EMR-4000
IM02602009E
Parameter
Description
Setting range
Default
Menu path
Scaling
Display of the measured values as primary, secondary,
or per unit values
Per unit values,
Primary values,
Secondary values
Primary values
[Operation
/General Settings]
Maint Mode
Activation Mode of the Arc Flash Reduction. Switching
into another mode is only possible when no Activation
Signal is active (pending).
Inactive,
Activation Manually,
Activation via
Comm,
Activation via DI
Inactive
[Service
/Maint Mode]
Maint Mode
Activated by
Activation Signal for the Arc Flash Reduction
Maintenance Switch
Only available if: Maint Mode Activated by = Activation
via DI
1..n, Dig Inputs
DI-8P X1.DI 7
[Service
/Maint Mode]
Program Mode
Program Mode
Either Motor Stop-
ped or Running,
Motor Stop
Either Motor
Stopped or
Running
[System Para]
System Module Input States
Name
Description
Assignment via
Ack LED-I
Module Input State: LEDs Acknowledgment by Digital Input.
[Device Para
/Ex Acknowledge]
Ack RO-I
Module Input State: Acknowledgment of the Relay Outputs.
[Device Para
/Ex Acknowledge]
Ack Comm-I
Module Input State: Acknowledge Communication via Digital Input.
The replica that Communication has received from the device is to
be reset.
[Device Para
/Ex Acknowledge]
PS1-I
State of the module input, respectively of the signal, that should
activate this Parameter Setting Group.
[Protection Para
/PSet-Switch]
PS2-I
State of the module input, respectively of the signal, that should
activate this Parameter Setting Group.
[Protection Para
/PSet-Switch]
PS3-I
State of the module input, respectively of the signal, that should
activate this Parameter Setting Group.
[Protection Para
/PSet-Switch]
PS4-I
State of the module input, respectively of the signal, that should
activate this Parameter Setting Group.
[Protection Para
/PSet-Switch]
Maint Mode-I
Module Input State: Arc Flash Reduction Maintenance Switch
[Service
/Maint Mode]