetooth

®

 discovery mode, but 

in order for OTASP to complete the sensor must not be 
paired with. After a two minute timeout, the sensor will 
connect to network and receive proper IP address and 
preferred roaming list. 

4.

Alternatively, if the device is Bluetooth

®

 paired and 

connected to ProView NXG

 

software, the sensor will 

complete OTASP upon disconnect of ProView NXG

 

software. 

5.

OTASP may take up to five (5) minutes, with included 
retries, so do not the remove battery from the sensor 
within this time frame. 

6.

OTASP results can be confirmed in the sensor’s 
communication logs with the ProView NXG software.

Note:

If the OTASP process fails and the sensor blinks red 
LEDs continuously, check the communication log for 
diagnostics. OTASP can fail if sensor is on roaming 
network or has poor signal strength.

Installing battery

1.

Remove sensor barrel cap to access battery 
compartment. Take care not to lose the gasket located on 
inside of cover. 

2.

Locate battery inside sensor and battery connector on 
side wall inside sensor shown in Figure 1. 

3.

Battery and sensor connectors are keyed to prevent 
misalignment. Press connectors together until they snap 
into locking position. 

4.

Device will begin initialization and attempt cellular 
activation. 

Leaving sensor activated without proper charging current
source will lead to equipment (battery) damage.

5.

Re-tighten cap from 17-22 in-lbs of torque to prevent any 
water ingress. 

In cases where a torque wrench is not available; tighten 
the cap until the gasket inside the cap makes contact 
with the battery, turn another 1/2 turn to ensure proper 
tightening.

Shelf mode

As an alternative to disconnecting the battery for prolonged 
time without a proper charging source, the sensor can be 
commanded into “Shelf Mode”. This is accomplished via an 
active connection with ProView NXG using the 

Operate

 

 

Control Operation dialog,

 or by sending a DNP3 binary 

output control command via the SCADA connection to binary 
output index 08.

To return the sensor to normal operation from Shelf Mode, 
perform a reed switch with a magnetic reset tool. The device 
will then initialize in the same manner as when installing the 
battery. There is no way to remotely force this action, so 
ensure the device initializes before leaving the site.

Battery 
connector

Shown with 
cap removed

Summary of Contents for GridAdvisor II Series

Page 1: ...IL915001EN GridAdvisor Series II smart sensor installation instructions Effective April 2019 Supersedes August 2017 Energy Automation Solutions ...

Page 2: ...SHALL NOT BECOME PART OF OR MODIFY ANY SUCH PRIOR OR EXISTING AGREEMENT The information recommendations descriptions and safety notations are based on Eaton experience and judgment THIS INFORMATION SHOULD NOT BE CONSIDERED AS ALL INCLUSIVE OR COVERING ALL CONTINGENCIES If further information is required Eaton should be consulted In no event will Eaton be responsible to the user in contract in tort...

Page 3: ...lampstick hotstick etc Following is important safety information For safe installation and operation of this equipment read and follow all cautions and instructions This manual may contain four types of hazard statements Indicates a hazardous situation which if not avoided will result in death or serious injury Indicates a hazardous situation which if not avoided could result in death or serious i...

Page 4: ...ile a claim with the carrier immediately Handling Be careful during handling and storage of the sensor to minimize the possibility of damage If the sensor is to be stored for any length of time prior to installation provide a clean dry storage area Quality standards ISO 9001 certified quality management system Installation procedures SIM cards A SIM card is a small removable card consisting of an ...

Page 5: ...disconnect of ProView NXG software 5 OTASP may take up to five 5 minutes with included retries so do not the remove battery from the sensor within this time frame 6 OTASP results can be confirmed in the sensor s communication logs with the ProView NXG software Note If the OTASP process fails and the sensor blinks red LEDs continuously check the communication log for diagnostics OTASP can fail if s...

Page 6: ... The exact trip value is dependent on the overall diameter of the double back neutral wires Figure 2 Recommended methods of concentric neutral primary cable preparation Method 2 refer to Figure 2B 1 Attach one or two strands of the concentric neutral wrapped around the cable to the tie off tab on the elbow 2 Terminate all of the remaining neutral wires just below the elbow The balance of the neutr...

Page 7: ...a location shown in Figure 4 while holding the hotstick horizontal The triggering mechanism will release the clamping arms and securely attach the device to the cable Note Only the closed core current transformer CT need be applied over the region of the cable where the concentric neutral has been removed or double backed Figure 5 For installation on tape shield cable the closed core CT of the sen...

Page 8: ...e annunciation during the installation of device to verify proper load current is present Programming sensor Refer to the GridAdvisor Series II Smart Sensor ProView NXG software programming manual MN915003EN for instructions on connecting to the sensor with the Bluetooth module and or programming device with ProView NXG software Load LED Source LED Table 1 GridAdvisor Series II Smart Sensor LEDs P...

Page 9: ...uence steps Action LED Behavior First reed switch activation After 10 seconds if no further reed switch closure occurred the Bluetooth radio will be turned on enter discoverable mode and wait for a connection Load and Source LEDs will flash a simultaneous blue sequence After 10 seconds the Load and Source LEDs will light solid for 2 seconds indicating that Bluetooth functionality is active You may...

Page 10: ...eived including interference that may cause undesired operation Anatel Anatel homologation 3670 15 8433 01 07898994273486 GridAdvisor Model E0013X41G10 Este equipamento opera em caráter secundário isto é não tem direito a proteção contra interferência prejudicial mesmo de estações do mesmo tipo e não pode causar interferência a sistemas operando em caráter primário This equipment operates on a sec...

Page 11: ...GridAdvisor Series II smart sensor installation instructions IL915001EN April 2019 Eaton com 11 Regulatory information ...

Page 12: ...utomation Solutions Division 3033 Campus Drive Suite 350N Minneapolis MN 55441 United States Eaton com 2019 Eaton All Rights Reserved Printed in USA Publication No IL915001EN Rev 3 April 2019 Eaton is a registered trademark All other trademarks are property of their respective owners For GridAdvisor series II smart sensor product information call 1 877 277 4636 or visit Eaton com ...

Reviews: