3
Technical Data
PR000-00-513-05
Effective
January 2018
Installation and User manual for the
conventional range of fire panels
EATON
www.eaton.com
Wiring
The following cable type and size are recommended:
Mains wiring:- 1 .5mm
2,
2 core, fireproof cable
Zone wiring:- 1 .5mm
2
, 2 core, fireproof cable
Sounder wiring:- 1 .5mm
2
to 2 .5mm
2
, 2 core, fireproof cable
CAUTION
DO NOT USE A HIGH VOLTAGE TESTER WHEN WIRING IS
CONNECTED TO ANY ELECTRONIC EQUIPMENT.
Zone Wiring
Each zone circuit is supplied with an End of Line Monitor unit
(EOLM-1) . All zone circuits must be terminated with an EOLM-1,
connected at the end of the installed zone wiring, taking care to
observe the correct polarity .
Figure 5. Wiring connection drawing
Figure 6. End of Line Monitor unit wiring
Do not fit any other component such as an end of line resistor to
the zone circuits .
The EOLM-1 works in conjunction with a diode fitted in each
detector base so that all call points continue to function should a
detector head be removed .
This range of control panels can support up to 30 detectors (max
per zone) and an unlimited number of call points per zone .