5
Operation
OperatiOnal manual
MN156001EN October 2015 www.eaton.com
Network Setup
IPe:
Displays the IP address for the TCP/IP Ethernet
connection.
Subnete:
Displays the unit’s subnet address.
See Unit Settings on
page 14
for instructions on
changing the Network Setup values.
Unit Setup
Unit Typee:
Indicates whether the unit is an active filter
or an electronic VAR compensator.
Unit Sizee:
Displays the unit amperage rating.
Nominal voltage and frequencye:
Displays the system
nominal voltage and frequency settings.
CT Conn .e:
Indicates the number of CT’s connected to
the unit.
CT Ratioe:
Displays the CT ratio used.
CT Configuration:
Indicates whether the CT’s are located on
the Source or Load side of the active filter system.
Voltages and Temperature
Voltages
Line Voltagee:
Displays the three-phase average of the
incoming line voltage to the unit.
Line Frequencye:
The measured source frequency.
DC Bus Tope:
The measured DC voltage of the top
DC bus section.
DC Bus Bote:
The measured DC voltage of the bottom
DC bus section.
Temperatures
All temperatures are displayed in degrees Celsius.
Inlete:
Unit’s inlet air temperature.
Unit Tope:
Outlet air temperature of the electronic
air section.
Control Boarde:
Air temperature surrounding the Control
Printed Circuit Board.
IGBT L1e:
Temperature of phase L1 inverter IGBT.
IGBT L2e:
Temperature of phase L2 inverter IGBT.
IGBT L3e:
Temperature of phase L3 inverter IGBT.
Unit Status
Uptimee:
Elapsed time from the last energization.
Total On Timee:
Total time the unit has been energized.
Total Run Timee:
Total time the unit has been in Run
condition.
Average Output L1e:
Average output current for L1 phase.
Average Output L2e: Average
output current for L2 phase.
Average Output L3e:
Average output current for L3 phase.