Checking the current firmware version of the Network Module
Servicing the Network Management Module – 139
•
•
•
•
•
This will allow to restart sequentially the IT equipment on utility recovery.
4.3.3.2.2 Resulting setup
UPS provides outlets (Group 1 and Group 2) and a primary output.
Connections to UPS can be done as described below:
Group 1: Applications
Group 2: Database servers
Primary: Storage
4.3.3.3 Step 2: Power outage policy settings
4.3.3.3.1 Objective
Use load segment restart settings to define restart sequencing.
4.3.3.3.2 Resulting setup
1. Navigate to
Contextual help>>>Protection>>>Shutdown on power outage
page and to the When utility comes back section.
2. Enable the "Keep shutdown sequence running until the end and then restart (forced reboot)".
3. Enable the "Automatically restart the UPS when battery capacity exceeds" and set it to 0%.
The storage will restart first, right after utility recovery without waiting the battery capacity to exceed a % limit.
4. Set Then Group 1 after to 120s.
The database servers will restart 120s after the utility recovery.
5. Set Then Group 2 after to 60s.
The database servers will restart 180s after the utility recovery.
4.4 Checking the current firmware version of the Network Module
Current firmware of the Network Module can be accessed in :
Contextual help>>>Maintenance>>>System information>>>Firmware information
Contextual help>>>Maintenance>>>Firmware
: Active FW version x.xx.x
4.5 Accessing to the latest Network Module firmware/driver/script
Download the latest Eaton Network Module firmware, driver or script from the Eaton website
When utility recovers, primary starts immediately.
Summary of Contents for eNMC2
Page 1: ...PDU Network Module eNMC2 User s Guide English 10 09 2023...
Page 2: ......
Page 25: ...Home Contextual help of the web interface 25 3 2 2 1 3 Battery mode 3 2 2 1 4 Off mode...
Page 27: ...Home Contextual help of the web interface 27 3 2 2 2 3 Battery mode 3 2 2 2 4 Off mode...
Page 29: ...Home Contextual help of the web interface 29 3 2 2 3 2 Bypass mode 3 2 2 3 3 Battery mode...
Page 50: ...Protection Contextual help of the web interface 50 Example 2 Immediate OFF Example 4 Custom...
Page 51: ...Protection Contextual help of the web interface 51 Settings 1 Settings 2...
Page 224: ...Acronyms and abbreviations Information 224...
Page 231: ......