RI-F100-C

OP532-EMC3P

-P2C1-V01-EA

TON

PRODUCT PROFILE

96mm x 96mm

SPECIFICATIONS

I

IP rating 

: IP54 Front only (When fitted with rubber gasket)

 

 

  Pulse Duration : Selectable 50...300mS 

The meter is intended to be installed in Mechanical Environment `M1`,with 
Shock and Vibrations of low significance, as per 2004/22/EC Directive.                                                
The meter is intended to be installed in Electromagnetic Environment `E2`, 
as per 2004/22/EC Directive.

   

   

- Communication in progress 

LCD Indications 

:  

- Integration of energy

PT Primary 

: 100V...600V (Programmable for any value)

Temperature 

: Operating

 

: -10

°

C...55

°

C

Display  

: Liquid crystal display with backlight    4 lines,    

Display Update Time  : 1 second for all parameters

   

   

- Maximum & Minimum Demand of Power

Auxiliary 

: 85...270V AC, 47...63Hz

Installation Category  : III (300V L-N)

Weight 

: 318gms

   

  Current indication as percentage of  CT rating

   

  PRG   

- Unit is in configuration menu

Meter Type 

: Indoor

Wiring Input 

: 3 Ø 

4 wire, 1 Ø 

2 wire - P1, 3 Ø 

- 3

 wire

   

  4 digits per line to show electrical Parameters 

CT Primary 

: 1/5A...6,000A (Programmable for any  Value)

Humidity 

: 85% non-condensing

Mounting 

: Panel mounting

Display Scrolling 

: Automatic / Manual

   

  Pulse Resolution: Selectable 0.01...99.99kWh

PT Secondary 

: 173...415V AC (L-L) (Programmable for any value)

CT Secondary 

: 1 or 5A (x1.2)

Rated Input Voltage 

: 3x230/400V 

   

  5th line, 8 digits to show energy Bar graph for 

Frequency Range 

: 47...63Hz (MID approved for 50Hz)

   

 

Storage

 

: -20

°

C...75

°

C

Pulse Output  

:  External 5...27VDC max./100mA max.

Communications  

: RS485 Modbus RTU

WIRING GUIDELINES

      equipment prior to undertaking any work. Always confirm absence of
        supply prior to starting work using appropriate voltage detection

    2. Wiring shall be done strictly according to the terminal layout. Confirm that 
        all connections are correct before energizing the equipment.
    3. To reduce electromagnetic interference use of wires with adequate 
       ratings and twists of equal size are recommended. All connection should be

    1. To prevent the risk of electrocution, always isolate the power supply to the

     kept as short as possible.
    4. Routing of connecting cables shall be away from any internal EMI source.

 

 

 

    5.All cables used for connections must have a  cross  section 

    6. Copper cable should be used. (stranded or solid core cable)
    7. All wiring to be in accordance with applicable local standards.

2  

2     

 

     

0

        of 0.5mm to 2.5mm . (20 to14AWG ; 75 C (min) )

        equipment. 

SAFETY PRECAUTIONS

RESOLUTION

PT Ratio x CT Ratio

kWh

SERIAL COMMUNICATION

Interface standard and protocol 

Communication address

Transmission Mode

Data types

Transmission distance

Transmission speed

Parity

Stop bits

RS485 AND MODBUS RTU

1...255

 Half duplex

Float, Hex and Integer 

500 Meter maximum

300, 600,1200, 2400, 4800, 9600, 
19200 (in bps)

None, Odd, Even

1 or 2

ACCURACY

Accuracy

Measurement 

Frequency 
For L-N > 20V,
For L-L  > 35V 

Measurement 

Accuracy

Voltage V

L-N 

Voltage V

L-L 

Current 

±

0.5% of F.S.

±

0.5% of F.S.

±

0.5% of F.S.

±

0.1% of F.S.

100 ms 

(max and independent of    baud rate)

 

Response time

EN50470-3: CI.B

EN62053-23: CI.2

Active Power 

Apparent power

Reactive Power

1%

1%

1%

Power factor 

Active energy

Reactive energy

Apparent energy

MAX/MIN 
Active Power

MAX/MIN 
Reactive Power

MAX Apparent Power

±

0.01 (Digit)

1%

Class 1

1%

1%

 

PT Primary  

 

 

Factory default 

NOTE: 
 

Once Programming Mode Is entered The parameters 
below will be locked out after 15 Minutes. No further 

 

CT Secondary    

 

Pulse Duration 

        

 

Network Selection  

 

PT secondary

 

   

 

 

 

Energy Reset 

 

CT Primary 

 

 

Pulse width

 

adjustment is possible without returning to supplier.

CONFIGURATION LOCK PARAMETER DESCRIPTION

Doc. name : OP INST EMC3P-P2C1                                OP532-EMC3P-P2C1-V01-EATON   (Page 1 of 6)

Product

Outputs

Certification

MID

EMC3P-P2C1

Rs485 (Modbus RTU) & Pulse  

(F.S - Full Scale)

I

TO COMPLY WITH MID CERTIFICATION 

THE CT RATIO MUST BE SET BEFORE 

PUTTING THE METER INTO SERVICE

NOTE : 

EMC3P-P2C1

0.01K

0.1K

<15

<150

Note:

 

blinks every 5 sec. This indicates energy is being consumed.

ORDER INFORMATION 

          

CAUTION

 

 

1.   Read complete instructions prior to installation or operation of the unit.
2.  Risk of electric shock. Only to be installed by competent personnel.
3.  The equipment in its installed state must not come in  close proximity to any 
    heating sources, oils, steam, caustic vapors or other unwanted process 
    by-products.

Safety related notifications, symbols and instructions that appear in this 
operating manual or on the equipment must be strictly followed to ensure the 
safety of personnel as well as the instrument. 

      No repairs, maintenance or adjustments are possible. 

If the equipment is not used in a manner specified by the manufacturer it may 
impair the protection provided     by the equipment.
    Do not use the equipment if there is any mechanical damage.
    Ensure that the equipment is supplied with correct voltage.

Press 

I

 key for 3 sec. to check the current connection. If current connection 

reverse meter will show in which phase connection is reversed. 
0 - No any phase 

2 - 2nd phase 

1 - 1st phase 

3 - 3rd phase

CURRENT CONNECTION INDICATION

Press PF key for 10 sec, displays CRC in first two row, HW & SW version no 
in 3rd and 4th raw & serial no in last row.

DEVICE IDENTIFICATION

In automatic mode when any key is pressed, unit temporarily switches to 
manual mode and the appropriate page is displayed, also if no key is 
pressed for 5 sec, unit resumes automatic mode.

Press E (    ) button for 3 seconds to toggle between Automatic

 

and Manual 

mode.

Note

 

By default unit operates in automatic mode. 

In automatic mode online pages scroll automatically at the rate of 5 
seconds per page. All the time, total import active energy will be displays & 
at any other page of energy if no key is pressed for 1 min. 

AUTOMATIC / MANUAL PAGE SCROLLING 

1K

0.01M
0.1M

<1500

<15000

>15000