3. Operation
Personnalisation batterie
Use EXIT key when set up is completed.
z
These parameters are only adjustable if
z
UPS
is OFF.
Access to the personalisation through external software
Insert the
z
Solution-Pac
CD ROM in your CD drive.
At the first Navigator Screen, select "Installation" and follow the instructions to install
z
Personal
Solution-Pac
for Windows.
If nothing appears, launch startup.exe
z
Then go to "Advanced settings" and "UPS settings".
z
Please note that the Linux/Unix/MacOS versions of
Personal Solution-Pac
do not include this feature.
3.2 Final start up sequence
Press the ON button more than 3 seconds.
z
After UPS internal test sequence, the green LED
z
13
goes on.
During the restart, if the Bypass AC source is out of tolerance, the UPS will generate an output 10 ms calibrated
break.
ON/OFF features
Function
Factory setting
Options
Comments
Cold start
Disabled
Enabled Start on battery.
Forced reboot
Enabled
Disabled Enables automatic restart of the system
even if normal AC source is restored before
the end of the shutdown sequence.
Automatic restart
Enabled
Disabled UPS restarts automatically
when normal AC source is restored.
Sleep mode
Disabled
Enabled
Automatic shudown on battery if output
load level < 10%.
UPS ON/OFF by software
Enabled
Disabled Enables consideration of shutdown
or restart orders from software to be
authorized.
Function
Factory setting
Options
Comments
Battery test
Every week
No test / daily / monthly
Low battery signal
20 %
0 to 100 %
1% increment.
Run time choice
UPS reads # of battery
modules connected
From 50 to 400 Ah
Requires
EX RT CLA
if using
options (see section 1.4
"Battery extensions").
Battery deep discharge
protection
Enabled
Disabled
If disabled, lost of EATON
warranty.