7
Technical Data
PR000-00-513-05
Effective
January 2018
Installation and User manual for the
conventional range of fire panels
EATON
www.eaton.com
Enable zone
•
Enter access code level 2, then press button
Yellow led of the first zone is flashing .
Push button several times until the yellow led of the relevant
zone is flashing .
Push button to enable the relevant zone .
Repeat this procedure to enable further disabled zones .
Disable sounders
Isolates sounder circuits from the system
•
Enter access code level, then press button
The yellow LED of the zone 1 will light and the internal buzzer will
pulse rapidly .
Push button several times until both the disabled and sound-
ers disabled yellow LEDs are lit .
Push button to confirm disable sounders .
The internal buzzer will pulse at a slow rate and the disabled and
sounders disabled LEDs will remain lit .
To silence the internal buzzer
•
Enter access code level 2, then press button
Enable sounders
•
Enter access code level 2, then press button
Internal buzzer will rapidly pulse .
Push button several times until sounder LED turns off .
Push button to confirm enable sounders
Self check detectors
This function is no longer available on new panels, however it
may be available on existing panels.
Detector LED function (applies to self check detectors only)
Self check detectors incorporate self check intelligence enabling
them to monitor their own status and to generate a fault signal at
the panel in the event of a malfunction .
Should a detector develop a fault, the zone to which the detector
is connected will indicate a zone fault and the status LED on the
faulty detector will illuminate amber .
Should the detector fail completely, it is possible to instruct the
panel to illuminate the LEDs of the healthy indicators instead .
To activate this function
•
Enter access code level 3 (engineer’s code)
•
Then press button
To cancel this mode
•
Enter access code level 3 (engineer’s code)
•
Then press button
The LED control facility can also be used to diagnose faults in the
external zone wiring . Should a zone open circuit occur, activate
the LED test mode as described above . The LEDs of all detec-
tors which still have a healthy connection to the panel will flash,
making it easier to identify the location of the break .
Follow the instructions above to cancel LED indicator mode .
④
④
①
④
④
①
⑤
④
④
①
③
③