Fiches et prises de 16 A pour atmosphères explosives,  
GHG 511

Caractéristiques techniques

1.1   

Fiches et prises GHG 511

ATEX Certificat de Conformité:

PTB 99 ATEX 1039

Marquage selon 94/9/CE et directive:
EN 60079-0

 II 2 G Ex de [ia] IIC T6/T5 
 II 2 D Ex tD A21 IP66 T80°C

IECEx Certificat de Conformité:

IECEx BVS 12.0027

Marquage selon:
IEC60079-0

Ex de IIC T5/T6 Gb 

Ex tb IIIC T80°C Db IP66

Tension nominale:
GHG 511 -  

3-pôles 

GHG 511 -  

4-pôles 

GHG 511 -  

5-pôles

jusqu’à 415 CA, 50/60 Hz 

jusqu’à 690 CA, 50/60 Hz 

jusqu’à 500 CA, 50/60 Hz

Courant nominal:

16 A au maxi

Fusible maximal placé en amont:
sans protection thermique

25 A au maxi

avec protection thermique

35 A gL au maxi

Pouvoir de coupure AC 3, 3 pôles:

250 V/16 A

Pouvoir de coupure AC 3, 4 pôles:

400 V/16 A

Pouvoir de coupure AC 3, 5 pôles:

400 V/16 A

Température ambiante admissible: 

(modèle de liste, en cas de modèles spéciaux d’autres 

températures possibles)

-20° C à +40° C

Température de stockage dans l’emballage original: -20° C à +40° C
**Indice de protection selon EN/CEI 60529,

avec le couvercle rabattant fermé et arrêté et

les dispositifs dûment enfichés:

IP 66 (modèle de liste)

Classe d’isolation selon EN/CEI 61140:

II - est remplie par les dispositifs

Entrée de câble:

(modèle de liste)

Prise murale

2 x bouchon de fermeture M25

Borne de connexion:

Section transv.        Longueur dénudée des fils
2 x 1,5  - 10 mm²  

     16 mm

Couples de serrage:
Vis de couvercle

3,0 Nm

Bornes de connexion L, N

4,0 Nm

Poids:

(modèle de liste)

Prise murale  

4/5 pôles   GHG 511

env.  5,4 kg

Contact auxiliaire:
tension nominale

250 V AC

Pouvoir de coupure

AC: 5 A
DC: 0,03 A

2   Consignes de sécurité

Attention! Cette annexe au mode 

d’emploi GHG 510 7001 P0012 

ne doit  être utilisée qu’avec le mode 
d’emploi original. 
”GHG 510 7001 P0001”. Les fiches et prises 
du type GHG 511 pour atmosphère explosive 
ne sont  pas appropriées à la zone 0 et  
zone 20.

Respectez les prescriptions nationales de 
sécurité et de prévoyance contre les 
accidents ainsi que les consignes de sécurité qui 
suivent dans ce mode d’emploi et qui sont 
mises en italique comme ce texte!

3   Domaine d’utilisation

Les fiches et prises du type GHG 511 
conviennent à l’emploi en les zones 1, 2 et  
21, 22 d’une atmosphère explosive selon  
CEI/EN 60079-10-1 et CEI/EN 60079-10-2! 
Pour l’enveloppe, y compris les pièces métal-
liques extérieures, des matières de qualité su-
périeure ont été employées qui assurent une 
protection appropriée contre la corrosion et 
une résistance contre des agents chimiques 
en “atmosphère industrielle normale”:

 

- polyamide résistant au choc   

 

- polyester renforcé par fibre de verre 

 

- acier spécial AISI 316

En cas d‘utilisation en atmosphère extrème-
ment  corrosive, vous pouvez obtenir des 
informations complémentaires sur la résistance 
chimique des plastiques utilisés chez la succur-
sale Cooper Crouse-Hinds de votre région.

5   Utilisation/Propriétés

Les fiches et prises GHG 511 servent à 
l’alimentation des appareils électriques 
et des machines mobiles situés dans des 
atmosphères explosibles. Les fiches et prises 
peuvent aussi être employées en „atmos-
phère industrielle normale“.

Les fiches et prises GHG 511 pour basses 
tensions sont dotées d’un sectionneur à 
coupure en charge et peuvent être exploitées 
jusqu’à 16 A au maxi (voir Caractéristiques 
techniques).   
Les prises et fiches sont utilisables dans les 
fourchettes de tension comprises dans la 
norme CEI/EN 60309 (par exemple, U

N

 400V 

appartient à la fourchette 380 - 415V).

L’ appareil connecté à la fiche doit être 
adapté à la tension du réseau correspondant.

 

Pattes de fixation murale

   sur les côtés

   en haut et en bas

Fig. 1

Summary of Contents for GHG 511

Page 1: ...G 511 Explosion protected plug and socket system 16 A 3 pole 4 pole 5 pole GHG 511 Fiches et prises de 16 A 3 p les 4 p les 5 p les pour atmosph res explosives GHG 511 Betriebsanleitung Operating inst...

Page 2: ...ions 7 3 Conformity with standards 8 4 Field of application 8 5 Use Properties 8 6 Installation 8 6 1 Mounting 9 6 2 Opening the device Electrical connection 9 6 3 Cable entries KLE blanking plugs 9 6...

Page 3: ...5 Ex tD A21 IP 66T 80 C Flanschsteckdose GHG 511 8 Ex db eb IIC IIB Gb Ex tb IIIC Db Bemessungsspannung GHG 511 3 polig bis 415 V 50 60 Hz GHG 511 4 polig bis 690 V 50 60 Hz GHG 511 5 polig bis 690 V...

Page 4: ...ng zu sichern Das Stecken undTrennen des Steckers von der Steckdose ist nur im ausgeschalteten Zustand m glich Nach dem Einschalten der Steckdose wird um die Schutzart gem Typenschild auch mit gesteck...

Page 5: ...das Griffst ck eindrehen Alle Schrauben und oder Muttern der An schlussklemmen auch die der nicht benutzten sind fest anzuziehen Bei berm igem Anziehen kann der Anschluss beeintr chtigt oder besch di...

Page 6: ...sicherstellen oder geeignete Schutzma nahmen ergreifen Die erforderlichenWartungsintervalle sind anwendungsspezifisch und daher in Abh ngig keit von den Einsatzbedingungen vom Betreiber festzulegen Im...

Page 7: ...x de ia II CT6 bzw T5 Ex tD A21 IP 66T 80 C Flange socket GHG 511 8 Ex db eb IIC IIB Gb Ex tb IIIC Db Rated voltage GHG 511 3 pole up to 415 V 50 60 Hz GHG 511 4 pole up to 690 V 50 60 Hz GHG 511 5 po...

Page 8: ...plug can be pushed into the socket and pulled out of it only whilst the socket is switched off In order to ensure the socket s type of protection acc to the type label also with the plug being inserte...

Page 9: ...tive contacts When reassembling the flange screws shall be screwed into the body sleeve with a maximum test torque of 1 Nm All screws and or nuts of the supply terminals also of those remaining vacant...

Page 10: ...s depend on the specific application and will therefore have to be determined by the user dependent on the conditions of use When servicing the plugs and sockets parti cularly those parts that are dec...

Page 11: ...Prise bride GHG 511 8 Ex db eb IIC IIB Gb Ex tb IIIC Db Tension nominale GHG 511 3 p les jusqu 415 V 50 60 Hz GHG 511 4 p les jusqu 690 V 50 60 Hz GHG 511 5 p les jusqu 500 V 50 60 Hz Fiche GHG 543 2...

Page 12: ...bloqu e avec l anneau ba onnette La fiche ne peut tre enfich e dans la prise ou retir e de celle ci que lorsque la prise est mise hors circuit Afin d assurer le mode de protection selon la plaque sign...

Page 13: ...exion aussi celles des bornes non utilis es doivent tre serr es fond Afin de maintenir le mode de protection contre l explosion le raccordement des conducteurs doit se faire tr s soigneusement Les bor...

Page 14: ...rvice requis d pendent de l emploi sp cifique et devront donc tre fix s par l utilisateur en tenant compte des condi tions d exploitation Lors de l entretien des appareils surtout les composants qui s...

Page 15: ...liaire GHG 511 543 Ansicht 1 View 1 Voir 1 Ansicht 2 View 2 Voir 2 2 1 Schaltschema Switching operation m canisme de commutation AnschlussbildWand Flanschsteckdose GHG 511 Contact arrangementWall Flan...

Page 16: ...nwand Inner wall of enclosure Paroi interne de l enveloppe 110 130V gelb yellow jaune 220 250V blau blue bleu 220 250V blau blue bleu 380 415V rot red rouge 500V schwarz black noir GHG 511 3 pol PE 50...

Page 17: ...s in mm Dimensions en mm X Befestigungsma e X fixing dimensions X dimensions de fixation 2 pol PE 3 pol PE 3 p l N PE Flanschsteckdose Flange socket Prise bride 2 pol p l PE Flanschsteckdose Flange so...

Page 18: ...e GHG 543 23 2 pol p l PE Stecker Plug Fiche GHG 531 7 4 5 pol p l PE Stecker Plug Fiche GHG 511 4 4 5 pol p l PE Stecker Plug Fiche GHG 511 43 2 pol p l PE Kupplung Coupler Prolongateur 2 pol p l PE...

Page 19: ...19 Notizen Notes Remarques...

Page 20: ...er Crouse Hinds CEAG estas instrucciones de servicio en otro idioma de la Union Europea EST Seda kasutusjuhendit oma riigikeeles v ite k sida oma riigis asuvast asjaomasest Cooper Crouse Hindsi CEAG e...

Page 21: ...plugs and sockets 16 A 4 pole and 5 pole GHG 511 stainless steal Fiche et prise de 16 A 4 p les et 5 p les pour atmosph res explosives GHG 511 acier inoxydable GHG 510 7001 P0012 D GB F a CROUSE HIND...

Page 22: ...ns contact auxiliaire avec contact auxiliaire GHG 511 3 pol PE 50 60Hz 380 415V rot GHG 511 4 pol PE 50 60Hz 220 250V blau 690V schwarz 500V schwarz 380 415V rot 220 250V blau 690V schwarz 500V schwar...

Page 23: ...eitshinweise Dieser Anhang zur Betriebsanleitung GHG 510 7001 P0012 ist immer mit der Betriebsanleitung GHG 510 7001 P0001 zu verwenden Dort aufgef hrte Hinweise sind zu beachten Die Steckvorrichtunge...

Page 24: ...nter Ber cksichti gung einschl giger Vorschriften anzuschlie en Der Zusammenbau erfolgt nach dem Kabel anschluss in umgekehrter Reihenfolge Die minimal und maximal anschlie baren Leiterquerschnitte so...

Page 25: ...instructions This Annex to operating instructions GHG 5107001P0012 is only for use with the original operating instructions GHG 510 7001 P0001 The GHG 511 plugs and sockets are not suitable for Zone...

Page 26: ...crews and or nuts of the supply terminals also of those remaining vacant shall be tightened down The conductors shall be connected with special care in order to maintain the explosion category The sup...

Page 27: ...utilis e qu avec le mode d emploi original GHG 510 7001 P0001 Les fiches et prises du type GHG 511 pour atmosph re explosive ne sont pas appropri es la zone 0 et zone 20 Respectez les prescriptions n...

Page 28: ...tenant compte des r glements respectifs les conducteurs d ment d nud s des c bles sont raccord s Apr s le raccordement du c ble le montage se fait dans l ordre inverse Les sections minimales et maxima...

Page 29: ...9 Notizen Notes Remarques...

Page 30: ...10 Notizen Notes Remarques...

Page 31: ...11 Notizen Notes Remarques...

Page 32: ...er Crouse Hinds CEAG estas instrucciones de servicio en otro idioma de la Union Europea EST Seda kasutusjuhendit oma riigikeeles v ite k sida oma riigis asuvast asjaomasest Cooper Crouse Hindsi CEAG e...

Reviews: