Data block transfer
EZD is provided with 32 function blocks BT01 to BT32 for
transferring values from one marker range (Copy data). The
marker ranges can be overwritten with a particular value (data
initialization). The following marker types can be transferred
and overwritten:
• MB,
• MW,
• MD.
The function block is enabled in the circuit diagram.
Figure 99: EZD circuit diagram with enabling of transfer data block
function block
Parameter display and parameter set for a data block transfer
function block:
Only constants can be modified in the parameter display of a
function block.
I 05--------------------------Ä BT07T_
BT07E1o
BT07E2s
BT07E3j-----------------------Ä M 42
BT07 INI
+
>I1
>I2
>NO
BT07
Data block transfer function block number 07
INI
INI mode, initialize marker ranges
+
Appears in the parameter display
>I1
Source range start
>I2
Destination range start
>NO
Number of elements to be written in bytes per range.
Value range 1 to + 383