1.5.5 Status LEDs

EMS electronic motor starters feature four LEDs that are used to indicate 
their operating state. These LEDs have the following designations and col-
ors:

Table 4:

LEDs at DOL starters (EMS-D…)

Table 5:

LEDs at reversing starter (EMS-R…)

After the supply voltage is applied, all four LEDs will light up once to ensure 
that they are working.

The green 

PWR

 LED indicates the device‘s general status.

The red 

ERR

 LED is used to signal external faults (process faults: overcur-

rent, imbalance, phase failures). When this occurs, the device will be in a 
safe, disconnected state. To leave this state, you will have to acknowledge 
the fault (

Chapter 4, “Device status and fault detection“, Page 50).

The green 

ON

L

, and 

R

 LEDs are used to indicate when the motor is running 

anticlockwise or clockwise.

1.5.6 Reset button

Faults are categorized as either process errors (e.g., phase failures) or device 
errors (e.g., internal device faults). Process error conditions can be acknow-
ledged manually by pressing the Reset pushbutton (

Chapter 4, “Device 

status and fault detection“).

The Reset button is also used to check the set rated motor current 
(

Chapter 3, “Commissioning“).

 Designation 

Color

PWR

green

ERR

red

ON

green

 Designation 

Color

PWR

green

ERR

red

L

green

R

green

For a detailed description of the various possible combinations 
between the status LED states and what they mean, please 
refer to 

Chapter 4, “Device status and fault detection“.

Summary of Contents for EMS Series

Page 1: ...Handbuch Manual 04 15 MN03407009Z DE EN Elektronischer Motorstarter EMS EMS Electronic Motorstarter...

Page 2: ...Verwendung elektronischer Systeme verarbeitet vervielf ltigt oder verbreitet werden nderungen vorbehalten All brand and product names are trademarks or registered trademarks of the owner concerned Eme...

Page 3: ...Geh use oder Schr nke d rfen nur im eingebauten Zustand Tischger te oder Portables nur bei geschlossenem Geh use betrieben und bedient werden Disconnect the power supply of the device Ensure that dev...

Page 4: ...erursachen In diesem Fall kann der Anwender verpflichtet sein ange messene Ma nahmen durchzuf hren Leitungen an den Klemmen MAN RES AUT d rfen nicht l nger als 30 m sein Measures should be taken to en...

Page 5: ...gang 11 2 Projektierung 12 2 1 Schaltungsbeispiele Direktstarter Wendestarter 12 2 1 1 Haupt und Steuerstrompfad beim Direktstarter EMS DO 24VDC 12 2 1 2 Haupt und Steuerstrompfad f r Wendestarter EMS...

Page 6: ...407009Z DE EN www eaton com 5 Anhang 23 5 1 Technische Daten 23 5 2 Sicherheitstechnische Funktionen 26 5 3 Ausl sekennlinien bei 20 C 27 5 4 Deratingkurven bei 100 Einschaltdauer EMS T 9 24VDC 27 5 5...

Page 7: ...reichen 0 1 nderungsprotokoll Gegen ber fr heren Ausgaben hat es folgende wesentliche nderungen gegeben 0 2 Zielgruppe Das Handbuch richtet sich an Fachpersonal das den elektronischen Motor starter EM...

Page 8: ...nweise vor Personensch den 0 3 3 Tipps VORSICHT Warnt vor gef hrlichen Situationen die m glicherweise zu leichten Verletzungen f hren WARNUNG Warnt vor gef hrlichen Situationen die m glicherweise zu s...

Page 9: ...urch diese werden mit einem erh hten Grad an Sicherheit die M glichkeiten von unzul ssig hohen Temperaturen und das Entstehen von Funken und Lichtb gen an Motoren bei denen dies im normalen Betrieb ni...

Page 10: ...ten angeboten Tabelle 1 bersicht ber die Ger tereihe EMS Ger tetyp Funktion Strombereich Versorgungs spannung Steuerspannung EMS DO T 2 4 24VDC Direktstarter mit Motorschutz 0 18 2 4 A AC 51 0 18 2 4...

Page 11: ...ngsspannung 1L1 3L2 5L3 b Ger tefu mit Aufnahme f r Tragschiene c LEDs PWR Versorgungsspannung ERR Meldung Fehler L Linkslauf R Rechtslauf ON Motorstart EMS D d 3 Phasen Ausgangsspannung 2T1 4T2 6T3 e...

Page 12: ...drehrichtung Die Ansteuerung erfolgt mit 24 V DC ber die Anschlussklemme E Enable erfolgt die Freigabe des Schaltbefehls f r die Motordrehrichtung Zur Freigabe des Schaltbefehls muss dieser Anschluss...

