6 Diagnostics
10
ESR5-NO-31-230VAC
12/19 MN049012EN
www.eaton.com
6 Diagnostics
○
– LED o
ff
●
– LED on
Table 1: Diagnostic description
Power
IN1/2
K1
K2
Fault
Remedy
Connection/
voltage error
○
○
○
○
Supply voltage not present.
Apply supply voltage.
●
●
●
○
Supply voltage too low.
Adjust supply voltage.
●
○
○
○
The enable circuits are connected incorrectly
or not connected at all.
Check the connection of the enable
circuits.
Cross-
circuit
○
○
○
○
Between both enable circuits S11- S12 and
S21-S22.
E.g., for emergency stop.
Remove cross-circuit.
Short circuit
○
○
○
○
Between contact points A1 and A2.
Remove short circuit.
●
●
●
○
Between S11 and S12.
Fault detection on next demand.
●
●
○
●
Between S21 and S22.
Fault detection on next demand.
Fault in reset
circuit
●
●
○
○
Faulty reset button,
short circuit between S12 and S34.
No fault detection on initial start, only on first
new demand.
Replace reset button.
Remove short circuit.
Fault with
internal
cause
●
●
○
●
Enable contact(s) of K1 faulty.
Replace safety relays.
●
●
●
○
Enable contact(s) of K2 faulty.
●
●
○
○
Enable contact(s) of K1 and K2 faulty.