Page 13: ...ichnung des EMS zu achten 1 5 4 Absicherung Die Absicherung eines 3 Phasen Netzes gegen ber Kurzschluss kann auf die folgenden Arten geschehen Tabelle 2 Absicherung f r IEC Anwendung Tabelle 3 Absiche...

Page 14: ...m sicheren abgeschalteten Zustand Zum Verlassen dieses Zustandes ist eine Fehlerquittierung notwendig Kapitel 4 Ger testatus und Fehlererken nung Seite 20 Der Links bzw Rechtslauf des Antriebs wird du...

Page 15: ...einen Fehler erkennt wird das R ck melderelais angesteuert d h der Schlie erkontakt Kontakt 95 98 wird geschlossen bzw der ffner 95 96 ge ffnet Dieses Verhalten entspricht dem eines Motorschutzschalt...

Page 16: ...Wendestarter 2 1 1 Haupt und Steuerstrompfad beim Direktstarter EMS DO 24VDC Abbildung 2 Direktstarter K1 EMS DO 24VDC T1 Rechtslauf 2 1 2 Haupt und Steuerstrompfad f r Wendestarter EMS RO 24VDC Abbi...

Page 17: ...rters nur einka nalig abgeschaltet wird ist diese Art der Installation nach SIL 3 Kat 3 Kat 4 nur zul ssig wenn ein Fehlerausschluss f r Querschluss erlaubt ist Dies ist beispielsweise der Fall wenn d...

Page 18: ...Lebensdauer Abbildung 4 Haupt und Steuerstrompfad NOT HALT einkanalig verringerte Lebensdauer S2 NOT HALT S3 Reset NOT HALT einkanalig nach Kat 3 SIL 3 PL e EMS ROS mit ber geordneter Sicherheitsrelai...

Page 19: ...aler Betriebs zustand ist wie beispielsweise bei Schutzt r oder Zweihand Applikationen muss eine Schaltung nach Abschnitt 2 3 1 Haupt und Steuerstrompfad NOT HALT einkanalig und Abschnitt 2 3 2 Haupt...

Page 20: ...HALT einkanalig Abbildung 6 Haupt und Steuerstrompfad NOT HALT einkanalig S2 NOT HALT S3 Reset NOT HALT Applikation einkanalig nach Kat 3 SIL 3 PL e EMS ROS mit bergeordneter Sicherheitsrelais Kombin...

Page 21: ...T zweikanalig Abbildung 7 Haupt und Steuerstrompfad NOT HALT zweikanalig S2 NOT HALT S3 Reset NOT HALT Applikation zweikanalig nach Kat 3 SIL 3 PL e EMS ROS mit bergeordneter Sicherheitsrelais Kombina...

Page 22: ...he Motorstarter ist nach dem LED Test bereit f r eine Einstellung des Nennstroms Hierf r ist erforderlich dass kein Fehler beim Ger t vorliegt Die LED ERR ist aus 3 1 Nennstromeinstellung Stellen Sie...

Page 23: ...rden Eine 230 V AC Bremse ist am Anschluss 4 T2 und dem Sternpunkt des Motors anzuschlie en Die Ansteuerung von externen Bremsen erfolgt ber separate Hilfssch tze z B DILA LED Code Nennstrom mA PWR R...

Page 24: ...der Peripherie zu erkennen Bei einem erkannten Fehler befindet sich das Ger t im sicheren abgeschalte ten Zustand Alle internen Fehler sind nicht quittierbar sie werden im Ger t gespeichert Das Ger t...

Page 25: ...kslauf aufgetreten ein aus blinkend blinkend manuell Ein Fehler ist beim Rechtslauf aufgetreten ein blinkend aus blinkend manuell Fehler beim Herstellen des Systemzu standes Checksumme fehlerhaft Das...

Page 26: ...ers Schlie ers zwischen den Klemmen MAN und RES bzw A1 24VDC und RES realisiert werden Eine Quittierung wird ausgel st sobald am Eingang MAN eine positive Flanke erkannt wird Wird nach Ablauf einer Ze...

Page 27: ...r glichkeit EMV Elektrostatische Entladung IEC EN 61000 4 2 Luftentladung kV 8 8 Kontaktentladung kV 6 6 Elektromagnetische Felder IEC EN 61000 4 3 80 1000 MHz V m 10 10 1 4 2 GHz V m 10 10 2 2 7 GHz...

Page 28: ...essungsbetriebsstrom Ie EN 60947 1 AC51 EN60947 4 3 A 0 18 2 4 1 2 9 AC53a EN60947 4 2 A 0 18 2 4 1 2 6 5 Minimale Verlustleistung W 1 1 1 1 Maximale Verlustleistung W 3 3 14 6 Bemessungssto spannungs...

Page 29: ...chsler Kontaktmaterial Ag Legierung hartvergoldet Ag Legierung hartvergoldet Signalkontakt Leistungskontakt Schaltspannung maximal V 30 AC 36 DC 250 AC DC Schaltspannung minimal 100 mV 12 V AC DC Daue...

Page 30: ...ebungstemperatur C 40 40 MTTFd a 420 421 Abschaltzeit ms 40 EMS 2 4 80 EMS 9 40 EMS 2 4 80 EMS 9 sd FIT 49 47 su FIT 1818 1582 dd FIT 269 269 du FIT 2 7 2 4 SFF 99 8 99 8 DCS 2 6 2 9 DC 99 99 PFH 1 h...

Page 31: ...instellung gr er als 4 A 5 4 Deratingkurven bei 100 Einschaltdauer EMS T 9 24VDC Abbildung 10 Deratingkurve bei 100 Einschaltdauer IL Laststrom a Einzelger t b Angereiht mit 30 mm Abstand c Angereiht...

Page 32: ...otors ermitteln berstromfaktor IA IN 11 2 3 4 5 6 7 82 9 10 Anpassungsfaktor K 1 1 1 1 1 0 96 0 83 0 72 0 64 0 58 1 Gebrauchskategorie AC 51 2 Gebrauchskategorie AC 53a Beispiel 1 Beispiel 2 Motor mit...

Page 33: ...ird DFFRUGLQJ OLVW RQ SDJH DQG SURYLGHG WKDW LW LV LQVWDOOHG PDLQWDLQHG DQG XVHG LQ DSSOLFDWLRQ LQWHQGHG IRU ZLWK UHVSHFW WR WKH UHOHYDQW PDQXIDFWXUHUV LQVWUXFWLRQV LQVWDOODWLRQ VWDQGDUGV DQG JRRG HQJ...

Page 34: ...Sortiments 7 SHV ZLWKLQ WKH UDQJH Die Konformit tserkl rung gilt f r folgende Typen der Produktfamilie und in Kombination mit den darunter folgenden Produkten 7KH GHFODUDWLRQ RI FRQIRUPLW DSSOLHV WR W...

Page 35: ...8 Feedback output 41 2 Engineering 42 2 1 Sample DOL starter and reversing starter circuits 42 2 1 1 Main and control current paths for EMS DO 24VDC DOL starters 42 2 1 2 Main and control current path...

Page 36: ...ection 50 4 1 Device status 50 4 2 Error acknowledgment 52 5 Appendix 53 5 1 Technical Data 53 5 2 Technical safety functions 56 5 3 Tripping characteristics at 20 C 57 5 4 Derating curves for 100 dut...

Page 37: ...visions The following significant amendments have been introduced since previous issues 0 2 Target group This manual is intended for qualified personnel in charge of installing commissioning operating...

Page 38: ...m 0 3 2 Hazard warnings of personal injury 0 3 3 Tips CAUTION Warns of the possibility of hazardous situations that may possibly cause slight injury WARNING Warns of possibility of hazardous situation...

Page 39: ...ype e Increased Safety These measures improve the degree of safety and prevent impermissible high temperature and develop ment of sparking and arcing which is usually not found when motors are operate...

Page 40: ...Device type Function Current Range Supply voltage control voltage EMS DO T 2 4 24VDC DOL starter with motor protection 0 18 2 4 A AC 51 0 18 2 4 A AC 53a 24 V DC EMS DO T 9 24VDC DOL starter with mot...

Page 41: ...e 1L1 3L2 5L3 b Fixing bracket with mount for mounting rail c LEDs PWR supply voltage ERR message error L counterclockwise R clockwise ON motor start EMS D d 3 phase output voltage 2T1 4T2 6T3 e Feedb...

Page 42: ...of motor rotation They are actuated with 24 V DC Meanwhile connection terminal E Enable is used to enable the switching command for the direction of motor rotation To enable the switching com mand thi...

Page 43: ...ctly by referring to the motor starter s terminal designations 1 5 4 Protective element The following fuses can be used to protect a 3 phase supply system against short circuits Table 2 Fuse for IEC a...

Page 44: ...he device will be in a safe disconnected state To leave this state you will have to acknowledge the fault Chapter 4 Device status and fault detection Page 50 The green ON L and R LEDs are used to indi...

Page 45: ...motor starter detects a fault the feedback relay will be energized i e the N O contact contact 95 98 will be closed or N C con tact 95 96 will be opened This behavior is the same as that of a motor p...

Page 46: ...Main and control current paths for EMS DO 24VDC DOL starters Figure 2 DOL starter K1 EMS DO 24VDC T1 Clockwise rotation 2 1 2 Main and control current paths for EMS RO 24VDC reversing starters Figure...

Page 47: ...ff with a sin gle channel configuration this type of installation is only permissible for SIL 3 cat 3 cat 4 if cross fault fault exclusions are allowed This will be the case for example when the elect...

Page 48: ...Figure 4 Single channel main and control current path emergency stop reduced lifespan S2 Emergency stop S3 Reset Emergency stop single channel as per cat 3 SIL 3 PL e EMS ROS with higher level safety...

Page 49: ...rotective door and two hand control applications a circuit like the ones shown in Section 2 3 1 Main and control current path emergency stop single channel and Section 2 3 2 Main and con trol current...

Page 50: ...Figure 6 Main and control current path emergency stop single channel S2 Emergency stop S3 Reset Emergency stop configuration single channel as per cat 3 SIL 3 PL e EMS ROS with higher level safety rel...

Page 51: ...gure 7 Main and control current path emergency stop dual channel S2 Emergency stop S3 Reset Emergency stop configuration dual channel as per cat 3 SIL 3 PL e EMS ROS with higher level safety relay com...

Page 52: ...e ready for you to set the rated operational current To be able to set the rated operational cur rent the device must not be indicating any faults The ERR LED must be off 3 1 Setting the rated operati...

Page 53: ...d to terminals 2 T1 and 6 T3 A 230 V AC brake must be connected to terminal 4 T2 and to the motor s neutral External brakes are actuated using separate contactor relays e g DILA LED code Rated operati...

Page 54: ...aults peripheral faults When a fault is detected the device will be in a safe disconnected state Internal faults cannot be acknowledged and will be stored in the device If more than 14 internal faults...

Page 55: ...or has occurred at anticlockwise oper ation on off flashing flashing manual A fault occurred during anticlockwise rota tion on flashing off flashing manual Error while attempting to determine the syst...

Page 56: ...emented by con necting a pushbutton N O between the MAN and RES A1 24 V DC and RES terminals An acknowledgment signal will be triggered as soon as a positive edge is detected at the MAN input If a neg...

Page 57: ...magnetic compatibility EMC Electrostatic discharge IEC EN 61000 4 2 Air discharge kV 8 8 Contact discharge kV 6 6 Electromagnetic fields IEC EN 61000 4 3 80 1000 MHz V m 10 10 1 4 2 GHz V m 10 10 2 2...

Page 58: ...urrent Ie EN 60947 1 AC51 EN60947 4 3 A 0 18 2 4 1 2 9 AC53a EN60947 4 2 A 0 18 2 4 1 2 6 5 Minimum heat dissipation W 1 1 1 1 Max heat dissipation W 3 3 14 6 Rated impulse withstand voltage Uimp kV 6...

Page 59: ...changeover contact Contact material Ag alloy hard gold plated Ag alloy hard gold plated Signal contact Power contact Maximum switching voltage V 30 AC 36 DC 250 AC DC Minimum switching voltage 100 mV...

Page 60: ...re C 40 40 MTTFd a 420 421 Shutdown time ms 40 EMS 2 4 80 EMS 9 40 EMS 2 4 80 EMS 9 sd FIT 49 47 su FIT 1818 1582 dd FIT 269 269 du FIT 2 7 2 4 SFF 99 8 99 8 DCS 2 6 2 9 DC current 99 99 PFH 1 h 2 7 x...

Page 61: ...t settings greater than 4 A 5 4 Derating curves for 100 duty factor EMS T 9 24VDC Figure 10 Derating curve for 100 duty factor IL load current a Stand alone device b Connected in series with a clearan...

Page 62: ...nt factor IA IN 11 2 3 4 5 6 7 82 9 10 Adjustment factor K 1 1 1 1 1 0 96 0 83 0 72 0 64 0 58 1 Utilization category AC 51 2 Utilization category AC 53a Example 1 Example 2 Motor with overcurrent fact...

Page 63: ...det wird DFFRUGLQJ OLVW RQ SDJH DQG SURYLGHG WKDW LW LV LQVWDOOHG PDLQWDLQHG DQG XVHG LQ DSSOLFDWLRQ LQWHQGHG IRU ZLWK UHVSHFW WR WKH UHOHYDQW PDQXIDFWXUHUV LQVWUXFWLRQV LQVWDOODWLRQ VWDQGDUGV DQG JRR...

Page 64: ...des Sortiments 7 SHV ZLWKLQ WKH UDQJH Die Konformit tserkl rung gilt f r folgende Typen der Produktfamilie und in Kombination mit den darunter folgenden Produkten 7KH GHFODUDWLRQ RI FRQIRUPLW DSSOLHV...

Reviews: