background image

EDR-5000

IM02602007E

Forcing RTDs*

* = Availability depends on ordered device.

The parameters, their defaults, and setting ranges have to be taken from 
RTD/UTRD section.

Principle – General Use

The User MUST ENSURE that the RTDs operate normally after maintenance 
is completed.

  

If the RTDs do not operate normally,

 

the protective device 

WILL NOT provide protection.

For commissioning purposes or for maintenance, RTD temperatures can be set by force.

Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/URTD], RTD temperatures can be set by force:

Permanent; or
Via timeout.

If they are set with a timeout, they will keep their “Forced Temperature” only as long as this timer runs.

  

If the timer 

expires, the RTD will operate normally.

  

If they are set as »

Permanent«, they will keep the “Forced Temperature” 

continuously.  This menu will show the measured values of the RTDs until the User activates the force mode by calling 
up the »

Function«.  As soon as the force mode is activated, the shown values will be frozen as long as this mode is 

active.  Now the User can force RTD values.  As soon as the force mode is deactivated, measured values will again be 
shown.

www.eaton.com

879

Summary of Contents for EDR-5000

Page 1: ...EDR 5000 DISTRIBUTION RELAY Installation Operation and Maintenance Software Version 3 0 c IM02602007E Revision E English...

Page 2: ...x avg phasors and angles Power Fund and RMS MVA Mwatt Mvar PF Metering Statistics and Demand standard 3 1 3 EDR 5000 74 TC Zone Interlocking SNTP Breaker Wear Programmable Logic 50 BF 51R 50R 46 67P 6...

Page 3: ...ltage Transformer Measuring Inputs 46 Typical Connection Diagrams 53 Slot X2 Relay Output Card 57 Slot X6 Digital Inputs 60 Digital Inputs 60 Slot X100 Ethernet Interface 63 Slot X103 Data Communicati...

Page 4: ...emand Management 191 Signals of the Demand Management States of the Outputs 191 Global Protection Parameter of the Demand Management 192 States of the Inputs of the Demand Management 195 Resets 196 Ma...

Page 5: ...ivate Respectively to Block Temporary Protection Functions 402 Protection Prot Module 404 How to Block All Protective and Supervisory Functions 404 Direct Commands of the Protection Module 411 Global...

Page 6: ...27 t LVRT Low Voltage Ride Through 771 UFLS Under Frequency Load Shedding 785 ExP External Protection 803 Supervision 809 BF Breaker Failure 50BF 62BF 809 CTS Current Transformer Supervision 834 LOP L...

Page 7: ...tor 910 URTD Interface 910 Boot Phase 910 Standards 911 Approvals 911 Design Standards 911 High Voltage Tests IEC 60255 1 911 EMC Immunity Tests 912 EMC Emission Tests 913 Environmental Tests 914 Mech...

Page 8: ...EDR 5000 IM02602007E md5_1 md5_2 RMS Handoff 0 File generated EDR 5000_user_manual_eaton_en odt This manual applies to devices version Version 3 0 c Build 28461 www eaton com 8...

Page 9: ...nging this manual and without previous notice Therefore no claim can be brought based on the information and descriptions included in this manual Text graphics and formulas do not always apply to the...

Page 10: ...rized modifications 1 constitute misuse and or negligence within the meaning of the product warranty thereby excluding warranty coverage for any resulting damage and 2 invalidate product certification...

Page 11: ...The manufacturer cannot be held liable for any resulting damage The User alone bears the risk if this device is used for any application for which it was not designed As to the appropriate use of the...

Page 12: ...s cigarette packages cellophane wrappers vinyl books or folders plastic bottles and plastic ash trays away from the device the modules and the work area as much as possible 4 Do not remove any printed...

Page 13: ...ains the device templates The device templates MUST BE installed to allow PowerPort E to configure a device off line Please make sure the product label wiring diagram type code and materials and descr...

Page 14: ...pre defined value can be selected 1 n Assignment List Name 1 n VeEnable No assignment 1 n No a ssignment 1 Name 1 n Assignment List Parameter of a Module Input with special values An 1 n output from...

Page 15: ...is expired the output becomes 1 too The time stage will be reset by 0 at the input Thus the output will be set to 0 at the same time Time stage minimum pulse width The pulse width name t will be start...

Page 16: ...SIGNALS are indicated by right and left double arrow heads and small caps Paths are indicated by brackets Software and Device names are written in italic Module and Instance Element names are display...

Page 17: ...ction module will lead to a general trip Each trip of an active trip authorized protection module will lead to a general trip Each trip of an active trip authorized protection module will lead to a ge...

Page 18: ...the device type will lead to a phase selective general pickup collective pickup Each phase selective pickup of a module I IG V VX depending on the device type will lead to a phase selective general p...

Page 19: ...m Q V Decoupling Distributed Generator Q V Decoupling Distributed Generator 40 Please Refer to Diagram CTS Pickup CTS Pickup 44 45 Please Refer to Diagram Analog Values Please Refer to Diagram Analog...

Page 20: ...Read Only Lv0 Prot Lv1 Prot Lv2 Supervisor Lv3 Control Lv1 Control Lv2 Parameters can only be read within this level This level enables execution of Resets and Acknowledgements This level enables mod...

Page 21: ...s the directional feature of the over current protections then the device no longer trips in a directional way but merely in a non directional way The manufacturer does not accept liability for any pe...

Page 22: ...Sensitive Ground Current 5A 1A Phase Current 5A 1A Ground Current 5A 1A EDR 5000 Communication Communication A Without B RS 485 Modbus RTU DNP RTU C Ethernet Modbus TCP DNP UDP TCP D Fiber Optics Prof...

Page 23: ...and a Projection Mount To order the EDR 5000 with a Standard Mount append the device code with a zero 0 To order the EDR 5000 2 with a Projection Mount append the device code with a one 1 Refer to the...

Page 24: ...with terminals B Modbus TCP DNP3 0 Ethernet 100MB RJ45 C Modbus RTU DNP3 0 Fibre optic interface ST connector F DNP3 0 Modbus RTU RS485 D SUB interface G IEC 61850 Ethernet 100MB RJ45 H Modbus RTU in...

Page 25: ...00 2 A 8 DI 11 Outputs Relays Removable Terminals Zone Interlocking 0 5A 1A Phase and Ground CTs Power Supply Range 19 300 Vdc 40 250 Vac B Modbus RTU RS 485 A Without Conformal Coating 1 Projection P...

Page 26: ...he auxiliary voltage is switched off unsafe voltages remain at the device connections Outline Projection Mount Door Cut out The housing must be carefully grounded Connect a ground cable AWG 12 10 4 to...

Page 27: ...onal injury or damage the relay Outline Standard Mount Door Cut out The housing must be carefully grounded Connect a ground cable AWG 12 10 4 to 6 mm2 15 In lb 1 7 Nm to the housing using the screw th...

Page 28: ...the individual modules can be determined from the connection diagram attached to the top of your device Overview of Slots Housing B2 Schematic Diagram The housing must be carefully grounded Connect a...

Page 29: ...6 mm2 15 In lb 1 7 Nm to the housing using the screw that is marked with the ground symbol at the rear side of the device The power supply card needs a separate ground connection AWG 14 2 5 mm2 5 7 In...

Page 30: ...d device type The different variants have a different scope of functions Available assembly groups in this slot DI8 X1 This assembly group comprises a wide range power supply unit and two non grouped...

Page 31: ...s to be configured Wrong switching thresholds can result in malfunctions wrong signal transfer times The digital inputs are provided with different switching thresholds that are configurable two AC an...

Page 32: ...DI1 COM2 DI2 DI3 DI4 DI5 DI6 DI7 DI8 COM3 Donot use DI 8P X COM3 N C Donot use 1 3 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Power Supply 1 2 3 4 5 6 7 8 9 10 11 12 COM1 13 14 15 16 17 18 V Power Supp...

Page 33: ...pe The different variants have a different scope of functions Available assembly groups in this slot RO 4Z X2 Assembly Group with four Relay Outputs two Form A and two Form C and Zone Interlocking The...

Page 34: ...elay Outputs section the assignment of the Relay Outputs is specified The changeable signals are listed in the Assignment List section Make sure that the tightening torque is 5 7 In lb 0 56 0 79 Nm Pl...

Page 35: ...com 35 Do not use Do not use RO3 CMN RO3 N O RO3 N C 1 3 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 RO 4Z X RO1 N O RO2 N O COM OUT IN COM RO4 CMN RO4 N O RO4 N C 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16...

Page 36: ...tive ground current measuring card Available assembly groups in this slot TI 4 X3 Standard ground current measuring card TIS 4 X3 Sensitive Ground current measuring card The Technical data of the sens...

Page 37: ...hort circuited before the current circuit to the device is opened The current measuring inputs may exclusively be connected to current measuring transformers with galvanic separation Do not mix the in...

Page 38: ...E Terminal Markings Pin Assignment www eaton com 38 IA 1A IA N IA 5A IB 1A IB N IC 1A IC N IC 5A IX 1A IX N IX 5A IB 5A 1 2 3 4 5 6 7 8 10 11 9 12 1 2 3 4 5 6 7 8 9 10 11 12 IA 1A 5A N IB 1A 5A N IC 1...

Page 39: ...transformers have to be short circuited before the current circuit to the device is opened The current measuring inputs may exclusively be connected to current measuring transformers with galvanic se...

Page 40: ...E Terminal Markings Pin Assignment www eaton com 40 IA 1A IA N IA 5A IB 1A IB N IC 1A IC N IC 5A IX 1A IX N IX 5A IB 5A 1 2 3 4 5 6 7 8 10 11 9 12 1 2 3 4 5 6 7 8 9 10 11 12 IA 1A 5A N IB 1A 5A N IC 1...

Page 41: ...ive current measuring inputs is the measurement of small currents like they could occur in isolated and high resistance grounded networks Due to the sensitiveness of these measuring inputs don t use t...

Page 42: ...07E 3 phase 3 wire IG Calculated www eaton com 42 A B C IA IB IC 1 X 2 3 4 5 6 7 8 9 10 11 12 Three phase Current Measurement Inom Secondary 5 A IA 1A 5A N IB 1A 5A N IC 1A 5A N IX 1A 5A N IB IC IA IR...

Page 43: ...IB 1A 5A N IC 1A 5A N IX 1A 5A N Warning The shielding at the dismantled end of the line has to be put through the zero sequence current transformer and has to be grounded at the cable side ZeroSequen...

Page 44: ...m 4th CT on Neutral www eaton com 44 A B C IA IB IC 1 X 2 3 4 5 6 7 8 9 10 11 12 4 wire system 4th CT on Neutral In secondary 5 A IA 1A 5A N IB 1A 5A N IC 1A 5A N IX 1A 5A N IB IC IA N IN IN IX meas I...

Page 45: ...g Neutral www eaton com 45 A B C IA IB IC 1 X 2 3 4 5 6 7 8 9 10 11 12 4 wire system with ground current CT Toroidal involving Neutral In secondary 5 A IA 1A 5A N IB 1A 5A N IC 1A 5A N IX 1A 5A N IB I...

Page 46: ...X4 Voltage Transformer Measuring Inputs Rear side of the device Slots This slot contains the voltage transformer measuring inputs www eaton com 46 X1 X2 X3 X100 X102 X5 X6 X104 X4 X103 slot3 slot4 slo...

Page 47: ...input is to be used for VX Make sure that the tightening torque is 1 2 1 6 Nm 11 15 In lb The rotating field of your power supply system has to be taken in to account Make sure that the voltage trans...

Page 48: ...EDR 5000 IM02602007E Terminal Marking Pin assignment www eaton com 48 VA 1 1 2 6 3 7 8 5 4 VA 2 VB 1 VB 2 VC 1 VC 2 VX1 1 VX1 2 1 2 3 4 5 6 7 8 X VX VX VC VC VB VB VA VA...

Page 49: ...on functionality VT Check Measuring Values Connect a three phase measuring voltage equal to the rated voltage to the relay Take the connection of the measuring transformers open delta Wye connection i...

Page 50: ...2602007E VT Wye www eaton com 50 A B C VAB VBC VCA VA VB VC VA A C B N VB VC VAB VBC VCA 1 X 2 3 4 5 6 7 8 Three phase voltage measurement wiring of the measurement inputs star connection VX VX VC VC...

Page 51: ...51 1 X 2 3 4 5 6 7 8 A B C VAB VBC VCA VA VB VC A C B N VB VC VAB VBC VCA VA n VX Three phase voltage measurement wiring of the measurement inputs star connection Measurement of the residual voltage...

Page 52: ...DR 5000 IM02602007E VT Open Delta www eaton com 52 A B C VAB VBC VCA A C B VAB VBC VCA 1 X 2 3 4 5 6 7 8 Two phase voltage measurement wiring of the measuring inputs Open Delta VX VX VC VC VB VB VA VA...

Page 53: ...tion Diagrams Wye VTs and 1 A CTs in Residual Connection www eaton com 53 1 X4 2 3 4 5 6 7 8 A B C C B A A B C 1 X3 2 3 4 5 6 7 8 9 10 11 12 IX IA 1A 5A N IB 1A 5A N IC 1A 5A N IX 1A 5A N IA IB IC IB...

Page 54: ...de of the Breaker and 1A CTs in Residual Connection www eaton com 54 1 X4 2 3 4 5 6 7 8 A B C C B A A B C 1 X3 2 3 4 5 6 7 8 9 10 11 12 IX IA 1A 5A N IB 1A 5A N IC 1A 5A N IX 1A 5A N IA IB IC IB IC IA...

Page 55: ...VTs Input Wiring and 1 A CTs in Residual Connection www eaton com 55 C B A A B C 1 X3 2 3 4 5 6 7 8 9 10 11 12 IX IA 1A 5A N IB 1A 5A N IC 1A 5A N IX 1A 5A N IA IB IC IB IC IA A B C 1 X4 2 3 4 5 6 7...

Page 56: ...side of the breaker and 1A CTs in Residual Connection www eaton com 56 A B C 1 X4 2 3 4 5 6 7 8 C B A A B C 1 X3 2 3 4 5 6 7 8 9 10 11 12 IX IA 1A 5A N IB 1A 5A N IC 1A 5A N IX 1A 5A N IA IB IC IB IC...

Page 57: ...e ordered device type The different variants have a different scope of functions Available assembly groups in this slot RO 6 X2 Assembly Group with 6 Relay Outputs The available combinations can be ga...

Page 58: ...ts section the assignment of the Relay Outputs is specified The changeable signals are listed in the Assignment List section Make sure that the tightening torque is 5 7 In lb 0 56 0 79 Nm Please caref...

Page 59: ...9 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 RO3 RO1 RO2 RO4 RO5 RO6 X RO1 CMN RO1 N O RO1 N C RO2 CMN RO2 N O RO2 N C RO3 CMN RO3 N O RO3 N C RO4 CMN RO4 N O RO4 N C RO5 CMN RO5 N O RO5 N C RO6 CMN...

Page 60: ...oups in this slot DI 8 X6 Assembly Group with 8 Digital Inputs The available combinations can be gathered from the ordering code Digital Inputs This module is provided with 8 grouped digital inputs In...

Page 61: ...list the states of the digital inputs are assigned to the module inputs e g I 1 The digital inputs are provided with different switching thresholds can be parameterized two AC and five DC input ranges...

Page 62: ...nt www eaton com 62 1 X 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 n c n c n c n c n c n c n c n c n c COM1 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI2 DI3 DI1 DI5 DI6 DI4 DI8 COM1 DI7 DI 8 X 1 3 2 4 5 6 7 8...

Page 63: ...of the device Slots An Ethernet interface may be available depending on the device type ordered The available combinations can be gathered from the ordering code www eaton com 63 X1 X2 X3 X100 X102 X...

Page 64: ...EDR 5000 IM02602007E Ethernet RJ45 Terminal Marking www eaton com 64 1 8 TxD TxD RxD N C N C RxD N C N C...

Page 65: ...unication interface Available assembly groups in this slot RS485 Terminals for Modbus and DNP Ethernet Interface for Modbus and DNP Fiber Optics for Modbus and DNP D Sub for Modbus and DNP Ethernet fo...

Page 66: ...bus connection cable must be shielded The shielding has to be fixed at the screw that is marked with the ground symbol at the rear side of the device The communication is Half Duplex www eaton com 66...

Page 67: ...the Bus Wiring Example Device at the End of the BUS Using the Integrated Terminal Resistor www eaton com 67 6 4 5 3 2 1 5V GND R1 560 R2 120 Protective Relay B B A A R1 R2 R1 HF Shield 6 4 5 3 2 1 5V...

Page 68: ...1 3 2 4 5 6 TR P B A B A B A B A TR N TR N TR N TR N Common Common Common Common HF Shield HF Shield HF Shield HF Shield 2 2nF internal 2 2nF internal 1 3 2 4 5 6 TR P 1 3 2 4 5 6 TR P 1 3 2 4 5 6 TR...

Page 69: ...IRIG B00X and Supervision Contact Rear side of the device Slots This comprises the IRIG B00X and the System contact Supervision Contact www eaton com 69 X1 X2 X3 X100 X102 X5 X6 X104 X4 X103 slot3 slo...

Page 70: ...o the Self Supervision section The System OK contact SC relay cannot be configured The system contact is a Form C contact that picks up when the device is free from internal faults While the device is...

Page 71: ...EDR 5000 IM02602007E Slot X120 PC Interface USB Mini B www eaton com 71 B1 B2 und B3 Housing USB Interface for Parameter Setting and Evaluation Software X120...

Page 72: ...IM02602007E Control Wiring Diagram Below is the recommended control wiring schematic for the EDR 5000 Wiring Diagrams Please refer to the file edr 5000_wiring_diagrams pdf on your manual CD www eaton...

Page 73: ...h of the digital inputs Nominal voltage Debouncing time A state change will only be adopted by the digital input after the debouncing time has expired and Inverting where necessary The debouncing time...

Page 74: ...r Setting Wrench Click on Add and assign a target Assign where required additional targets Deleting an assignment Select as described above a Digital Input that should be edited at the HMI Call up the...

Page 75: ...1 Checking the Assignments of a Digital Input In order to check the targets that a Digital Input is assigned to please proceed as follows Call up menu Device Parameter Digital Inputs Navigate to the...

Page 76: ...e Para Digital Inputs DI 8P X1 Group 1 Debouncing Time 1 A change of the state of a digital input will only be recognized after the debouncing time has expired become effective Thus transient signals...

Page 77: ...tal Inputs DI 8P X1 Group 3 Debouncing Time 3 A change of the state of a digital input will only be recognized after the debouncing time has expired become effective Thus transient signals will not be...

Page 78: ...Time 20 ms 50 ms 100 ms 20 ms Device Para Digital Inputs DI 8P X1 Group 3 Inverting 7 Inverting the input signals Inactive Active Inactive Device Para Digital Inputs DI 8P X1 Group 3 Debouncing Time 7...

Page 79: ...DI 8P X Signal Description DI 1 Signal Digital Input DI 2 Signal Digital Input DI 3 Signal Digital Input DI 4 Signal Digital Input DI 5 Signal Digital Input DI 6 Signal Digital Input DI 7 Signal Digi...

Page 80: ...will only be recognized after the debouncing time has expired become effective Thus transient signals will not be misinterpreted No Debouncing Time 20 ms 50 ms 100 ms 20 ms Device Para Digital Inputs...

Page 81: ...puts DI 8 X6 Group 1 Inverting 5 Inverting the input signals Inactive Active Inactive Device Para Digital Inputs DI 8 X6 Group 1 Debouncing Time 5 A change of the state of a digital input will only be...

Page 82: ...ctive Device Para Digital Inputs DI 8 X6 Group 1 Debouncing Time 8 A change of the state of a digital input will only be recognized after the debouncing time has expired become effective Thus transien...

Page 83: ...ific functions on digital inputs Alias Example The 52a contact will be assigned connected to Digital input1 DI1 Once the 52a is aliased linked on the DI1 the signal WiredInput 52A can be used instead...

Page 84: ...uts TOCa M1 Main 1 Breaker Connected 1 n Dig Inputs Device Para Wired Inputs 43 10 M1 Main 1 Breaker Selected To Trip 1 n Dig Inputs Device Para Wired Inputs 52a M2 Main 2 Breaker Closed 1 n Dig Input...

Page 85: ...nputs Device Para Wired Inputs 43 10 T Tie Breaker Selected To Trip 1 n Dig Inputs Device Para Wired Inputs 43 M System In Manual 1 n Dig Inputs Device Para Wired Inputs 43 A System in Auto 1 n Dig In...

Page 86: ...ara Wired Inputs TOCa M2 I State of the module input Main 2 Breaker Connected Device Para Wired Inputs 43 10 M2 I State of the module input Main 2 Breaker Selected To Trip Device Para Wired Inputs 52a...

Page 87: ...will keep it s position as long as it has not been reset and as long as the power supply feeds the protective relay In the case of a loss of power to the protective device the relays will return to th...

Page 88: ...verting 4 Assignment 5 Inverting 5 OR Inactive Active Latched Assignment 6 Inverting 6 Assignment 7 Inverting 7 OR OR AND State of the Relay Output Acknowledge HMI Acknowledge 1 n Assignment List Ackn...

Page 89: ...cknowledgment Options Relay output contacts can be acknowledged Via the push button Ack Rst at the operating panel If Latched is active each relay output contact can be acknowledged by a signal for ex...

Page 90: ...X2 Force all Outs By means of this function the normal Relay Output State can be overwritten forced The relay can be set from normal operation relay works according to the assigned signals to force e...

Page 91: ...n the normal Relay Output State can be overwritten forced The relay can be set from normal operation relay works according to the assigned signals to force energized or force de energized state Normal...

Page 92: ...l that acknowledges the corresponding Relay Output can be assigned to each Relay Output The acknowledgement signal is only effective if the parameter Latched is set to active Only available if Latched...

Page 93: ...f the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 4Z X2 RO 1 Assignment 5 Assignment 1 n Assignment List Device Para Relay Outputs RO 4Z X2 RO 1 Inverting 5 Inverting of the...

Page 94: ...ve Device Para Relay Outputs RO 4Z X2 RO 2 Acknowledgment Acknowledgment Signal An acknowledgment signal that acknowledges the corresponding Relay Output can be assigned to each Relay Output The ackno...

Page 95: ...ignment 1 n Assignment List Device Para Relay Outputs RO 4Z X2 RO 2 Inverting 4 Inverting of the state of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 4Z X2 RO 2 Assignmen...

Page 96: ...fines whether the Relay Output will be latched when it picks up Inactive Active Inactive Device Para Relay Outputs RO 4Z X2 RO 3 Acknowledgment Acknowledgment Signal An acknowledgment signal that ackn...

Page 97: ...f the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 4Z X2 RO 3 Assignment 4 Assignment 1 n Assignment List Device Para Relay Outputs RO 4Z X2 RO 3 Inverting 4 Inverting of the...

Page 98: ...a Relay Outputs RO 4Z X2 RO 4 t Off Delay Switch Off Delay 0 00 300 00s 0 2s Device Para Relay Outputs RO 4Z X2 RO 4 Latched Defines whether the Relay Output will be latched when it picks up Inactive...

Page 99: ...ignment 1 n Assignment List Device Para Relay Outputs RO 4Z X2 RO 4 Inverting 3 Inverting of the state of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 4Z X2 RO 4 Assignmen...

Page 100: ...tep of a two step process to inhibit the operation or the relay outputs Please refer to DISARMED for the second step Inactive Active Inactive Service Test Mode Prot inhibit WARNING Cont DISARMED RO 4Z...

Page 101: ...uration of this time That means for the duration of this time the Relay Output does not show the state of the signals that are assigned on it Only available if Mode Timeout DISARM 0 00 300 00s 0 03s S...

Page 102: ...itiated the setting are fallen back and the hold time is expired Device Para Relay Outputs RO 4Z X2 RO 1 RO2 1 Module Input State Assignment Device Para Relay Outputs RO 4Z X2 RO 2 RO2 2 Module Input...

Page 103: ...Relay Outputs RO 4Z X2 RO 2 RO3 1 Module Input State Assignment Device Para Relay Outputs RO 4Z X2 RO 3 RO3 2 Module Input State Assignment Device Para Relay Outputs RO 4Z X2 RO 3 RO3 3 Module Input...

Page 104: ...O 4 RO4 3 Module Input State Assignment Device Para Relay Outputs RO 4Z X2 RO 4 RO4 4 Module Input State Assignment Device Para Relay Outputs RO 4Z X2 RO 4 RO4 5 Module Input State Assignment Device P...

Page 105: ...er to safely perform maintenance while eliminating the risk of taking an entire process off line Note Zone Interlocking and Supervision Contact cannot be disarmed YOU MUST ENSURE that the relays are A...

Page 106: ...outputs of an entire assembly group has precedence to forcing a single relay output Normal De Energized Energized Normal Service Test Mode Prot inhibit WARNING Cont Force RO RO 6 X5 Force RO1 By means...

Page 107: ...n the normal Relay Output State can be overwritten forced The relay can be set from normal operation relay works according to the assigned signals to force energized or force de energized state Normal...

Page 108: ...l that acknowledges the corresponding Relay Output can be assigned to each Relay Output The acknowledgement signal is only effective if the parameter Latched is set to active Only available if Latched...

Page 109: ...of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 6 X5 RO 1 Assignment 5 Assignment 1 n Assignment List Device Para Relay Outputs RO 6 X5 RO 1 Inverting 5 Inverting of the s...

Page 110: ...Inactive Device Para Relay Outputs RO 6 X5 RO 2 Acknowledgment Acknowledgment Signal An acknowledgment signal that acknowledges the corresponding Relay Output can be assigned to each Relay Output The...

Page 111: ...signment 1 n Assignment List Device Para Relay Outputs RO 6 X5 RO 2 Inverting 4 Inverting of the state of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 6 X5 RO 2 Assignment...

Page 112: ...Defines whether the Relay Output will be latched when it picks up Inactive Active Inactive Device Para Relay Outputs RO 6 X5 RO 3 Acknowledgment Acknowledgment Signal An acknowledgment signal that ac...

Page 113: ...of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 6 X5 RO 3 Assignment 4 Assignment 1 n Assignment List Device Para Relay Outputs RO 6 X5 RO 3 Inverting 4 Inverting of the s...

Page 114: ...a Relay Outputs RO 6 X5 RO 4 t Off Delay Switch Off Delay 0 00 300 00s 0 2s Device Para Relay Outputs RO 6 X5 RO 4 Latched Defines whether the Relay Output will be latched when it picks up Inactive Ac...

Page 115: ...signment 1 n Assignment List Device Para Relay Outputs RO 6 X5 RO 4 Inverting 3 Inverting of the state of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 6 X5 RO 4 Assignment...

Page 116: ...O 4 Operating Mode Operating Mode Norm De energ Norm Energ Norm De energ Device Para Relay Outputs RO 6 X5 RO 5 t Off Delay Switch Off Delay 0 00 300 00s 0 2s Device Para Relay Outputs RO 6 X5 RO 5 La...

Page 117: ...of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 6 X5 RO 5 Assignment 3 Assignment 1 n Assignment List Device Para Relay Outputs RO 6 X5 RO 5 Inverting 3 Inverting of the s...

Page 118: ...ay Outputs RO 6 X5 RO 5 Assignment 7 Assignment 1 n Assignment List Device Para Relay Outputs RO 6 X5 RO 5 Inverting 7 Inverting of the state of the assigned signal Inactive Active Inactive Device Par...

Page 119: ...elay Outputs RO 6 X5 RO 6 Inverting 1 Inverting of the state of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 6 X5 RO 6 Assignment 2 Assignment 1 n Assignment List Device P...

Page 120: ...ay Outputs RO 6 X5 RO 6 Inverting 6 Inverting of the state of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 6 X5 RO 6 Assignment 7 Assignment 1 n Assignment List Device Par...

Page 121: ...ce Test Mode Prot inhibit WARNING Cont DISARMED RO 6 X5 Force Mode By means of this function the normal Relay Output States can be overwritten forced in case that the Relay Output is not in a disarmed...

Page 122: ...Relay Outputs RO 6 X5 RO 1 RO1 5 Module Input State Assignment Device Para Relay Outputs RO 6 X5 RO 1 RO1 6 Module Input State Assignment Device Para Relay Outputs RO 6 X5 RO 1 RO1 7 Module Input Sta...

Page 123: ...ate Assignment Device Para Relay Outputs RO 6 X5 RO 2 RO2 6 Module Input State Assignment Device Para Relay Outputs RO 6 X5 RO 2 RO2 7 Module Input State Assignment Device Para Relay Outputs RO 6 X5 R...

Page 124: ...ate Assignment Device Para Relay Outputs RO 6 X5 RO 3 RO3 7 Module Input State Assignment Device Para Relay Outputs RO 6 X5 RO 3 Ack signal RO 3 Module Input State Acknowledgment signal for the Relay...

Page 125: ...ate Assignment Device Para Relay Outputs RO 6 X5 RO 4 Ack signal RO 4 Module Input State Acknowledgment signal for the Relay Output If latching is set to active the Relay Output can only be acknowledg...

Page 126: ...e Input State Acknowledgment signal for the Relay Output If latching is set to active the Relay Output can only be acknowledged if those signals that initiated the setting are fallen back and the hold...

Page 127: ...Device Para Relay Outputs RO 6 X5 RO 6 Signals of RO 6 X Signal Description RO 1 Signal Relay Output RO 2 Signal Relay Output RO 3 Signal Relay Output RO 4 Signal Relay Output RO 5 Signal Relay Outpu...

Page 128: ...chapter is valid The only difference between Group A and Group B is within the menu paths Via the INFO push button it is always possible to display the current pickups and alarm texts that are assign...

Page 129: ...signal from the LED Reset list e g digital inputs or communication signals If Latched active The Ex Acknowledge module all LEDs can be acknowledged at once if the signal for external acknowledgment be...

Page 130: ...signment 1 Inverting 1 Assignment 2 Inverting 2 Assignment 3 Inverting 3 Assignment 4 Inverting 4 Assignment 5 Inverting 5 LE D Active Color LED Inactive Color OR OR AND Acknowledge HMI Acknowledge 1...

Page 131: ...LED for System OK Operational lights up in green signaling that the protection function is activated Please refer to chapter Self Supervision and to the external document Troulbe Shooting Guide to fi...

Page 132: ...a LEDs LEDs group A LED 1 LED Active Color The LED lights up in this color if the state of the OR assignment of the signals is true Green Red Red flash Green flash LEDs group A Red LEDs group B Green...

Page 133: ...gned signal Inactive Active Inactive Device Para LEDs LEDs group A LED 1 Assignment 5 Assignment 1 n Assignment List Device Para LEDs LEDs group A LED 1 Inverting 5 Inverting of the state of the assig...

Page 134: ...nt List LEDs group A 51X 1 Trip LEDs group B Bkr Pos CLOSE Device Para LEDs LEDs group A LED 2 Inverting 1 Inverting of the state of the assigned signal Inactive Active Inactive Device Para LEDs LEDs...

Page 135: ...when it picks up Inactive Active Active Device Para LEDs LEDs group A LED 3 Ack signal Acknowledgment signal for the LED If latching is set to active the LED can only be acknowledged if all signals t...

Page 136: ...oup A LED 3 Inverting 2 Inverting of the state of the assigned signal Inactive Active Inactive Device Para LEDs LEDs group A LED 3 Assignment 3 Assignment 1 n Assignment List Device Para LEDs LEDs gro...

Page 137: ...Ds LEDs group A LED 4 LED Active Color The LED lights up in this color if the state of the OR assignment of the signals is true Green Red Red flash Green flash Red Device Para LEDs LEDs group A LED 4...

Page 138: ...state of the assigned signal Inactive Active Inactive Device Para LEDs LEDs group A LED 4 Assignment 5 Assignment 1 n Assignment List Device Para LEDs LEDs group A LED 4 Inverting 5 Inverting of the...

Page 139: ...5 Assignment 1 Assignment 1 n Assignment List LEDs group A Prot Pickup LEDs group B ZI Trip Device Para LEDs LEDs group A LED 5 Inverting 1 Inverting of the state of the assigned signal Inactive Acti...

Page 140: ...when it picks up Inactive Active Active Device Para LEDs LEDs group A LED 6 Ack signal Acknowledgment signal for the LED If latching is set to active the LED can only be acknowledged if all signals t...

Page 141: ...ng 2 Inverting of the state of the assigned signal Inactive Active Inactive Device Para LEDs LEDs group A LED 6 Assignment 3 Assignment 1 n Assignment List Device Para LEDs LEDs group A LED 6 Invertin...

Page 142: ...t Device Para LEDs LEDs group A LED 7 LED Active Color The LED lights up in this color if the state of the OR assignment of the signals is true Green Red Red flash Green flash LEDs group A Green flash...

Page 143: ...tate of the assigned signal Inactive Active Inactive Device Para LEDs LEDs group A LED 7 Assignment 4 Assignment 1 n Assignment List Device Para LEDs LEDs group A LED 7 Inverting 4 Inverting of the st...

Page 144: ...e Para LEDs LEDs group A LED 1 LED1 4 Module Input State LED Device Para LEDs LEDs group A LED 1 LED1 5 Module Input State LED Device Para LEDs LEDs group A LED 1 Acknow Sig 1 Module Input State Ackno...

Page 145: ...2 Module Input State Acknowledgment Signal only for automatic acknowledgment Device Para LEDs LEDs group A LED 2 LED3 1 Module Input State LED Device Para LEDs LEDs group A LED 3 LED3 2 Module Input...

Page 146: ...LEDs group A LED 4 LED4 3 Module Input State LED Device Para LEDs LEDs group A LED 4 LED4 4 Module Input State LED Device Para LEDs LEDs group A LED 4 LED4 5 Module Input State LED Device Para LEDs LE...

Page 147: ...5 Module Input State Acknowledgment Signal only for automatic acknowledgment Device Para LEDs LEDs group A LED 5 LED6 1 Module Input State LED Device Para LEDs LEDs group A LED 6 LED6 2 Module Input...

Page 148: ...LEDs group A LED 7 LED7 2 Module Input State LED Device Para LEDs LEDs group A LED 7 LED7 3 Module Input State LED Device Para LEDs LEDs group A LED 7 LED7 4 Module Input State LED Device Para LEDs LE...

Page 149: ...plies to protective devices with a small display www eaton com 149 1 2 3 5 7 6 8 10 USB Interface PowerPort E Connection ACK RST key INFO Key Signals Messages Control Softkeys Display LED System OK Pr...

Page 150: ...to protective devices with a large display www eaton com 150 1 2 3 5 6 8 7 10 Control Softkeys Display LED System OK Programmable LEDs 9 OK key 4 Programmable LEDs Protective Device INFO Key Signals M...

Page 151: ...ates of each function activated Based on the application need up to 14 but not necessarily all programmable LEDs can be activated By properly configuring some or all 14 LEDs the User will be able to v...

Page 152: ...application need up to 14 but not necessarily all programmable LEDs can be activated By properly configuring some or all 14 LEDs the User will be able to view the relay s overall operation and some cr...

Page 153: ...e seconds the SOFTKEYs will be shown flashing If there is more than one signal assigned to an LED indicated by three dots the User can check the state of the multiple assignments by proceeding as foll...

Page 154: ...The User can exit the reset menu by pressing the Softkey Arrow left 8 USB Interface PowerPort E Connection Connection to the computer software PowerPort E is done via the USB interface 9 OK Key When u...

Page 155: ...Via SOFTKEY Top of List the User will be taken directly to the top of a list Via SOFTKEY Bottom of List the User will be taken directly to the end of a list Via SOFTKEY the related digit will be incre...

Page 156: ...nual MN026001EN Menu controlled parameter setting incl validity checks Offline configuration of all relay types Reading and evaluating of statistical data and measuring values Setting into operation a...

Page 157: ...tomize waveform channel layout and views including channel overlapping and zooming Analyze sample by sample data points and line up the displayed analog waveform channels along with the recorded inter...

Page 158: ...of measured values within the HMI and Power Port E Scaling of Measured values By means of the parameter Scaling the user can determine how measured values are to be displayed within the HMI and Power...

Page 159: ...unter will start counting again at zero A corresponding signal will indicate the counter overflow Counter overflow at Energy Auto Scaling Depends on the settings for the current and voltage transforme...

Page 160: ...ent Fund IX meas Fund Measured value measured IX Fundamental Operation Measured Values Current Fund IR calc Fund Measured value calculated IR Fundamental Operation Measured Values Current Fund I0 Fund...

Page 161: ...of Positive Sequence System Operation Measured Values Current Fund Angle I2 Measured value calculated Angle of Negative Sequence System Operation Measured Values Current Fund IA RMS Measured value Ph...

Page 162: ...RMS IA THD Measured Value Calculated IA Total Harmonic Current Operation Measured Values Current RMS IB THD Measured Value Calculated IB Total Harmonic Current Operation Measured Values Current RMS IC...

Page 163: ...ase to phase voltage Fundamental Operation Measured Values Voltage Fund VA Fund Measured value Phase to neutral voltage Fundamental Operation Measured Values Voltage Fund VB Fund Measured value Phase...

Page 164: ...d value Phase to phase voltage RMS Operation Measured Values Voltage RMS VA RMS Measured value Phase to neutral voltage RMS Operation Measured Values Voltage RMS VB RMS Measured value Phase to neutral...

Page 165: ...le of Phasor VR calc Operation Measured Values Voltage Fund Angle V0 Measured Value calculated Angle of Zero Sequence System Operation Measured Values Voltage Fund Angle V1 Measured Value calculated A...

Page 166: ...Operation Measured Values Voltage RMS VAB THD Measured value calculated VAB Total Harmonic Distortion Operation Measured Values Voltage RMS VBC THD Measured value calculated VBC Total Harmonic Distort...

Page 167: ...e Calculated 55D Displacement Power Factor Sign Convention sign PF sign Syst W Operation Measured Values Power Wh Fwd Positive Active Power is consumed active energy Operation Measured Values Energy W...

Page 168: ...Active Power RMS Operation Measured Values Power Apt PF Measured Value Calculated 55A Apparent Power Factor Sign Convention sign PF sign Syst W Operation Measured Values Power Syst W 1 Measured Watts...

Page 169: ...MVA GW GVAr GVA Power Auto Scaling Operation General Settings Energy Units Energy Units Energy Auto Sca ling kWh kVArh kVAh MWh MVArh MVAh GWh GVArh GVAh MWh MVArh MVA h Operation General Settings Di...

Page 170: ...unter Wh Fwd Res Cr Signal Wh Fwd Reset Counter Wh Rev Res Cr Signal Wh Rev Reset Counter VArh Net Res Cr Signal VArh Net Reset Counter VArh Lag Res Cr Signal VArh Lag Reset Counter VArh Lead Res Cr S...

Page 171: ...ation Minimum and Maximum Values Peak Values Pointers Time interval for the calculation of the minimum and maximum values Reset Configuration Options Where to configure Within menu Device Para Statist...

Page 172: ...e calculation based on sliding period fixed fixed Average calculation is reset by the end of the period that means with the next starting period duration fixed or sliding period Start Fct The average...

Page 173: ...ion Statistics Vavg Configuration of the Power Based Average Value Calculation Availability depends on the ordered device code Power based Average Values Demand and Peak Values Time period for the cal...

Page 174: ...Operation Reset ResFc Min Resetting of all Minimum values Inactive Active Inactive Operation Reset ResFc Max Resetting of all Maximum values Inactive Active Inactive Operation Reset Global Protection...

Page 175: ...1 n Assignment List Device Para Statistics Demand Current Demand Duration I Demand Recording time Only available if Start I Demand via Duration 2 s 5 s 10 s 15 s 30 s 1 min 5 min 10 min 15 min 30 min...

Page 176: ...P Demand Resetting of Statistics Power Demand avg peak avg 1 n Assignment List Device Para Statistics Demand Power Demand Duration P Demand Recording time Only available if Start P Demand via Duratio...

Page 177: ...emand Device Para Statistics Demand Power Demand ResFc I Demand I State of the module input Resetting of Statistics Current Demand avg peak avg Device Para Statistics Demand Current Demand ResFc P Dem...

Page 178: ...e Statistics Value Description Menu path Res Cr I Demand Number of resets since last booting The timestamp shows date and time of the last reset Operation Statistics Demand Current Demand Res Cr P Dem...

Page 179: ...s Min CT I2 max Fund Maximum value unbalanced load current Fundamental Operation Statistics Max CT I2 min Fund Minimum value unbalanced load current Fundamental Operation Statistics Min CT IA max RMS...

Page 180: ...ue RMS Operation Statistics Demand Current Demand IC min RMS IC minimum value RMS Operation Statistics Min CT IX meas max RMS Measured value IX maximum value RMS Operation Statistics Max CT IX meas mi...

Page 181: ...in Measured value calculated I2 I1 minimum value phase sequence will be taken into account automatically Operation Statistics Min CT IA Peak demand IA Peak value RMS value Operation Statistics Demand...

Page 182: ...Fund Minimum value Symmetrical components positive phase sequence voltage Fundamental Operation Statistics Min Voltage V2 max Fund Maximum value Symmetrical components negative phase sequence voltage...

Page 183: ...tistics Max Voltage VCA min RMS VCA minimum value RMS Operation Statistics Min Voltage VA max RMS VA maximum value RMS Operation Statistics Max Voltage VA min RMS VA minimum value RMS Operation Statis...

Page 184: ...max RMS Measured value calculated VR maximum value RMS Operation Statistics Max Voltage VR calc min RMS Measured value calculated VR minimum value RMS Operation Statistics Min Voltage V2 V1 max Measur...

Page 185: ...Statistics Min Power Syst VA max Maximum value of the apparent power Operation Statistics Max Power Syst VA avg Average of the apparent power Operation Statistics Demand Power Demand Syst VA min Minim...

Page 186: ...Maximum value of the 55A Apparent Power Factor Sign Convention sign PF sign Syst W Operation Statistics Max Power Apt PF min Minimum value of the 55A Apparent Power Factor Sign Convention sign PF sign...

Page 187: ...by contract with the energy supplier If the contractual target values are exceeded extra charges are to be paid to the energy supplier Therefore demand management helps the User detect and avoid aver...

Page 188: ...ow can be set to fixed or sliding Example for a fixed window If the range is set for 15 minutes the protective device calculates the average current or power over the past 15 minutes and updates the v...

Page 189: ...4 Window configuration Sliding Window configuration Fixed Sliding Sliding t Delay 0 Duration Average Calculation Pickup t Delay 0 Average Calculation Pickup t Delay 0 Average Calculation Pickup t Dela...

Page 190: ...mum min and maximum max values can be seen Minimum values since last reset The minimum values are continuously compared to the last minimum value for that measuring value If the new value is less than...

Page 191: ...gnal Alarm VARs demand value Alarm VA Demand Signal Alarm VAs demand value Alm Current Demd Signal Alarm Current demand value Alarm I THD Signal Alarm Total Harmonic Distortion Current Alarm V THD Sig...

Page 192: ...n parameter If the signal becomes true those modules elements are blocked that are parameterized ExBlo Fc active 1 n Assignment List SysA General Settings Alarm Alarm Inactive Active Inactive SysA Pow...

Page 193: ...o be entered as primary value 1 40000000kW 10000kW SysA Demand Power Demand Watt Demand t Delay Tripping Delay 0 60min 0min SysA Demand Power Demand Watt Demand Alarm Alarm Inactive Active Inactive Sy...

Page 194: ...urrent Demand Threshold Threshold to be entered as primary value 10 500000A 500A SysA Demand Current Demand t Delay Tripping Delay 0 60min 0min SysA Demand Current Demand Alarm Alarm Inactive Active I...

Page 195: ...Setting range Default Menu path t Delay Tripping Delay 0 3600s 0s SysA THD V THD States of the Inputs of the Demand Management Name Description Assignment via ExBlo I Module Input State External Block...

Page 196: ...mmands at once Where Operation Acknowledge All at once Where Operation Acknowledge External Acknowledg ment Via a signal from the assignment list e g a digital Input all can be acknowledged All LEDs a...

Page 197: ...nu of this single LED Relay Output Where Within the Configuration menu of this single Relay Output Pending Trip Command Where Within the module BkrManager If the User is within the parameter setting m...

Page 198: ...ss the Ack Rst button on the panel Select the item to be acknowledged via the softkeys Relay Outputs LEDs SCADA A trip command or All the above mentioned items at once Press the Softkey with the Wrenc...

Page 199: ...signment list that Acknowledges all acknowledgeable LEDs at once Acknowledges all acknowledgeable Output Relays at once or Acknowledges all acknowledgeable Communication Scada signals at once www eato...

Page 200: ...Factory Defaults This Function will reset the device to the factory defaults All records will be deleted and and the measured values and counters will be reset The operation hours counter will be kept...

Page 201: ...state of all signals can be viewed This means the User is able to see if the individual signals are active or inactive at that moment The User can see all signals sorted by protective elements module...

Page 202: ...range Default Menu path Contrast Contrast 0 100 50 Device Para HMI Global Protection Parameters of the Panel Parameter Description Setting range Default Menu path t max Edit Access If no other key s i...

Page 203: ...r and post trigger time To trigger the waveform recorder up to eight signals can be selected from the Assignment list The trigger events are OR linked If a waveform record is written a new waveform re...

Page 204: ...EDR 5000 IM02602007E www eaton com 204 Start 1 Trigger Start 2 Trigger Start 3 Trigger Start 4 Trigger Start 5 Trigger Start 6 Trigger Start 7 Trigger Start 8 Trigger Man Trigger Recording OR OR...

Page 205: ...trigger time t 0 1 500 ms Post trigger time t 0 1 2000 ms t rec t 0 1 2000 ms Max file size Start 1 Prot Pickup Start 2 Start 3 Start 4 Start 5 Start 6 Start 7 Start 8 Post trigger time 25 Pre trigger...

Page 206: ...trigger time t 0 1 500 ms Post trigger time t 0 1 1000 ms t rec t rec Max file size t 0 1 2000 ms Max file size Start 1 Prot Trip Start 2 Start 3 Start 4 Start 5 Start 6 Start 7 Start 8 Post trigger...

Page 207: ...form Records Within the Operation Waveform rec menu the User can Delete waveform records Choose the waveform record that is to be deleted via SOFTKEY up and SOFTKEY down Call up the detailed view of t...

Page 208: ...n Assignment List Prot Pickup Device Para Recorders Waveform rec Start 2 Start recording if the assigned signal is true 1 n Assignment List Prot Trip Device Para Recorders Waveform rec Start 3 Start r...

Page 209: ...m rec Post trigger time The post trigger time is settable up to a maximum of 50 of the Maximum file size setting The post trigger will be the remaining time of the Max file size but at maximum Post tr...

Page 210: ...orm rec Start5 I State of the module input Trigger event start recording if Device Para Recorders Waveform rec Start6 I State of the module input Trigger event start recording if Device Para Recorders...

Page 211: ...enu path Rec state Recording state Ready Ready Recording Writing file Trigger Blo Operation Status Display Recorders Waveform rec Error code Error code OK OK Write err Clear fail Calculation err File...

Page 212: ...alysis already at the HMI After a fault a popup window will be sent onto the display in order to draw the users attention to the fault The Fault Recorder will provide information on the causes of the...

Page 213: ...falling edge of the General Pickup Signal Please note that General Pickup is an or connection disjunction of all Pickup signals General Trip is an OR connection of all Trips www eaton com 213 Prot Pic...

Page 214: ...en does the overlay popup appears on the display of the HMI A popup will appear on the HMI display when the General Pickup Prot Pickup disappears No time to trip will be shown if the pickup signal tha...

Page 215: ...using Softkey OK How to find out fast if a fault has lead to a trip or not Faults that lead to a trip will be indicated by a flash icon right side within the overview menu of the fault recorder Which...

Page 216: ...n that will be displayed depends on which protection module has tripped That means e g that the thresholds are shown In case that the trip was initiated by the MotorStart applies to motor protection r...

Page 217: ...ext lower item within this fault record How to read Out the Fault Recorder In order to read out a fault record there are two options available Option 1 A Fault has popped up on the HMI because an trip...

Page 218: ...e Operation Reset Global Protection Parameters of the Fault Recorder Module Parameter Description Setting range Default Menu path Record Mode Recorder Mode Set the behaviour of the recorder Pickups an...

Page 219: ...t Pickup A grid fault No can have several Fault Nos This counter will be incremented by each General Pickup Exception AR this applies only to devices that offer auto reclosing Time stamp What has chan...

Page 220: ...nd Recorder is to be configured within Device Para Recorders Trend Recorder menu The User has to set the time interval This defines the distance between two measuring points The User can select up to...

Page 221: ...Observed Value5 Observed Value5 1 n TrendRecList VT VA RMS Device Para Recorders Trend rec Observed Value6 Observed Value6 1 n TrendRecList VT VB RMS Device Para Recorders Trend rec Observed Value7 O...

Page 222: ...Parameter Description Setting range Default Menu path Reset Delete all entries Inactive Active Inactive Operation Reset Counter Values of the Trend Recorder Value Description Default Size Menu path M...

Page 223: ...ltage RMS VT V0 Fund Measured value calculated Symmetrical components Zero voltage Fundamental VT V1 Fund Measured value calculated Symmetrical components positive phase sequence voltage Fundamental V...

Page 224: ...ctive power P Fed Active Power P Consumpted Active Power Fundamental ECr Syst VAr Fund Measured VARs Reactive power Q Fed Reactive Power Q Consumpted Reactive Power Fundamental ECr Syst W 1 Measured W...

Page 225: ...nchronized via the following protocols IRIG B SNTP Communications Protocol Modbus RTU or TCP and or These protocols use different hardware interfaces and are different in accuracy Further information...

Page 226: ...actors Accuracy of the connected time generator Synchronization protocol that is used and At Modbus TCP and SNTP Network load and data package transmission times Please consider the accuracy of the ti...

Page 227: ...ezone menu 2 There also configure the switching of daylight savings time 3 Select the used time synchronization protocol in the TimeSync menu e g IRIG B 4 Set the parameters of the synchronization pro...

Page 228: ...ertime Daylight Saving Time Only available if DST manual Active Inactive Active Inactive Device Para Time Timezone Summertime m Month of clock change summertime Only available if DST manual Inactive J...

Page 229: ...T manual Inactive 0 59min 0min Device Para Time Timezone Wintertime m Month of clock change wintertime Only available if DST manual Inactive January February March April May June July August September...

Page 230: ...u path Wintertime h Hour of clock change wintertime Only available if DST manual Inactive 0 23h 3h Device Para Time Timezone Wintertime min Minute of clock change wintertime Only available if DST manu...

Page 231: ...C 9 5 Adelaide UTC 9 Tokyo UTC 8 Hong Kong UTC 7 Bangkok UTC 6 5 Rangoon UTC 6 Colombo UTC 5 75 Kath mandu UTC 5 5 New Delhi UTC 5 Islamabad UTC 4 5 Kabul UTC 4 Abu Dhabi UTC 3 5 Tehran UTC 3 Moscow U...

Page 232: ...EDR 5000 IM02602007E Parameter Description Setting range Default Menu path TimeSync Time synchronization IRIG B SNTP Modbus DNP Device Para Time TimeSync TimeSync www eaton com 232...

Page 233: ...or two connected SNTP servers The device s system time will be synchronized by the connected SNTP server 1 to 4 times per minute In turn the SNTP server synchronizes its time via NTP with other NTP s...

Page 234: ...used because this could cause fluctuations of the time synchronization The network quality gives information about the network s load and data package transmission time The quality should be GOOD or...

Page 235: ...ration Status Display Time Sync Sntp menu If the SNTP status is not active please proceed as follows Check if the wiring is correct Ethernet cable connected Check if a valid IP address is set in the d...

Page 236: ...Counter Reset all Counters Inactive Active Inactive Operation Reset Global Protection Parameters of the SNTP Parameter Description Setting range Default Menu path Server1 Server 1 Inactive Active Inac...

Page 237: ...er2 Server 2 Inactive Active Inactive Device Para Time TimeSync SNTP IP Byte1 IP1 IP2 IP3 IP4 0 255 0 Device Para Time TimeSync SNTP IP Byte2 IP1 IP2 IP3 IP4 0 255 0 Device Para Time TimeSync SNTP IP...

Page 238: ...SmallSyncs Service counter Total Number of very small Time Corrections 0 0 9999999999 Operation Count and RevData TimeSync SNTP NoOfNormSyncs Service counter Total Number of normal Time Corrections 0...

Page 239: ...umServer2 Stratum of Server 2 0 0 9999999999 Operation Status Display TimeSync SNTP SNTP Values Value Description Default Size Menu path Used Server Which Server is used for SNTP synchronization None...

Page 240: ...EDR 5000 IM02602007E Value Description Default Size Menu path NetConn Quality of Network Connection GOOD SUFFICIENT BAD GOOD SUFFICIENT BAD Operation Status Display TimeSync SNTP www eaton com 240...

Page 241: ...ion device supports IRIG B according to the IRIG STANDARD 200 04 This means that all time synchronization formats IRIG B00X IRIG B000 B001 B002 B003 B004 B005 B006 B007 are supported It is recommended...

Page 242: ...as being active please proceed as follows To begin with check the IRIG B wiring Check if the correct IRIG B00X type is configured IRIG B Control Commands In addition to the date and time information...

Page 243: ...e Operation Reset Global Protection Parameters of the IRIG B00X Parameter Description Setting range Default Menu path Function Permanent activation or deactivation of module element Inactive Active In...

Page 244: ...y can be used for further control procedures inside the device e g logic funtions Control Signal9 Signal IRIG B Control Signal The external IRIG B generator can set these signals They can be used for...

Page 245: ...nd RevData TimeSync IRIG B NoOfFrameErrors Total Number of Frame Errors Physically corrupted Frame 0 0 65535 Operation Count and RevData TimeSync IRIG B Edges Edges Total number of rising and falling...

Page 246: ...date and time The User cannot set time and date manually manual changes will be ignored if the clock of the protective device is synchronized automatically e g via IRIG B or SNTP Version Within the D...

Page 247: ...ished That means the User MUST first read out the IP address at the HMI of the device within menu Device para TCP IP then compare the IP address with the list If the addresses are identical establish...

Page 248: ...on Reset Ack Comm Communication will be acknowledged Inactive Active Inactive Operation Reset Reboot Rebooting the device No Yes No Service General MaintMode Manually Arc Flash Reduction Maintenance S...

Page 249: ...be executed In case all input functions are inactive the device will keep working with the Setting Group that was activated lastly Only available if PSet Switch PSS via Inp fct 1 n PSS Sys Maint Mode...

Page 250: ...ed if the state of the assigned signal becomes true Only available if Remote Reset Active 1 n Assignment List Device Para Ex Acknowledge Scaling Display of the measured values as primary secondary or...

Page 251: ...t Switch Maint Mode I Module Input State Arc Flash Reduction Maintenance Switch Service Maint Mode System Module Signals Signal Description Reboot Signal Rebooting the device 1 Restart initiated by po...

Page 252: ...al LEDs Acknowledgment Ack RO Signal Acknowledgment of the Relay Outputs Ack Counter Signal Reset of all Counters Ack Comm Signal Acknowledge Communication Ack TripCmd Signal Reset Trip Command Ack LE...

Page 253: ...of the System Module Value Description Menu path Build Build Device Para Version Version Version Device Para Version Operating hours Cr Operating hours counter of the protective device Operation Coun...

Page 254: ...hanging the protocol will cause a restart of the device Do not use Modbus RTU Modbus TCP DNP RTU DNP TCP DNP UDP IEC61850 Profibus Do not use Device Planning Signals Output States of the SCADA Interfa...

Page 255: ...IP Advanced Settings Keep Alive Interval Keep Alive Interval is the duration between two successive keep alive retransmissions if the acknowledgement to the previous keepalive transmission was not re...

Page 256: ...ce such as Type of unit version Measuring values statistical measured values Switch operating position in preparation State of device Time and date State of the device s digital inputs and Protection...

Page 257: ...e defining the period within which an inquiry from the master has to be answered Part 2 Hardware Connection For hardware connection to the control system there is an RS485 interface at the rear side o...

Page 258: ...Setting a unit identifier is only necessary if a TCP network should be coupled to a RTU network If a different port than the default port 502 should be used please proceed as follows Choose Private wi...

Page 259: ...twork should be coupled 1 255 255 Device Para Modbus Communication TCP Port Config TCP Port Configuration This parameter is to be set only if the default Modubs TCP Port should not be used Default Pri...

Page 260: ...0s Device Para Modbus Communication Comm CmdBlo Activating allowing Deactivating disallowing the blocking of the Communication Commands Inactive Active Inactive Device Para Modbus Communication Disabl...

Page 261: ...ce 1 n Assignment List Prot Trip Device Para Modbus Configb Registers States Latched Config Bin Inp3 Latched Configurable Binary Input Inactive Active Active Device Para Modbus Configb Registers State...

Page 262: ...bus Configb Registers States Config Bin Inp8 Virtual Digital Input This corresponds to a virtual binary output of the protective device 1 n Assignment List Device Para Modbus Configb Registers States...

Page 263: ...Assignment List BF Trip Device Para Modbus Configb Registers States Latched Config Bin Inp12 Latched Configurable Binary Input Inactive Active Inactive Device Para Modbus Configb Registers States Conf...

Page 264: ...Configb Registers States Config Bin Inp17 Virtual Digital Input This corresponds to a virtual binary output of the protective device 1 n Assignment List Sgen Running Device Para Modbus Configb Registe...

Page 265: ...1 n Assignment List Device Para Modbus Configb Registers States Latched Config Bin Inp21 Latched Configurable Binary Input Inactive Active Inactive Device Para Modbus Configb Registers States Config...

Page 266: ...evice Para Modbus Configb Registers States Config Bin Inp26 Virtual Digital Input This corresponds to a virtual binary output of the protective device 1 n Assignment List Device Para Modbus Configb Re...

Page 267: ...1 n Assignment List Device Para Modbus Configb Registers States Latched Config Bin Inp30 Latched Configurable Binary Input Inactive Active Inactive Device Para Modbus Configb Registers States Config...

Page 268: ...a Modbus Configb Registers Measured Values Mapped Meas 5 Mapped Measured Values They can be used to provide measured values to the Modbus Master 1 n TrendRecList Device Para Modbus Configb Registers M...

Page 269: ...Modbus Configb Registers Measured Values Mapped Meas 13 Mapped Measured Values They can be used to provide measured values to the Modbus Master 1 n TrendRecList Device Para Modbus Configb Registers M...

Page 270: ...ce Para Modbus Configb Registers States Config Bin Inp4 I State of the module input Config Bin Inp Device Para Modbus Configb Registers States Config Bin Inp5 I State of the module input Config Bin In...

Page 271: ...input Config Bin Inp Device Para Modbus Configb Registers States Config Bin Inp13 I State of the module input Config Bin Inp Device Para Modbus Configb Registers States Config Bin Inp14 I State of the...

Page 272: ...input Config Bin Inp Device Para Modbus Configb Registers States Config Bin Inp22 I State of the module input Config Bin Inp Device Para Modbus Configb Registers States Config Bin Inp23 I State of th...

Page 273: ...isters States Config Bin Inp29 I State of the module input Config Bin Inp Device Para Modbus Configb Registers States Config Bin Inp30 I State of the module input Config Bin Inp Device Para Modbus Con...

Page 274: ...Meas 5 Mapped Measured Values They can be used to provide measured values to the Modbus Master Operation Count and RevData Modbus Mapped Meas 6 Mapped Measured Values They can be used to provide measu...

Page 275: ...ey can be used to provide measured values to the Modbus Master Operation Count and RevData Modbus Mapped Meas 15 Mapped Measured Values They can be used to provide measured values to the Modbus Master...

Page 276: ...ation Command Comm Cmd 3 Communication Command Comm Cmd 4 Communication Command Comm Cmd 5 Communication Command Comm Cmd 6 Communication Command Comm Cmd 7 Communication Command Comm Cmd 8 Communicat...

Page 277: ...RevData Modbus NoOfOverrunErros Total Number of Overrun Failures Physically corrupted Frame 0 0 9999999999 Operation Count and RevData Modbus NoOfParityErrors Total number of parity errors Physically...

Page 278: ...tem there is optional an D SUB interface at the rear side of the device Connect bus and device wiring Up to 123 slaves can be connected Terminate the Bus by means of an Terminate Resistor Error Handli...

Page 279: ...fig Bin Inp 2 Virtual Digital Input This corresponds to a virtual binary output of the protective device 1 n Assignment List Device Para Profibus Config Bin Inp 1 16 Latched 2 Defines whether the Inpu...

Page 280: ...Input is latched Only available if Latched Active Inactive Active Inactive Device Para Profibus Config Bin Inp 1 16 Config Bin Inp 7 Virtual Digital Input This corresponds to a virtual binary output...

Page 281: ...Input is latched Only available if Latched Active Inactive Active Inactive Device Para Profibus Config Bin Inp 1 16 Config Bin Inp 12 Virtual Digital Input This corresponds to a virtual binary output...

Page 282: ...nput is latched Only available if Latched Active Inactive Active Inactive Device Para Profibus Config Bin Inp 1 16 Config Bin Inp 17 Virtual Digital Input This corresponds to a virtual binary output o...

Page 283: ...Input is latched Only available if Latched Active Inactive Active Inactive Device Para Profibus Config Bin Inp 17 32 Config Bin Inp 22 Virtual Digital Input This corresponds to a virtual binary output...

Page 284: ...Input is latched Only available if Latched Active Inactive Active Inactive Device Para Profibus Config Bin Inp 17 32 Config Bin Inp 27 Virtual Digital Input This corresponds to a virtual binary output...

Page 285: ...nput This corresponds to a virtual binary output of the protective device 1 n Assignment List Device Para Profibus Config Bin Inp 17 32 Latched 31 Defines whether the Input is latched Only available i...

Page 286: ...nt 5 I Module input state Comm Assignment Device Para Profibus Config Bin Inp 1 16 Assignment 6 I Module input state Comm Assignment Device Para Profibus Config Bin Inp 1 16 Assignment 7 I Module inpu...

Page 287: ...s Config Bin Inp 1 16 Assignment 17 I Module input state Comm Assignment Device Para Profibus Config Bin Inp 17 32 Assignment 18 I Module input state Comm Assignment Device Para Profibus Config Bin In...

Page 288: ...input state Comm Assignment Device Para Profibus Config Bin Inp 17 32 Assignment 28 I Module input state Comm Assignment Device Para Profibus Config Bin Inp 17 32 Assignment 29 I Module input state C...

Page 289: ...mand Comm Cmd 3 Communication Command Comm Cmd 4 Communication Command Comm Cmd 5 Communication Command Comm Cmd 6 Communication Command Comm Cmd 7 Communication Command Comm Cmd 8 Communication Comma...

Page 290: ...ation Count and RevData Profibus ssCrcErrors Number of CRC errors that the subsystem has recognized in received trigger frames from host 1 1 99999999 Operation Count and RevData Profibus ssResets Numb...

Page 291: ...hange Operation Status Display Profibus State Baud rate The baud rate that has been detected lastly will still be shown after a connection issue 12 Mb s 6 Mb s 3 Mb s 1 5 Mb s 0 5 Mb s 187500 baud 937...

Page 292: ...out events is submitted between each IED Therefore each IED has to know about the functional capability of all other connected IEDs Each IEC 61850 capable device includes a description of its own func...

Page 293: ...s and Wiring according to wiring scheme Commissioning steps for a substation with IEC 61850 environment 1 Parameter setting of the IEDs Ethernet installation TCP IP settings for the IEDs 2 IEC 61850 c...

Page 294: ...1 Connect the device with your PC Notebook 2 Start Power Port E 3 Click on Receive data from Device in the menu Device 4 Click on IEC61850 in the menu Device Para 5 Click on the SCD icon in the IEC61...

Page 295: ...IEC Communication and submit the changed parameter set into the device 10 Repeat Steps 1 through 9 for all devices connected to this IEC 61850 environment 11 If no error message occurs the configurati...

Page 296: ...range Default Menu path VirtualOutput1 Virtual Output This signal can be assigned or visualized via the SCD file to other devices within the IEC61850 substation 1 n Assignment List Device Para IEC6185...

Page 297: ...igned or visualized via the SCD file to other devices within the IEC61850 substation 1 n Assignment List Device Para IEC61850 VirtualOutput10 Virtual Output This signal can be assigned or visualized v...

Page 298: ...assigned or visualized via the SCD file to other devices within the IEC61850 substation 1 n Assignment List Device Para IEC61850 VirtualOutput20 Virtual Output This signal can be assigned or visualize...

Page 299: ...assigned or visualized via the SCD file to other devices within the IEC61850 substation 1 n Assignment List Device Para IEC61850 VirtualOutput29 Virtual Output This signal can be assigned or visualize...

Page 300: ...Out8 I Module input state Binary state of the Virtual Output GGIO Device Para IEC61850 VirtOut9 I Module input state Binary state of the Virtual Output GGIO Device Para IEC61850 VirtOut10 I Module inp...

Page 301: ...nput state Binary state of the Virtual Output GGIO Device Para IEC61850 VirtOut25 I Module input state Binary state of the Virtual Output GGIO Device Para IEC61850 VirtOut26 I Module input state Binar...

Page 302: ...Input IEC61850 GGIO Ind VirtInp14 Signal Virtual Input IEC61850 GGIO Ind VirtInp15 Signal Virtual Input IEC61850 GGIO Ind VirtInp16 Signal Virtual Input IEC61850 GGIO Ind VirtInp17 Signal Virtual Inp...

Page 303: ...t Quality of GGIO In19 Self Supervision of the GGIO Input Quality of GGIO In20 Self Supervision of the GGIO Input Quality of GGIO In21 Self Supervision of the GGIO Input Quality of GGIO In22 Self Supe...

Page 304: ...that can be set by clients like e g the Master Communication System Single Point Controllable Status Output SPCSO15 Status bit that can be set by clients like e g the Master Communication System Singl...

Page 305: ...System Single Point Controllable Status Output SPCSO29 Status bit that can be set by clients like e g the Master Communication System Single Point Controllable Status Output SPCSO30 Status bit that c...

Page 306: ...and RevData IEC61850 NoOfGooseTxAll Total Number of GOOSE messages that have been published by this device 0 0 9999999999 Operation Count and RevData IEC61850 NoOfGooseTxNew Total Number of new GOOSE...

Page 307: ...ta IEC61850 No of Client Connections Number of active MMS client connections 0 0 9999999999 Operation Count and RevData IEC61850 Values of the IEC 61850 Value Description Default Size Menu path GooseP...

Page 308: ...al Port DNP3 TCP via Ethernet DNP3 UDP via Ethernet DNP Protocol General Settings Please note that unsolicited reporting is not available for serial communication if more than one slave is connected t...

Page 309: ...he general settings of the DNP protocol are done the point mapping is to be done as a next step Binary Inputs States to be send to the master Double Bit Inputs Breaker states to be send to the master...

Page 310: ...NP communication That means do not leave unused inputs outputs in between used inputs outputs e g Do not use Binary Output 1 and 3 when 2 is unused www eaton com 310 DNP Master Protective Relay Point...

Page 311: ...re pulse signals by DNP definition not steady state Steady states can be created by means of Logic functions The Logic Functions can be assigned onto the Relay Inputs Please note You can use a Set Res...

Page 312: ...65519 65500 Device Para DNP Communication Global Protection Parameters of the DNP Parameter Description Setting range Default Menu path Function Permanent activation or deactivation of module element...

Page 313: ...ink packet sending after failing 0 255 3 Device Para DNP Communication Direction Bit Enables Direction Bit functionality The Direction Bit is 0 for SlaveStation and 1 for MasterStation Inactive Active...

Page 314: ...n back from the master 0 255 2 Device Para DNP Communication TestSeqNo Test if sequence number of request is incremented If it is not correctly incremented the request will be ignored It is recommende...

Page 315: ...ist Device Para DNP Point map Binary Inputs BinaryInput 4 Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device 1 n Assignment List Device Para DNP Point map B...

Page 316: ...st Device Para DNP Point map Binary Inputs BinaryInput 13 Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device 1 n Assignment List Device Para DNP Point map B...

Page 317: ...ist Device Para DNP Point map Binary Inputs BinaryInput 22 Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device 1 n Assignment List Device Para DNP Point map...

Page 318: ...ist Device Para DNP Point map Binary Inputs BinaryInput 31 Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device 1 n Assignment List Device Para DNP Point map...

Page 319: ...ist Device Para DNP Point map Binary Inputs BinaryInput 40 Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device 1 n Assignment List Device Para DNP Point map...

Page 320: ...ist Device Para DNP Point map Binary Inputs BinaryInput 49 Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device 1 n Assignment List Device Para DNP Point map...

Page 321: ...ist Device Para DNP Point map Binary Inputs BinaryInput 58 Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device 1 n Assignment List Device Para DNP Point map...

Page 322: ...ive device 1 n Assignment List Device Para DNP Point map Double Bit Inputs DoubleBitInput 3 Double Bit Digital Input DNP This corresponds to a double bit binary output of the protective device 1 n Ass...

Page 323: ...er 1 n Assignment List Device Para DNP Point map BinaryCounter BinaryCounter 5 Counter can be used to report counter values to the DNP master 1 n Assignment List Device Para DNP Point map BinaryCounte...

Page 324: ...alog value 1 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 1 The scale factor is used to convert the measured value i...

Page 325: ...alog value 3 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 3 The scale factor is used to convert the measured value i...

Page 326: ...alog value 5 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 5 The scale factor is used to convert the measured value i...

Page 327: ...alog value 7 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 7 The scale factor is used to convert the measured value i...

Page 328: ...log value 9 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 9 The scale factor is used to convert the measured value in...

Page 329: ...log value 11 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 11 The scale factor is used to convert the measured value...

Page 330: ...log value 13 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 13 The scale factor is used to convert the measured value...

Page 331: ...log value 15 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 15 The scale factor is used to convert the measured value...

Page 332: ...log value 17 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 17 The scale factor is used to convert the measured value...

Page 333: ...log value 19 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 19 The scale factor is used to convert the measured value...

Page 334: ...log value 21 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 21 The scale factor is used to convert the measured value...

Page 335: ...log value 23 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 23 The scale factor is used to convert the measured value...

Page 336: ...log value 25 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 25 The scale factor is used to convert the measured value...

Page 337: ...log value 27 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 27 The scale factor is used to convert the measured value...

Page 338: ...log value 29 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale Factor 29 The scale factor is used to convert the measured value...

Page 339: ...he master 0 01 100 00 1 Device Para DNP Point map Analog Input Analog value 31 Analog value can be used to report values to the master DNP 1 n TrendRecList Device Para DNP Point map Analog Input Scale...

Page 340: ...Digital Input DNP This corresponds to a virtual binary output of the protective device Device Para DNP Point map Binary Inputs BinaryInput4 I Virtual Digital Input DNP This corresponds to a virtual bi...

Page 341: ...Device Para DNP Point map Binary Inputs BinaryInput12 I Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device Device Para DNP Point map Binary Inputs BinaryIn...

Page 342: ...e Device Para DNP Point map Binary Inputs BinaryInput21 I Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device Device Para DNP Point map Binary Inputs BinaryI...

Page 343: ...e Device Para DNP Point map Binary Inputs BinaryInput30 I Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device Device Para DNP Point map Binary Inputs BinaryI...

Page 344: ...e Device Para DNP Point map Binary Inputs BinaryInput39 I Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device Device Para DNP Point map Binary Inputs BinaryI...

Page 345: ...e Device Para DNP Point map Binary Inputs BinaryInput48 I Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device Device Para DNP Point map Binary Inputs BinaryI...

Page 346: ...e Device Para DNP Point map Binary Inputs BinaryInput57 I Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device Device Para DNP Point map Binary Inputs BinaryI...

Page 347: ...sponds to a double bit binary output of the protective device Device Para DNP Point map Double Bit Inputs DoubleBitInput2 I Double Bit Digital Input DNP This corresponds to a double bit binary output...

Page 348: ...Cr Tot Numb of Vdips to Trip Counter Total number of voltage dips that caused a Trip AR AR Shot No Counter Auto Reclosure Attempts AR Total number Cr Total number of all executed Automatic Reclosures...

Page 349: ...nary input of the protective device BinaryOutput12 Virtual Digital Output DNP This corresponds to a virtual binary input of the protective device BinaryOutput13 Virtual Digital Output DNP This corresp...

Page 350: ...ta DNP NSent Diagnostic counter Number of sent characters 0 0 9999999999 Operation Count and RevData DNP NBadFramings Diagnostic counter Number of bad framings A large number indicates a disturbed ser...

Page 351: ...ameters By modifying the Device Parameters the User may depending on the type of device Configure digital inputs Assign LEDs Configure Relay Outputs Assign acknowledgment signals Configure statistics...

Page 352: ...erial damage as a result of incorrect planning Contact your Eaton Customer Service representative for more information The protection parameters include the following protection parameter trees Global...

Page 353: ...Resetting of a Counter State of the Module Inputs Module Inputs are part of the Device Parameter tree The State of the Module Input is context dependent By means of the Module Inputs information can b...

Page 354: ...0 s Active Inactive Active Inactive 0 In 1 n 0 s 0 05 n 1 n 0 s Active Inactive Active Inactive 0 In 1 n 0 s 0 05 n 1 n 0 s Active Inactive Active Inactive 0 In 1 n 0 s 0 05 n 1 n 0 s Active Inactive...

Page 355: ...so be used to realize various special protective functions or to expand the existing function modules in a simple way without costly redesign the existing hardware or software platform The Adaptive Pa...

Page 356: ...TF enabled Signal Switch Onto Fault enabled This Signal can be used to modify Overcurrent Protection Settings CLPU enabled Signal Cold Load enabled ExP 1 Alarm Signal Alarm ExP 2 Alarm Signal Alarm Ex...

Page 357: ...nd Modbus Comm Cmd 10 Communication Command Modbus Comm Cmd 11 Communication Command Modbus Comm Cmd 12 Communication Command Modbus Comm Cmd 13 Communication Command Modbus Comm Cmd 14 Communication...

Page 358: ...1850 VirtInp31 Signal Virtual Input IEC61850 GGIO Ind IEC61850 VirtInp32 Signal Virtual Input IEC61850 GGIO Ind IEC61850 SPCSO1 Status bit that can be set by clients like e g the Master Communication...

Page 359: ...Point Controllable Status Output Profibus Comm Cmd 1 Communication Command Profibus Comm Cmd 2 Communication Command Profibus Comm Cmd 3 Communication Command Profibus Comm Cmd 4 Communication Command...

Page 360: ...Timer Out Signal Timer Output Logic LE7 Out Signal Latched Output Q Logic LE7 Out inverted Signal Negated Latched Output Q NOT Logic LE8 Gate Out Signal Output of the logic gate Logic LE8 Timer Out S...

Page 361: ...LE16 Out Signal Latched Output Q Logic LE16 Out inverted Signal Negated Latched Output Q NOT Logic LE17 Gate Out Signal Output of the logic gate Logic LE17 Timer Out Signal Timer Output Logic LE17 Ou...

Page 362: ...nverted Signal Negated Latched Output Q NOT Logic LE26 Gate Out Signal Output of the logic gate Logic LE26 Timer Out Signal Timer Output Logic LE26 Out Signal Latched Output Q Logic LE26 Out inverted...

Page 363: ...ate Out Signal Output of the logic gate Logic LE35 Timer Out Signal Timer Output Logic LE35 Out Signal Latched Output Q Logic LE35 Out inverted Signal Negated Latched Output Q NOT Logic LE36 Gate Out...

Page 364: ...LE44 Timer Out Signal Timer Output Logic LE44 Out Signal Latched Output Q Logic LE44 Out inverted Signal Negated Latched Output Q NOT Logic LE45 Gate Out Signal Output of the logic gate Logic LE45 Tim...

Page 365: ...LE53 Out Signal Latched Output Q Logic LE53 Out inverted Signal Negated Latched Output Q NOT Logic LE54 Gate Out Signal Output of the logic gate Logic LE54 Timer Out Signal Timer Output Logic LE54 Ou...

Page 366: ...nverted Signal Negated Latched Output Q NOT Logic LE63 Gate Out Signal Output of the logic gate Logic LE63 Timer Out Signal Timer Output Logic LE63 Out Signal Latched Output Q Logic LE63 Out inverted...

Page 367: ...ate Out Signal Output of the logic gate Logic LE72 Timer Out Signal Timer Output Logic LE72 Out Signal Latched Output Q Logic LE72 Out inverted Signal Negated Latched Output Q NOT Logic LE73 Gate Out...

Page 368: ...Output Q NOT Logic LE79 Gate Out Signal Output of the logic gate Logic LE79 Timer Out Signal Timer Output Logic LE79 Out Signal Latched Output Q Logic LE79 Out inverted Signal Negated Latched Output...

Page 369: ...he corresponding Adaptive Set 5 Set the modified parameter for the selected Adaptive Set Application Example The tripping time t for the 50 1 element of Parameter Set 1 should be desensitized reduced...

Page 370: ...on can easily be realized using the Adaptive Parameter features mentioned previously The standard time overcurrent protection element e g 51P should trip instantaneously in case of SOTF condition If t...

Page 371: ...that desensitizes the overcurrent protection By means of Adaptive Parameter Sets an Adaptive Auto Reclosure can be realized After a reclosure attempt the tripping thresholds or tripping curves of the...

Page 372: ...2 This password provides access to the reset and acknowledge options In addition to that it permits changing of protection settings and the configuration of the trip manager Control Lv1 This password...

Page 373: ...e passwords have to be kept as a secret and to be known only by the authorized persons A lock symbol indicates in the upper right corner of the display if there are any access authorizations active at...

Page 374: ...difications are not overtaken by the device indicated by a star symbol in the upper left corner The passwords are part of the device fixed assignments That means passwords will not be overwritten if a...

Page 375: ...urrently unlocked As soon as there is an unlocked access area authorization above Read Only Lv0 this will be indicated by an unlocked lock symbol within the upper right corner of the device display ww...

Page 376: ...Passwords during Commissioning It is possible optionally to deactivate passwords during commissioning It is not allowed to use this feature for other purposes than commissioning In order to deactivat...

Page 377: ...xample For password 3244 press successively Softkey 3 Softkey 2 Softkey 4 Softkey 4 Password Forgotten By pressing the Ack Rst key during cold booting a reset menu will be called up By selecting Reset...

Page 378: ...e obtained In order to do the parameter changes please proceed as follows Move to the parameter you want to change by using the Softkeys If the parameter is selected the lower right corner of the disp...

Page 379: ...l at any time where parameter changes have been made and have not been saved finally In addition to the star trace to the temporary saved parameter changes a general parameter changing symbol is faded...

Page 380: ...by the question mark plausibility trace This makes it possible to control or follow from the main menu level at any time where implausibilities are intended to be saved In addition to the question ma...

Page 381: ...hanges by pressing the Yes Softkey or dismiss by pressing No To change additional parameters and save afterwards move to other parameters and change them A star symbol in front of the changed paramete...

Page 382: ...by the question mark plausibility trace This makes it possible to control or follow from the main menu level at any time where implausibilities are intended to be saved In addition to the question mar...

Page 383: ...That means if there is more or less than one request signal active no switch over will be executed Example DI3 is assigned onto Parameter set 1 DI3 is active 1 DI4 is assigned onto Parameter set 2 DI...

Page 384: ...I 6 Signal Digital Input DI 8 X6 DI 7 Signal Digital Input DI 8 X6 DI 8 Signal Digital Input Logic LE1 Gate Out Signal Output of the logic gate Logic LE1 Timer Out Signal Timer Output Logic LE1 Out Si...

Page 385: ...Signal Output of the logic gate Logic LE9 Timer Out Signal Timer Output Logic LE9 Out Signal Latched Output Q Logic LE9 Out inverted Signal Negated Latched Output Q NOT Logic LE10 Gate Out Signal Out...

Page 386: ...LE18 Timer Out Signal Timer Output Logic LE18 Out Signal Latched Output Q Logic LE18 Out inverted Signal Negated Latched Output Q NOT Logic LE19 Gate Out Signal Output of the logic gate Logic LE19 Tim...

Page 387: ...LE27 Out Signal Latched Output Q Logic LE27 Out inverted Signal Negated Latched Output Q NOT Logic LE28 Gate Out Signal Output of the logic gate Logic LE28 Timer Out Signal Timer Output Logic LE28 Ou...

Page 388: ...nverted Signal Negated Latched Output Q NOT Logic LE37 Gate Out Signal Output of the logic gate Logic LE37 Timer Out Signal Timer Output Logic LE37 Out Signal Latched Output Q Logic LE37 Out inverted...

Page 389: ...ate Out Signal Output of the logic gate Logic LE46 Timer Out Signal Timer Output Logic LE46 Out Signal Latched Output Q Logic LE46 Out inverted Signal Negated Latched Output Q NOT Logic LE47 Gate Out...

Page 390: ...LE55 Timer Out Signal Timer Output Logic LE55 Out Signal Latched Output Q Logic LE55 Out inverted Signal Negated Latched Output Q NOT Logic LE56 Gate Out Signal Output of the logic gate Logic LE56 Tim...

Page 391: ...LE64 Out Signal Latched Output Q Logic LE64 Out inverted Signal Negated Latched Output Q NOT Logic LE65 Gate Out Signal Output of the logic gate Logic LE65 Timer Out Signal Timer Output Logic LE65 Ou...

Page 392: ...nverted Signal Negated Latched Output Q NOT Logic LE74 Gate Out Signal Output of the logic gate Logic LE74 Timer Out Signal Timer Output Logic LE74 Out Signal Latched Output Q Logic LE74 Out inverted...

Page 393: ...ted Signal Negated Latched Output Q NOT Logic LE80 Gate Out Signal Output of the logic gate Logic LE80 Timer Out Signal Timer Output Logic LE80 Out Signal Latched Output Q Logic LE80 Out inverted Sign...

Page 394: ...he Program Mode is used for Motor Protection devices the user has the following options Motor Stop Lock parameter changes if the motor is not in the STOP state This ensures that parameter changes can...

Page 395: ...and the mains operational method like frequency primary and secondary values and the star point treatment General System Parameters Parameter Description Setting range Default Menu path Phase Sequenc...

Page 396: ...s parameter defines the primary nominal current of the connected ground current transformer If the ground current is measured via the Residual connection the primary value of the phase current transfo...

Page 397: ...ourth measuring input of the voltage measuring card measures the voltage that is to be synchronized A B C AB BC CA A System Para General Settings delta phi Mode The delta phi element vector surge trip...

Page 398: ...d is connected to a wye grounded broken delta 3V0 connection Measured Calculated Calculated System Para Direction Ground MTA Ground Maximum Torque Angle Angle between chosen operating quantity and cho...

Page 399: ...Off Set the Function parameter to Active or Inactive in the Prot module Protection is activated only if in the Prot module the parameter Function is Active i e with Function Inactive no protection fun...

Page 400: ...general protection parameters a signal has to be additionally chosen from the Assignment list The blocking only becomes active when the assigned signal is active To Block the Tripping Command of a Pro...

Page 401: ...of a Protection Module www eaton com 401 Inactive Active Name Blo TripCmd Inactive Active Name ExBlo TripCmd Fc 1 n Assignment List Name ExBlo TripCmd Name ExBlo TripCmd Trip Blockings Name All Module...

Page 402: ...ked Name ExBlo1 I 1 n Assignment List Name ExBlo 2 Name ExBlo2 I Name A ll Modules That A re Blockable 1 2 Please Refer to Diagram Prot OR AND All protective elements will be blocked that are using fu...

Page 403: ...t Name ExBlo 1 1 n Assignment List Name Rvs Blo Name ExBlo Name Rvs Blo Blockings Th e G en eral Protection module is no t deact ivate d or blocke d Name I 1 n IG 1 n Name ExBlo1 I Name Rvs Blo I 1 n...

Page 404: ...In such a case the protective function is Inactive Protection Active If the master Protection module was activated and a blockade for this module was not activated respectively the assigned blocking s...

Page 405: ...1 Prot ExBlo Prot Active 1 n Assignment List Prot ExBlo 2 Prot ExBlo1 I Prot ExBlo2 I AND Prot Available Measured Values OK At the moment no parameter is being changed except parameter set parameters...

Page 406: ...signal OR ed from all protection elements Prot Trip is the collective Trip signal OR ed from all protection elements and etc The Tripping commands of the protection elements have to be fed to the Bkr...

Page 407: ...EDR 5000 IM02602007E www eaton com 407 Prot Trip Name Trip Name Each trip of an active trip authorized protection module will lead to a general trip Name Trip Prot Trip Name n Trip 15 15 15 OR...

Page 408: ...7E www eaton com 408 Prot Pickup Prot Pickup Name Pickup Name Pickup Name Pickup Name Each pickup of a module except from supervision modules but including BF will lead to a general pickup collective...

Page 409: ...e will lead to a phase selective general trip 19c 19d 23 OR Prot Trip Phase A 50P 1 n Trip Phase A 51P 1 n Trip Phase A V n Trip Phase A 16a 16b 20 OR Prot Trip Phase B 50P 1 n Trip Phase B 51P 1 n Tr...

Page 410: ...o a phase selective general pickup collective pickup 27c 27d 31 OR Prot Pickup Phase B 50P 1 n Pickup IB V n Pickup Phase B 25a 29 OR 51P 1 n Pickup IB 25b Prot Pickup Phase C 50P 1 n Pickup IC V n Pi...

Page 411: ...al protection functionality of the device Inactive Active Inactive Protection Para Global Prot Para Prot ExBlo1 If external blocking of this module is activated allowed the global protection functiona...

Page 412: ...nal General Trip Phase A Trip Phase B Signal General Trip Phase B Trip Phase C Signal General Trip Phase C Trip IX or IR Signal General Trip Ground Fault Trip Signal General Trip Res FaultNo a GridFau...

Page 413: ...t circuit might cause several faults with trip and autoreclosing each fault being identified by an increased fault number In this case the grid fault number remains the same Trip First trip cause whic...

Page 414: ...to live parts of a system Beside protection functions protective relays more and more will take care about controlling switchgear like breakers load break switches disconnectors and ground connectors...

Page 415: ...ment can be issued to the same output relays where the other control commands are issued If the commands are issued to different relays output relays the amount of wiring increases Assignment of Posit...

Page 416: ...become true Supervision of the OPEN command When an OPEN command is initiated the t Move OPEN timer will be started While the timer is running the POS INDETERM State will become true If the command i...

Page 417: ...gnal Pos Indeterm disappears If the moving time elapsed before the switchgear has reached the end position the switching operation was not successful and the Position Indication will change to POS Dis...

Page 418: ...ositions Aux CLOSE I Aux OPEN I POS CLOSE POS OPEN POS Indeterm POS Disturb POS State Not wired 0 0 0 1 while t Move OPEN is running 0 while t Move OPEN is running 0 Intermediate Not wired 1 0 1 0 0 1...

Page 419: ...Manual Switch Command Auto reclosure issues the following commands Automatic Switch Command Protection issues Trip Command e g 50P Interlockings AND Trip command assigned and configured within the Tr...

Page 420: ...assigned in the Trip Manager lead to an operation of the switchgear In addition to that the User can set the minimum hold time of the tripping command within this module and define whether the trippi...

Page 421: ...ctive Bkr Latched R TripCmd Cr Bkr Res TripCmdCr Name TripCmd Name TripCmd Name TripCmd Name TripCmd Acknowledge HMI Acknowledge 1 n Assignment List Acknowledge Comm Name Each trip of an active trip a...

Page 422: ...ronizm defines which signal indicates synchronizm If the synchronizm condition shall be evaluated by the internal Synch Check module the signal Sync Ready to Close release by synch check module has to...

Page 423: ...Signal Breaker Ready Trigger x Trigger x Synchronizm B r e a k e r BreakerOPEN Command BreakerCLOSE Command Trip Command CLOSE Request Position Indication OPEN CLOSE Indeterminated Disturbed HMI Auto...

Page 424: ...ngle command Permanent Non interlocked switching for a certain time Non interlocked switching activated by an assigned signal The set time for non interlocked switching applies also for the single Ope...

Page 425: ...breaker alarm Inactive Active Inactive Operation Reset Ack TripCmd Acknowledge Trip Command Inactive Active Inactive Operation Reset Global Protection Parameters of the Control Parameter Description S...

Page 426: ...ng of the OPEN command 1 n Assignment List Control Bkr Interlockings Interl OPEN3 Interlocking of the OPEN command 1 n Assignment List Control Bkr Interlockings SC CLOSE Switching CLOSE Command e g th...

Page 427: ...ontrol Bkr Trip Manager Trigger5 Open Command to the Breaker if the state of the assigned signal becomes true 1 n Trip Cmds 51P 2 TripCmd Control Bkr Trip Manager Trigger6 Open Command to the Breaker...

Page 428: ...true 1 n Trip Cmds 27M 1 TripCmd Control Bkr Trip Manager Trigger16 Open Command to the Breaker if the state of the assigned signal becomes true 1 n Trip Cmds 27M 2 TripCmd Control Bkr Trip Manager T...

Page 429: ...mes true 1 n Trip Cmds 46 2 TripCmd Control Bkr Trip Manager Trigger27 Open Command to the Breaker if the state of the assigned signal becomes true 1 n Trip Cmds 47 1 TripCmd Control Bkr Trip Manager...

Page 430: ...the assigned signal becomes true 1 n Trip Cmds PF 55A 1 TripCmd Control Bkr Trip Manager Trigger38 Open Command to the Breaker if the state of the assigned signal becomes true 1 n Trip Cmds PF 55A 2...

Page 431: ...eaker if the state of the assigned signal becomes true 1 n Trip Cmds Control Bkr Trip Manager Trigger49 Open Command to the Breaker if the state of the assigned signal becomes true 1 n Trip Cmds Contr...

Page 432: ...he module input Acknowledgment Signal only for automatic acknowledgment Module input signal Control Bkr Trip Manager Interl CLOSE1 I State of the module input Interlocking of the CLOSE command Control...

Page 433: ...inputs are active Interl OPEN Signal One or more IL_Open inputs are active CES succesf Signal Command Execution Supervision Switching command executed successfully CES Disturbed Signal Command Executi...

Page 434: ...Cmd Signal CLOSE command issued to the switchgear Depending on the setting the signal may include the CLOSE command of the Prot module OPEN Cmd Signal OPEN command issued to the switchgear Depending...

Page 435: ...ve that the user provides The relay will monitor the frequency of CLOSE OPEN cycles The User can set thresholds for the maximum allowed sum of interrupt currents and the maximum allowed sum of interru...

Page 436: ...nts that the user can replicate the switchgear wear curve within menu Control SG SG x SGW Each point has two settings the interrupt current in kilo amperes and the allowed operation counts No matter h...

Page 437: ...an alarm will be issued The breaker maintenance curve is to be taken from the technical data sheet of the breaker manufactor By means of the available points this curve is to be replicated Inactive Ac...

Page 438: ...Only available if Bwear Curve Fc Active 1 32000 1900 Control Bkr Bwear Current5 Interrupted Current Level 5 Only available if Bwear Curve Fc Active 0 00 2000 00kA 5 00kA Control Bkr Bwear Count5 Open...

Page 439: ...Control Bkr Bwear Current9 Interrupted Current Level 9 Only available if Bwear Curve Fc Active 0 00 2000 00kA 20 00kA Control Bkr Bwear Count9 Open Counts Allowed 9 Only available if Bwear Curve Fc A...

Page 440: ...es TripCmdCr Signal Resetting of the Counter total number of trip commands Res Isum trip Signal Reset summation of the tripping currents WearLevel Alarm Signal Breaker Wear curve Alarm WearLevel Locko...

Page 441: ...0 00A 0 00 1000 00A Operation Count and RevData Control Bkr Isum trip IC Summation of the tripping currents phase 0 00A 0 00 1000 00A Operation Count and RevData Control Bkr Isum Intr per hour Sum pe...

Page 442: ...Active Inactive Operation Reset Res Isum trip Reset summation of the tripping currents Inactive Active Inactive Operation Reset Res Isum Intr per hour Sum per hour of interrupting currents Inactive A...

Page 443: ...thority Local Remote Switching Authority Remote SG Indeterm Minimum one Switchgear is moving Position cannot be determined SG Disturb Minimum one Switchgear is disturbed Counters of the Control Module...

Page 444: ...Signal Digital Input DI 8 X6 DI 8 Signal Digital Input Logic LE1 Gate Out Signal Output of the logic gate Logic LE1 Timer Out Signal Timer Output Logic LE1 Out Signal Latched Output Q Logic LE1 Out i...

Page 445: ...ate Logic LE9 Timer Out Signal Timer Output Logic LE9 Out Signal Latched Output Q Logic LE9 Out inverted Signal Negated Latched Output Q NOT Logic LE10 Gate Out Signal Output of the logic gate Logic L...

Page 446: ...LE18 Out inverted Signal Negated Latched Output Q NOT Logic LE19 Gate Out Signal Output of the logic gate Logic LE19 Timer Out Signal Timer Output Logic LE19 Out Signal Latched Output Q Logic LE19 Ou...

Page 447: ...logic gate Logic LE28 Timer Out Signal Timer Output Logic LE28 Out Signal Latched Output Q Logic LE28 Out inverted Signal Negated Latched Output Q NOT Logic LE29 Gate Out Signal Output of the logic ga...

Page 448: ...LE37 Out inverted Signal Negated Latched Output Q NOT Logic LE38 Gate Out Signal Output of the logic gate Logic LE38 Timer Out Signal Timer Output Logic LE38 Out Signal Latched Output Q Logic LE38 Ou...

Page 449: ...logic gate Logic LE47 Timer Out Signal Timer Output Logic LE47 Out Signal Latched Output Q Logic LE47 Out inverted Signal Negated Latched Output Q NOT Logic LE48 Gate Out Signal Output of the logic ga...

Page 450: ...LE56 Out inverted Signal Negated Latched Output Q NOT Logic LE57 Gate Out Signal Output of the logic gate Logic LE57 Timer Out Signal Timer Output Logic LE57 Out Signal Latched Output Q Logic LE57 Ou...

Page 451: ...logic gate Logic LE66 Timer Out Signal Timer Output Logic LE66 Out Signal Latched Output Q Logic LE66 Out inverted Signal Negated Latched Output Q NOT Logic LE67 Gate Out Signal Output of the logic ga...

Page 452: ...LE75 Out inverted Signal Negated Latched Output Q NOT Logic LE76 Gate Out Signal Output of the logic gate Logic LE76 Timer Out Signal Timer Output Logic LE76 Out Signal Latched Output Q Logic LE76 Ou...

Page 453: ...Signal Trip Command 51R 2 TripCmd Signal Trip Command 27M 1 TripCmd Signal Trip Command 27M 2 TripCmd Signal Trip Command 59M 1 TripCmd Signal Trip Command 59M 2 TripCmd Signal Trip Command 27A 1 Trip...

Page 454: ...ipCmd Signal Trip Command 32V 2 TripCmd Signal Trip Command 32V 3 TripCmd Signal Trip Command PF 55D 1 TripCmd Signal Trip Command PF 55D 2 TripCmd Signal Trip Command PF 55A 1 TripCmd Signal Trip Com...

Page 455: ...itching authority and interlockings can be set By means of the softkey SG it can be switched to the menu SG In this menu specific settings for the switch gear can be done This page can be directly cal...

Page 456: ...l or Local and Remote Now it is possible to execute switching commands at the HMI Push the right arrow softkey to get to the control page The breaker is opened therefore it can be closed only After pu...

Page 457: ...chgear It will be shown on the display when the switchgear reaches the new end position Further possible switching operations OPEN will be displayed by softkeys Notice For the case the switchgear does...

Page 458: ...rrent protection elements time inverse or instantaneous or time delay etc can trip in a specified fault current direction When the trip direction is set to Non directional the directon detection takes...

Page 459: ...poss Prot I dir rev Prot I dir fwd VA IA IB IC VC VB Prot I Phase MTA VAB VA VBC VB VCA VC VBC I1 Phase M TA Reverse Forward Voltage memory Forward Reverse Not possible Prot Phase failure Direction De...

Page 460: ...directio nal Reverse For wa rd Name Mode AND AND Prot I dir fwd Prot I dir rev Name Fault in Projected Direction F orw ard R everse Direction Decision Phase overcurrent AND Prot I dir n poss N ot pos...

Page 461: ...ion will be displayed as ANSI 50 elements That means that the name of an ANSI 50 element wont change if it is set within the device planning from non directional to directional For each element the fo...

Page 462: ...Element is not deactivated and no active blocking signals AND AND AND Name IH2 Blo Tripping command deactivated or blocked 5 6 7 4 3 Please Refer to Diagram IH2 Please Refer to Diagram IH2 Please Refe...

Page 463: ...ssignment List Protection Para Global Prot Para I Prot 50P 1 ExBlo2 External blocking of the module if blocking is activated allowed within a parameter set and if the state of the assigned signal is t...

Page 464: ...Global Prot Para I Prot 50P 1 AdaptSet 2 Assignment Adaptive Parameter 2 AdaptSet Protection Para Global Prot Para I Prot 50P 1 AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet Protection Para Glo...

Page 465: ...parameterized Rvs Blo Fc active Inactive Active Inactive Protection Para 1 4 I Prot 50P 1 Blo TripCmd Permanent blocking of the Trip Command of the module element Inactive Active Inactive Protection P...

Page 466: ...602007E Parameter Description Setting range Default Menu path t Tripping delay Only available if Characteristic DEFT 0 00 300 00s 50P 1 0s 50P 2 0 25s 50P 3 0 25s Protection Para 1 4 I Prot 50P 1 www...

Page 467: ...otection Para Global Prot Para I Prot 50P 1 Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para I Prot 50P 1 AdaptSet1 I Module Input State Adaptive Parameter1 Protection Pa...

Page 468: ...Blocking of the Trip Command Pickup IA Signal Pickup IA Pickup IB Signal Pickup IB Pickup IC Signal Pickup IC Pickup Signal Pickup Trip Signal Trip TripCmd Signal Trip Command Active AdaptSet Active A...

Page 469: ...y please refer to the tolerances of the protection elements breaker operating time about 50 ms Please take the breaker operating times from the technical data specified in the relevant documentation p...

Page 470: ...e measured total tripping delays or individual tripping delays threshold values and dropout ratios correspond with those values specified in the adjustment list Permissible deviations tolerances can b...

Page 471: ...on the parameter setting either trip non directional or it will be blocked All overcurrent protective elements are identically structured This module offers Adaptive Parameter Sets Parameters can be m...

Page 472: ...anned as non directional or optionally as directional elements This means all 6 elements can be planned user defined in forward reverse or non directional For each element the following characteristic...

Page 473: ...d and no active blocking signals AND AND AND Name IH2 Blo Imax Tripping command deactivated or blocked 5 6 7 4 3 Please Refer to Diagram IH2 Please Refer to Diagram IH2 Please Refer to Diagram IH2 24b...

Page 474: ...5 6 7 4 3 Please Refer to Diagram IH2 Please Refer to Diagram IH2 Please Refer to Diagram IH2 15a 24b 25b 26b 14 OR OR AND AND AND AND AND INV Imax Name t reset Name t multiplier Name Curve Shape Name...

Page 475: ...vercurrent protection may achieve adequate sensitivity and better coordination The device uses a simple linear model to determine the effective pickup by characterizing the relationship between the vo...

Page 476: ...MainVT sec 3 If the parameter VT con within the field parameters is set to Phase to Phase the setting Phase to Neutral in the current modules is effectless Device Planning Parameters of the 51P Modul...

Page 477: ...odule the element if blocking is activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para I Prot 51P 1 Rvs Blo Reve...

Page 478: ...hose modules element are blocked that are parameterized Rvs Blo Fc active Inactive Active Inactive Protection Para 1 4 I Prot 51P 1 Blo TripCmd Permanent blocking of the Trip Command of the module ele...

Page 479: ...depends on the selected tripping curve 0 02 20 00 51P 1 1 51P 2 2 51P 3 3 Protection Para 1 4 I Prot 51P 1 Reset Mode Reset Mode Instantaneous t delay Calculated Calculated Protection Para 1 4 I Prot...

Page 480: ...stem Parameters Main VT con is set to Wye Vn Main VT sec SQRT 3 Only available if VRestraint Active 0 04 1 30Vn 1 00Vn Protection Para 1 4 I Prot 51P 1 LOP Blo Activates the use of the measuring circu...

Page 481: ...ection Para Global Prot Para I Prot 51P 1 Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para I Prot 51P 1 AdaptSet1 I Module Input State Adaptive Parameter1 Protection Para...

Page 482: ...ocking of the Trip Command Pickup IA Signal Pickup IA Pickup IB Signal Pickup IB Pickup IC Signal Pickup IC Pickup Signal Pickup Trip Signal Trip TripCmd Signal Trip Command Active AdaptSet Active Ada...

Page 483: ...e protection stages breaker operating time about 50 ms Please take the breaker operating times from the technical data specified in the relevant documentation provided by the breaker manufacturer Nece...

Page 484: ...refer to the tolerances of the protection stages breaker operating time about 50 ms Please take the breaker switching times from the technical data specified in the relevant documentation provided by...

Page 485: ...e measured total tripping delays or individual tripping delays threshold values and dropout ratios correspond with those values specified in the adjustment list Permissible deviations tolerances can b...

Page 486: ...acturer Necessary means Current source Voltage Source Current and Voltage meters and Timer Procedure Testing the threshold values 3 x single phase and 1 x three phase Feed Pickup voltage For each test...

Page 487: ...Please proceed as follows Read and understand the section Adaptive Parameters within the chapter Parameter Do the device planning and set all required parameters for the Undervoltage element Do the d...

Page 488: ...be either measured or calculated This can be selected by the parameter 3V0 Source in the System Para Direction menu IX Neg With this selection the negative phase sequence voltage and current Polarizi...

Page 489: ...le or else IX 3V0 measured If V2 and I2 are available 90 Phase MTA else Ground MTA IX Dual Measured Negative phase sequence current and voltage preferred measured ground current and neutral voltage al...

Page 490: ...Source System Para Calculated VR calc VX meas IX 3V0 IX Neg IX Dir Cntrl IX Dual 3V0 3V0 If V2 and I2 are available I2 is the operating quantity else IX is the operating quantity V2 IG IX meas 90 Phas...

Page 491: ...Ground overcurrent protection directional Device Planning menu Setting Forward Reverse Measuring Mode Fundamental TrueRMS VX Selection measured 1 calculated 1 for wiring see chapter Connection Exampl...

Page 492: ...aracteristics are available DEFT definite time For tripping curves please refer to Instantaneous Current Curves Ground Current Measured located in the Appendix The ground current can be measured eithe...

Page 493: ...ctivated or blocked IH2 Blo IG Inactive Active Name IGH2 Blo AND Name Pickup Name IGH2 Blo 8 4 3 Please Refer to Diagram IH2 15 14 27a 19a AND AND AND DEFT Name t Name Pickup IX Measured Fund RMS Name...

Page 494: ...owed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para I Prot 50X 1 ExBlo TripCmd External blocking of the Trip Command of the...

Page 495: ...etting range Default Menu path AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet Protection Para Global Prot Para I Prot 50X 1 AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet Protection Para Glo...

Page 496: ...tion parameter If the signal becomes true those modules element are blocked that are parameterized Rvs Blo Fc active Inactive Active Inactive Protection Para 1 4 I Prot 50X 1 Blo TripCmd Permanent blo...

Page 497: ...u path Pickup sensitive If the pickup value is exceeded the module element will be started 0 002 2 000In 0 02In Protection Para 1 4 I Prot 50X 1 t Tripping delay Only available if Characteristic DEFT...

Page 498: ...ommand Protection Para Global Prot Para I Prot 50X 1 Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para I Prot 50X 1 AdaptSet1 I Module Input State Adaptive Parameter1 Prot...

Page 499: ...ickup IX or IR Trip Signal Trip TripCmd Signal Trip Command Active AdaptSet Active Adaptive Parameter DefaultSet Signal Default Parameter Set AdaptSet 1 Signal Adaptive Parameter 1 AdaptSet 2 Signal A...

Page 500: ...Reverse Measuring Mode Fundamental TrueRMS VX Selection measured 1 calculated 1 for wiring see chapter Connection Examples VT Wye with Broken Delta Criterion For all protection elements it can be det...

Page 501: ...IEC XInv LINV IEC XInv EINV IEC XInv MINV ANSI XInv VINV ANSI XInv EINV ANSI XInv Thermal Flat IT I2T and I4T For tripping curves please refer to Time Current Curves Ground Current located in the App...

Page 502: ...ctive Name IGH2 Blo AND Name Pickup Name IGH2 Blo 8 4 3 Please Refer to Diagram IH2 15 14 27b 19b AND AND AND IX Measured Fund RMS Name Criterion 51X 1 n Name 51X 1 n INV Name t reset Name t multiplie...

Page 503: ...rot 51X 1 ExBlo2 External blocking of the module if blocking is activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot...

Page 504: ...ent Adaptive Parameter 2 AdaptSet Protection Para Global Prot Para I Prot 51X 1 AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet Protection Para Global Prot Para I Prot 51X 1 AdaptSet 4 Assignment...

Page 505: ...protection parameter If the signal becomes true those modules element are blocked that are parameterized Rvs Blo Fc active Inactive Active Inactive Protection Para 1 4 I Prot 51X 1 Blo TripCmd Perman...

Page 506: ...at IT I2T I4T ANSI MINV Protection Para 1 4 I Prot 51X 1 t multiplier Time multiplier tripping characteristic factor The setting range depends on the selected tripping curve 0 02 20 00 51X 1 1 51X 2 2...

Page 507: ...ommand Protection Para Global Prot Para I Prot 51X 1 Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para I Prot 51X 1 AdaptSet1 I Module Input State Adaptive Parameter1 Prot...

Page 508: ...ickup IX or IR Trip Signal Trip TripCmd Signal Trip Command Active AdaptSet Active Adaptive Parameter DefaultSet Signal Default Parameter Set AdaptSet 1 Signal Adaptive Parameter 1 AdaptSet 2 Signal A...

Page 509: ...raditional way to polarize a ground fault element is to use neutral voltage 3V0 The neutral voltage can however be either measured or calculated This can be selected by the parameter 3V0 Source in the...

Page 510: ...ent and neutral ground current IR IX 0 fixed IR IPol N A Residual current and neutral ground current preferred residual current and neutral voltage alternatively IR IX if available or else IR 3V0 meas...

Page 511: ...IX meas I2 V2 I0 IR calc Prot IR dir n poss Prot IR dir rev Prot IR dir fwd Forward Reverse Not possible 10a 10a polarizing operating Prot 50R 51R Direction Detection o p e r a ti n g 0 fixed Ground M...

Page 512: ...R Ground overcurrent protection directional Device Planning menu Setting Forward Reverse Measuring Mode Fundamental TrueRMS VX Selection measured 1 calculated 1 for wiring see chapter Connection Examp...

Page 513: ...racteristics are available DEFT definite time For tripping curves please refer to Instantaneous Current Curves Ground Current Calculated located in the Appendix The ground current can be measured eith...

Page 514: ...Blo IG Inactive Active Name IGH2 Blo AND Name Pickup Name IGH2 Blo 8 4 3 Please Refer to Diagram IH2 15 14 27c 19c AND AND AND Fund RMS Name Criterion 50R 1 n Name 50R 1 n IX Calculated Name t Name Pi...

Page 515: ...owed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para I Prot 50R 1 ExBlo TripCmd External blocking of the Trip Command of the...

Page 516: ...e element This parameter is only effective if a signal is assigned to the corresponding global protection parameter If the signal becomes true those modules elements are blocked that are parameterized...

Page 517: ...that are parameterized ExBlo TripCmd Fc active Inactive Active Inactive Protection Para 1 4 I Prot 50R 1 Criterion Measuring method fundamental or rms or 3rd harmonic only generator protection relays...

Page 518: ...ommand Protection Para Global Prot Para I Prot 50R 1 Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para I Prot 50R 1 AdaptSet1 I Module Input State Adaptive Parameter1 Prot...

Page 519: ...IX or IR Trip Signal Trip TripCmd Signal Trip Command Active AdaptSet Active Adaptive Parameter DefaultSet Signal Default Parameter Set AdaptSet 1 Signal Adaptive Parameter 1 AdaptSet 2 Signal Adapti...

Page 520: ...d Reverse Measuring Mode Fundamental TrueRMS VX Selection measured 1 calculated 1 for wiring see chapter Connection Examples VT Wye with Broken Delta Criterion For all protection elements it can be de...

Page 521: ...IEC XInv LINV IEC XInv EINV IEC XInv MINV ANSI XInv VINV ANSI XInv EINV ANSI XInv Thermal Flat IT I2T and I4T For tripping curves please refer to Time Current Curves Ground Current located in the App...

Page 522: ...tive Name IGH2 Blo AND Name Pickup Name IGH2 Blo 8 4 3 Please Refer to Diagram IH2 15 14 27d 19d AND AND AND Fund RMS Name Criterion INV Name t reset Name t multiplier Name Curve Shape Name Reset Mode...

Page 523: ...rot 51R 1 ExBlo2 External blocking of the module if blocking is activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot...

Page 524: ...ent Adaptive Parameter 2 AdaptSet Protection Para Global Prot Para I Prot 51R 1 AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet Protection Para Global Prot Para I Prot 51R 1 AdaptSet 4 Assignment...

Page 525: ...on parameter If the signal becomes true those modules element are blocked that are parameterized Rvs Blo Fc active Inactive Active Inactive Protection Para 1 4 I Prot 51R 1 Blo TripCmd Permanent block...

Page 526: ...Time multiplier tripping characteristic factor The setting range depends on the selected tripping curve 0 02 20 00 51R 1 1 51R 2 2 Protection Para 1 4 I Prot 51R 1 Reset Mode Reset Mode Instantaneous...

Page 527: ...ommand Protection Para Global Prot Para I Prot 51R 1 Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para I Prot 51R 1 AdaptSet1 I Module Input State Adaptive Parameter1 Prot...

Page 528: ...ickup IX or IR Trip Signal Trip TripCmd Signal Trip Command Active AdaptSet Active Adaptive Parameter DefaultSet Signal Default Parameter Set AdaptSet 1 Signal Adaptive Parameter 1 AdaptSet 2 Signal A...

Page 529: ...back up protection to the downstream breaker and 2 protection of the conductors between the upstream and downstream breakers For faults which occur on the conductors between the upstream and downstrea...

Page 530: ...ycles settable to wait for downstream devices interlocking signals Zone interlocking trip signal only possible by absence of zone interlocking INPUT signals Configurable zone interlocking trip functio...

Page 531: ...sent to the upstream device if a breaker failure on downstream device is detected Parameter Description Setting range Default Menu path ExBlo1 External blocking of the module if blocking is activated...

Page 532: ...ication is only used for an upstream device main breaker or Zone 1 the setting ZoneInterlockOut within the OUTPUT group should be disabled TRIP Activate the Zone Trip The TRIP group comprises the sett...

Page 533: ...ding global protection parameter If the signal becomes true those modules elements are blocked that are parameterized ExBlo Fc active Inactive Active Inactive Protection Para 1 4 ZI General Settings B...

Page 534: ...Type Phase Ground Both Both Protection Para 1 4 ZI Zone Trip Zone Interlocking Output Logic X2 The following current protective function elements serve as the Phase Zone Interlock OUTPUT start functio...

Page 535: ...2602007E www eaton com 535 ZI OUT Zone Interlocking OUTPUT Logic Timing STARTED STANDBY TRIPPED RESET STANDBY STATE TRANSFER 51P 1 Trip 51P 1 Pickup ZI Bkr Blo t t 0 1 0 1 t 0 1 t 0 1 t 0 1 Reset Time...

Page 536: ...ripCmd 50X 1 Pickup 51X 1 Pickup 50X 2 Pickup 50R 1 Pickup 51R 1 Pickup 50R 2 Pickup 50X 1 TripCmd 51X 1 TripCmd 50X 2 TripCmd 50R 1 TripCmd 51R 1 TripCmd 50R 2 TripCmd Active ZI OUT Fc Inactive BF Tr...

Page 537: ...llowing overcurrent protection elements trigger Phase Zone Interlock trip functions 1 5 51P 1 50P 1 and 50P 2 The following overcurrent protection elements trigger Ground Zone Interlock trip functions...

Page 538: ...07E www eaton com 538 Zone Interlocking TRIP Logic Timing STARTED STANDBY TRIPPED STANDBY INTERLOCKED STANDBY ZI Trip STATE TRANSFER 51P 1 Pickup ZI Pickup t t 0 1 0 1 t 0 1 t 0 1 t 0 1 Trip Delay Tim...

Page 539: ...kup 50R 1 Pickup 51R 1 Pickup 50R 2 Pickup Active Trip Inactive ZI Ground Pickup ZI Phase Pickup ZI Phase Trip ZI Ground Trip ZI Trip ZI IN ZI Zone Trip Please Refer to Diagram Blockings 2 Element is...

Page 540: ...External Blocking Blo TripCmd Signal Trip Command blocked ExBlo TripCmd Signal External Blocking of the Trip Command Bkr Blo Signal Blocked by Breaker Failure Phase Pickup Signal Zone Interlocking Pha...

Page 541: ...tputs may be paralleled from up to ten devices FP 5000 or DT 3000 or a combination of both for connection to upstream zone interlocked relays www eaton com 541 Zone 1 J3 FP X000 1 4 2 Out In Com X2 13...

Page 542: ...such as an FP5000 DT3000 etc As an upstream device the terminals Phase Ground IN should be connected to the OUT terminals of up to ten downstream device s by means of a dedicated cable wired in paral...

Page 543: ...2 for Device EDR 4000 EDR 5000 EMR 4000 EMR 5000 EGR 4000 and EGR 5000 www eaton com 543 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 RO3 X Do not use Do not use COM OUT IN COM RO4 RO1 RO2 1 2 3 4 5 6...

Page 544: ...rip pickup setting It is defined by the ratio of negative sequence current to positive sequence current I2 I1 for ABC rotation and I1 I2 for ACB rotation The device will automatically select the corre...

Page 545: ...agram Blockings IA Name Pickup Please Refer to Diagram Trip Blockings 46 1 n Element is not deactivated and no active blocking signals Tripping command deactivated or blocked IC IB Name 46 1 n 2 3 15a...

Page 546: ...ate of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para Unbalance Prot 46 1 ExBlo2 External blocking of the module if blocking is activated allowed within a parameter s...

Page 547: ...ctive if a signal is assigned to the corresponding global protection parameter If the signal becomes true those modules elements are blocked that are parameterized ExBlo TripCmd Fc active Inactive Act...

Page 548: ...ra Unbalance Prot 46 1 ExBlo TripCmd I Module Input State External Blocking of the Trip Command Protection Para Global Prot Para Unbalance Prot 46 1 Current Unbalance Module Signals Output States Sign...

Page 549: ...de for I2 Fund is the same as that for the balanced nominal currents fed to the relay it implies that the phase sequence of the currents seen by the relay is reversed Now turn off phase A Again check...

Page 550: ...I1 100 so the first condition I2 I1 2 is always fulfilled Now increase the phase A current until the relay is activated Testing the dropout ratio of the threshold values Having tripped the relay in th...

Page 551: ...e previous test now decrease the phase A current The dropout of I2 I1 has to be 1 below the I2 I1 setting Successful test result The measured trip delays threshold values and dropout ratios are within...

Page 552: ...load condition is finished a cold to warm load condition is detected due to for example breaker closing or load current injection a load inrush detector will be initiated that supervises the coming a...

Page 553: ...ually the CLPU enabled signal will be issued for this time That means for the duration of this time the tripping thresholds of the overcurrent protection can be desensitized by means of adaptive param...

Page 554: ...EDR 5000 IM02602007E Example Mode Breaker Position www eaton com 554 Name CLPU CLPU CinBkr 52a 0 1 0 1 CLPU detected t Load Off t Max Block Cold Load 0 1...

Page 555: ...A IB IC CLPU I AR Running CLPU AND AND AND I Bkr State And I CLPU Mode Bkr State Bkr State Or I OR OR Bkr x Pos OPEN Applies only for devices with Auto Reclosure AND CLPU Load Inrush CLPU Settle Time...

Page 556: ...rnal blocking of the module if blocking is activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para CLPU ExBlo2 Ext...

Page 557: ...the corresponding global protection parameter If the signal becomes true those modules element are blocked that are parameterized Rvs Blo Fc active Inactive Active Inactive Protection Para 1 4 CLPU t...

Page 558: ...t Para CLPU Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para CLPU Signals of the Cold Load Pickup Module States of the Outputs Signal Description Active Signal Active ExB...

Page 559: ...Combine the abruptly changing current switching the current ON and OFF with the manual switching ON and OFF of the breaker Mode I or Bkr state Initially carry out the test with an abruptly changing c...

Page 560: ...ured total tripping delays or individual tripping delays threshold values and drop out ratios correspond with those values specified in the adjustment list Permissible deviations tolerances can be fou...

Page 561: ...ually and or An external trigger This protection module can initiate a high speed trip of the overcurrent protection modules The module can be started via a digital input that indicates that the break...

Page 562: ...no active blocking signals Name SOTF 2 SOTF enabled SOTF I IA IB IC SOTF I SOTF AR Blo AR Running S OTF t en able t T Ext SOTF SOTF AND AND AND I Bkr State And I SOTF Mode Bkr State Bkr manual CLOSE...

Page 563: ...d allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para SOTF ExBlo2 External blocking of the module if blocking is activat...

Page 564: ...active Inactive Active Inactive Protection Para 1 4 SOTF Rvs Blo Fc Activate allow or inactivate disallow reverse blocking of the module element This parameter is only effective if a signal is assigne...

Page 565: ...everse Blocking Protection Para Global Prot Para SOTF Ext SOTF I Module Input State External Switch Onto Fault Alarm Protection Para Global Prot Para SOTF Signals of the Switch Onto Fault Module Outpu...

Page 566: ...stinctly greater than the I threshold to the measuring inputs of the relay Mode I and Bkr state Simultaneously manually switch on the breaker and feed with an abrupt change current that is distinctly...

Page 567: ...sured total tripping delays or individual tripping delays threshold values and drop out ratios correspond with those values specified in the adjustment list Permissible deviations tolerances can be fo...

Page 568: ...ollows Flexible assignment of initiate functions for individual shots Maximum of six autoreclose shots Dynamic adjustment of protection setting values e g pickup time delay tripping curve etc during a...

Page 569: ...to the line and all circuits connected on the line will still be energized 80 90 of the faults are not permanent After a period from 0 5 up to 1 sec the line is probably no longer faulty and the compl...

Page 570: ...he pre shot the trigger start events can be assigned For each shot a maximum of four initiate functions protective functions which are dedicated to start this shot can be selected from a list of avail...

Page 571: ...te transitions between the various states of the autoreclosure function This diagram visualizes the run time logic and timing sequence according to the state transition direction and the events which...

Page 572: ...AR Cycle Start t dead t Run2Ready 4 Lock True Initiate AR InitiateFc True successful Bkr Pos CLOSE Lock True Bkr Pos CLOSE t ManualCloseBlock timer elapsed Reset Lockout True t Reset Lockout timer el...

Page 573: ...art functions and No external or internal AR blocking signals are present No autoreclose shot operation is possible if the autoreclose function is within Standby state 2 t manual close block Suppose t...

Page 574: ...in Ready state 4 Run Cycle The RUN state can only be reached if the following conditions are fulfilled The autoreclose was in READY state before The breaker was in closed position before No external o...

Page 575: ...n activated autoreclose function goes into the BLOCKED state when one of the assigned blocking functions is true The autoreclose function exits the BLOCKED state if the assigned blocking signal is no...

Page 576: ...e Autoreclose rate per hour exceeds the limit Breaker failure during AR starting Manual breaker close operation during autoreclose process At least one protective function is still tripping before the...

Page 577: ...False Shot Shot 1 tCI start Shot Shot 1 tCI start CB_CLOSE True t Run2Ready 16 t dead 14 Waiting Bkr Open 13 Ready 11 Ready 11 AR Lock True AR Blo True AR Lock True AR Lock True AR Blo True AR Blo Tr...

Page 578: ...ion is not initiated from any initiate start functions and No external or internal AR blocking signals are present 13 Waiting Bkr Open While in the WAITING BKR OPEN state the autoreclosure supervises...

Page 579: ...The breaker is in open position The breaker is ready for next reclosing operation if the CB Ready logic input is used No pickup from current assigned AR initiate function s No trip from current assign...

Page 580: ...more faults detected within the t Run2Ready timer the autoreclosure logic will leave the RUN state and goes back to the READY state The flag successful is set Unsuccessful Autoreclose If a fault is de...

Page 581: ...w eaton com 581 Pre Shot Shot AR Running Shot 1 Shot 2 AR Module states t 0 1 Ready Running Lockout Reclosing t 0 1 Bkr State t 0 1 Protection t 0 1 Protection t 0 1 Fault t 0 1 t D1 t D2 t Run2Ready...

Page 582: ...ww eaton com 582 Pre Shot Shot AR Running Shot 1 Shot 2 AR Module states t 0 1 Ready Running Ready Reclosing t 0 1 Bkr State t 0 1 Protection t 0 1 Protection t 0 1 Fault t 0 1 t D1 t D2 t Run2Ready P...

Page 583: ...mer does not care about that and timing continues until it times out After it times out the AR module looks at the breaker status again and sees that the breaker is open The AR goes to the STANDBY sta...

Page 584: ...w eaton com 584 Lockout Reset AR Module states t 0 1 Lockout t Man Close Blo Ready Manual Breaker Close t 0 1 t 0 1 Lockout Reset Time t ManualCloseBlock t Reset Lockout Standby Bkr State Pos OPEN Pos...

Page 585: ...with a reclosure and fuse By means of the zone coordination a fuse saving scheme might be realized In order to save fuses the downstream protective device might trip for the first reclosure attempt at...

Page 586: ...e assigned overcurrent protection pickup signal This exhibits that the fault current was tripped by the downstream recloser opening The shot counter of an enabled zone coordination will be incremented...

Page 587: ...EDR 5000 IM02602007E www eaton com 587 Protective Device Recloser Shot1 triggered by I 1 Tripping Curve ofthe Fuse Shot2 triggered by I 2 Shot1 triggered by I 1 Shot2 triggered by I 2 I t I t I t...

Page 588: ...t Res ServiceCr Reset the Service Counters Inactive Active Inactive Operation Reset Reset Lock via HMI Reset the AR Lockout via the panel Inactive Active Inactive Operation Reset Res Max Shots h Cr Re...

Page 589: ...bal Prot Para AR General Settings Ex Shot Inc The AR Shot counter will be incremented by this external Signal This can be used for Zone Coordination of upstream Auto Reclosure devices 1 n DI LogicList...

Page 590: ...t and delay curve operation thus avoiding overtripping Inactive Active Inactive Protection Para 1 4 AR General Settings Ex Shot Inc Fc The AR Shot counter will be incremented by this external Signal T...

Page 591: ...Para 1 4 AR Shot Manager Shot 3 t D4 Dead time between trip and reclosure attempt Can be initiated either by a phase or a ground fault Only available if Shots 4 6 0 1 9999 00s 1s Protection Para 1 4...

Page 592: ...signal anymore 0 01 9999 00s 10 0s Protection Para 1 4 AR General Settings t AR Supervision AR Overall supervision time sum of all the timers used by AR 1 00 9999 00s 100 0s Protection Para 1 4 AR Ge...

Page 593: ...ot Manager Initiate AR Shot 1 InitiateFc1 Automatic Reclosure Attempt Initiate Function Only available if Shots 1 6 Start fct Protection Para 1 4 AR Shot Manager Shot 1 Shot 1 InitiateFc2 Automatic Re...

Page 594: ...6 Start fct Protection Para 1 4 AR Shot Manager Shot 2 Shot 2 InitiateFc4 Automatic Reclosure Attempt Initiate Function Only available if Shots 2 6 Start fct Protection Para 1 4 AR Shot Manager Shot...

Page 595: ...6 Start fct Protection Para 1 4 AR Shot Manager Shot 4 Shot 4 InitiateFc3 Automatic Reclosure Attempt Initiate Function Only available if Shots 4 6 Start fct Protection Para 1 4 AR Shot Manager Shot...

Page 596: ...teFc1 Automatic Reclosure Attempt Initiate Function Only available if Shots 6 Start fct Protection Para 1 4 AR Shot Manager Shot 6 Shot 6 InitiateFc2 Automatic Reclosure Attempt Initiate Function Only...

Page 597: ...m Auto Reclosure devices Note This parameter enables the functionallity only The assignment has to be set within the global parameters Protection Para Global Prot Para AR General Settings Ex Lock I Mo...

Page 598: ...been detected Blo Signal Auto Reclosure is blocked t Blo Reset Signal Delay Timer for resetting the AR blocking The release de blocking of the AR will be delayed for this time if there is no blocking...

Page 599: ...y executed Automatic Reclosures 0 0 65536 Operation Count and RevData AR Cr failed Total number of unsuccessfully executed automatic reclosure attempts 0 0 65536 Operation Count and RevData AR Cr Serv...

Page 600: ...te of the assigned signal is true If the state of this function is true the AR will be aborted 1 n Assignment List Protection Para Global Prot Para AR BlockFct Abort 4 Abort the AR cycle if the state...

Page 601: ...of the assigned signal is true If the state of this function is true the AR will be aborted Protection Para Global Prot Para AR BlockFct Abort 4 Abort the AR cycle if the state of the assigned signal...

Page 602: ...ipCmd Signal Trip Command 50X 2 TripCmd Signal Trip Command 51X 1 TripCmd Signal Trip Command 51X 2 TripCmd Signal Trip Command 50R 1 TripCmd Signal Trip Command 50R 2 TripCmd Signal Trip Command 51R...

Page 603: ...ual Digital Output DNP This corresponds to a virtual binary input of the protective device DNP BinaryOutput16 Virtual Digital Output DNP This corresponds to a virtual binary input of the protective de...

Page 604: ...C61850 GGIO Ind IEC61850 VirtInp6 Signal Virtual Input IEC61850 GGIO Ind IEC61850 VirtInp7 Signal Virtual Input IEC61850 GGIO Ind IEC61850 VirtInp8 Signal Virtual Input IEC61850 GGIO Ind IEC61850 Virt...

Page 605: ...e set by clients like e g the Master Communication System Single Point Controllable Status Output IEC61850 SPCSO7 Status bit that can be set by clients like e g the Master Communication System Single...

Page 606: ...lay setting is the time period an undervoltage must occur before the device initiates a trip Depending on the settings within the System Parameters the element works based on phase to phase Open Delta...

Page 607: ...n case that the breaker is open Assign the Bkr POS OPEN signal to a blocking input ExBlo1 or ExBlo2 within the Global Parameters of the 27M element and ExBlo Fc has to be set to active within the para...

Page 608: ...e VC However if line to line voltages are applied to the measuring inputs and field parameter Main VT Con is set to Phase to Phase then the messages should be interpreted as follows 27M 1 PICKUP A or...

Page 609: ...am Blockings Please Refer to Diagram Trip Blockings Element is not deactivated and no active blocking signals 27M 1 n Inactive Name LOP Blo Active Name 27M 1 n Tripping com mand deactivated or blocked...

Page 610: ...if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para Main V Prot 27M 1 ExBlo2 External blocking of the module if blocking is activated allowed within a para...

Page 611: ...cking of the module element This parameter is only effective if a signal is assigned to the corresponding global protection parameter If the signal becomes true those modules elements are blocked that...

Page 612: ...Main V Prot 27M 1 t Tripping delay 0 00 3000 00s 0 00s Protection Para 1 4 Main V Prot 27M 1 LOP Blo Activates the use of the measuring circuit supervision In this case the module will be blocked if a...

Page 613: ...te External Blocking of the Trip Command Protection Para Global Prot Para Main V Prot 27M 1 Undervoltage Protection Module Signals Output States Signal Description Active Signal Active ExBlo Signal Ex...

Page 614: ...se consider the following deviations For testing the threshold values the test voltage has to be decreased until the relay is activated For detection of the dropout ratio the measuring quantity has to...

Page 615: ...wo or all the Overvoltage function operates Depending on the settings within the System Parameters the element works based on phase to phase Open Delta or phase to ground wye voltages This element wil...

Page 616: ...e voltage VC However if line to line voltages are applied to the measuring inputs and field parameter Main VT con is set to Wye then the messages should be interpreted as follows 59M 1 PICKUP A or 59M...

Page 617: ...ickup Phase B Please Refer to Diagram Blockings Please Refer to Diagram Trip Blockings Element is not deactivated and no active blocking signals 59M 1 n AND AND Name 59M 1 n Tripping command deactivat...

Page 618: ...f the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para Main V Prot 59M 1 ExBlo2 External blocking of the module if blocking is activated allowed within a param...

Page 619: ...nactivate disallow blocking of the module element This parameter is only effective if a signal is assigned to the corresponding global protection parameter If the signal becomes true those modules ele...

Page 620: ...Description Setting range Default Menu path V Drop Out Drop Out is in percent of setting 80 99 97 Protection Para 1 4 Main V Prot 59M 1 t Tripping delay 0 00 3000 00s 0 00s Protection Para 1 4 Main V...

Page 621: ...te External Blocking of the Trip Command Protection Para Global Prot Para Main V Prot 59M 1 Overvoltage Protection Module Signals Output States Signal Description Active Signal Active ExBlo Signal Ext...

Page 622: ...hose of the voltmeter the deviation must be within the permissible toler ances Testing the trip delay For testing the trip delay a timer is to be connected to the contact of the associated trip relay...

Page 623: ...dervoltage setting for the Auxiliary VT This device setting works exactly the same as the 27M except it is a single phase element only operating from the Auxiliary VT input The Alarm Delay is the time...

Page 624: ...fer to Diagram Blockings Name Pickup Name Trip Name TripCmd V Please Refer to Diagram Trip Blockings Element is not deactivated and no active blocking signals Name 27A 1 n Tripping command deactivated...

Page 625: ...state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para Aux V Prot 27A 1 ExBlo2 External blocking of the module if blocking is activated allowed within a parameter s...

Page 626: ...Prot 27A 1 Blo TripCmd Permanent blocking of the Trip Command of the module element Inactive Active Inactive Protection Para 1 4 Aux V Prot 27A 1 ExBlo TripCmd Fc Activate allow or inactivate disallo...

Page 627: ...Prot 27A 1 ExBlo TripCmd I Module Input State External Blocking of the Trip Command Protection Para Global Prot Para Aux V Prot 27A 1 Aux Undervoltage Module Signals Output States Signal Description...

Page 628: ...tmeter the deviation must be within the permissible tolerances Testing the trip delay For testing the trip delay a timer is to be connected to the contact of the associated trip relay The timer is sta...

Page 629: ...ll elements are identically structured This is the 59 device Overvoltage setting for the Auxiliary VT This device setting works exactly the same as the 59M except it is a single phase element only ope...

Page 630: ...Refer to Diagram Blockings Name Pickup Name Trip Name TripCmd V Please Refer to Diagram Trip Blockings Element is not deactivated and no active blocking signals 59A 1 n Name 59A 1 n Tripping comm and...

Page 631: ...state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para Aux V Prot 59A 1 ExBlo2 External blocking of the module if blocking is activated allowed within a parameter se...

Page 632: ...Aux V Prot 59A 1 Blo TripCmd Permanent blocking of the Trip Command of the module element Inactive Active Inactive Protection Para 1 4 Aux V Prot 59A 1 ExBlo TripCmd Fc Activate allow or inactivate d...

Page 633: ...Prot 59A 1 ExBlo TripCmd I Module Input State External Blocking of the Trip Command Protection Para Global Prot Para Aux V Prot 59A 1 Aux Overvoltage Module Signals Output States Signal Description A...

Page 634: ...trip delay a timer is to be connected to the contact of the associated trip relay The timer is started when the limiting value of the tripping voltage is exceeded and it is stopped when the relay tri...

Page 635: ...Blockings Name Pickup Name Trip Name TripCmd VX Please Refer to Diagram Trip Blockings Element is not deactivated and no active blocking signals 59N 1 n Name 59N 1 n T ripping comm and deactivated or...

Page 636: ...ate of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para Neutral V Prot 59N 1 ExBlo2 External blocking of the module if blocking is activated allowed within a parameter...

Page 637: ...element Inactive Active Inactive Protection Para 1 4 Neutral V Prot 59N 1 ExBlo TripCmd Fc Activate allow or inactivate disallow blocking of the module element This parameter is only effective if a si...

Page 638: ...V Prot 59N 1 ExBlo TripCmd I Module Input State External Blocking of the Trip Command Protection Para Global Prot Para Neutral V Prot 59N 1 Neutral Overvoltage Module Signals Output States Signal Des...

Page 639: ...e voltmeter the deviation must be wi thin the permissible tolerances Testing the trip delay For testing the trip delay a timer is to be connected to the contact of the associated trip relay The timer...

Page 640: ...easuring input is compared Sync check The sync check function is provided for the applications where a line has two ended power sources The sync check function has the abilities to check voltage magni...

Page 641: ...Frequency F The second condition for paralleling two electrical systems is that their frequencies are nearly equal This can be controlled by the generator s speed governor www eaton com 641 Line VA Bu...

Page 642: ...cy fBus is not equal to the mains frequency fLine it results in a slip frequency F fBus fLine between the two system frequencies Voltage Curve with Enlarged Resolution www eaton com 642 t v t t v t v...

Page 643: ...ght frequency difference is accepted In such cases the angular difference is not constant but changes with the slip frequency F By taking the breaker closing time into consideration a lead of the clos...

Page 644: ...late the moment of synchronization and gives the paralleling release When paralleling two systems it has to be verified that the system to system mode is selected Paralleling two systems in generator...

Page 645: ...nced Close Angle Calculator Bkr Open LBDL Active DBLL Active Main VT con Ext Blocked DBDL Active Bkr Open LBDL DBLL DBDL Bypass override Sync override LB DB LBLL LL DL Sync SynchronRunTiming Sync Sync...

Page 646: ...the breaker closing time into account The sync check element measures the three phase to neutral voltages VA VB and VC or the three phase to phase voltages VAB VBC and VCA of the station voltage bus b...

Page 647: ...D Line VX LBDL Active DBLL Active Main VT con Ext Blocked DBDL Active LBDL DBLL DBDL Bypass override Sync override LB DB LBLL LL DL Sync SyncOverridden Sync VDiffTooHigh Sync In Sync Allowed Sync Slip...

Page 648: ...eck function LBDL Live Bus Dead Line DBLL Dead Bus Live Line DBDL Dead Bus Dead Line Also the sync check function can be bypassed by an external source When the sync check function is overridden or by...

Page 649: ...ara Sync check ExBlo2 External blocking of the module if blocking is activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global...

Page 650: ...ng generator to system breaker close initiate needed SYSTEM2SYSTEM SynchronCheck between two systems Stand Alone no breaker info needed System2System Generator2System System2System Protection Para 1 4...

Page 651: ...ine voltage phasors Delta V for synchronizm Related to bus voltage secondary rating 0 01 1 00Vn 0 24Vn Protection Para 1 4 Sync check Conditions MaxSlipFrequency Maximum frequency difference Slip Delt...

Page 652: ...Signal External Blocking LiveBus Signal Live Bus flag 1 Live Bus 0 Voltage is below the LiveBus threshold LiveLine Signal Live Line flag 1 Live Line 0 Voltage is below the LiveLine threshold Synchron...

Page 653: ...difference Operation Measured Values Sync check f Bus Bus frequency Operation Measured Values Sync check f Line Line frequency Operation Measured Values Sync check V Bus Bus Voltage Operation Measure...

Page 654: ...I 8 X6 DI 3 Signal Digital Input DI 8 X6 DI 4 Signal Digital Input DI 8 X6 DI 5 Signal Digital Input DI 8 X6 DI 6 Signal Digital Input DI 8 X6 DI 7 Signal Digital Input DI 8 X6 DI 8 Signal Digital Inp...

Page 655: ...d Signal Negated Latched Output Q NOT Logic LE9 Gate Out Signal Output of the logic gate Logic LE9 Timer Out Signal Timer Output Logic LE9 Out Signal Latched Output Q Logic LE9 Out inverted Signal Neg...

Page 656: ...ate Out Signal Output of the logic gate Logic LE18 Timer Out Signal Timer Output Logic LE18 Out Signal Latched Output Q Logic LE18 Out inverted Signal Negated Latched Output Q NOT Logic LE19 Gate Out...

Page 657: ...LE27 Timer Out Signal Timer Output Logic LE27 Out Signal Latched Output Q Logic LE27 Out inverted Signal Negated Latched Output Q NOT Logic LE28 Gate Out Signal Output of the logic gate Logic LE28 Tim...

Page 658: ...LE36 Out Signal Latched Output Q Logic LE36 Out inverted Signal Negated Latched Output Q NOT Logic LE37 Gate Out Signal Output of the logic gate Logic LE37 Timer Out Signal Timer Output Logic LE37 Ou...

Page 659: ...nverted Signal Negated Latched Output Q NOT Logic LE46 Gate Out Signal Output of the logic gate Logic LE46 Timer Out Signal Timer Output Logic LE46 Out Signal Latched Output Q Logic LE46 Out inverted...

Page 660: ...ate Out Signal Output of the logic gate Logic LE55 Timer Out Signal Timer Output Logic LE55 Out Signal Latched Output Q Logic LE55 Out inverted Signal Negated Latched Output Q NOT Logic LE56 Gate Out...

Page 661: ...LE64 Timer Out Signal Timer Output Logic LE64 Out Signal Latched Output Q Logic LE64 Out inverted Signal Negated Latched Output Q NOT Logic LE65 Gate Out Signal Output of the logic gate Logic LE65 Tim...

Page 662: ...LE73 Out Signal Latched Output Q Logic LE73 Out inverted Signal Negated Latched Output Q NOT Logic LE74 Gate Out Signal Output of the logic gate Logic LE74 Timer Out Signal Timer Output Logic LE74 Ou...

Page 663: ...Logic LE79 Timer Out Signal Timer Output Logic LE79 Out Signal Latched Output Q Logic LE79 Out inverted Signal Negated Latched Output Q NOT Logic LE80 Gate Out Signal Output of the logic gate Logic LE...

Page 664: ...t is defined by the ratio of negative sequence voltage to positive sequence voltage Unbalance V2 V1 or V2 V1 for ABC rotation and V1 V2 for ACB rotation The device will automatically select the correc...

Page 665: ...gs NPS Filter VA Name Pickup Please Refer to Diagram Trip Blockings 47 1 n Element is not deactivated and no active blocking signals Tripping command deactivated or blocked VC VB V2 PPS Filter V1 Name...

Page 666: ...meter set and if the state of the assigned signal is true 1 1 n Assignment List Protection Para Global Prot Para Unbalance Prot 47 1 ExBlo2 External blocking of the module if blocking is activated all...

Page 667: ...d to the corresponding global protection parameter If the signal becomes true those modules elements are blocked that are parameterized ExBlo TripCmd Fc active Inactive Active Inactive Protection Para...

Page 668: ...1 I Module Input State External Blocking1 Protection Para Global Prot Para Unbalance Prot 47 1 ExBlo2 I Module Input State External Blocking2 Protection Para Global Prot Para Unbalance Prot 47 1 ExBlo...

Page 669: ...s the same as that for the balanced nominal voltages fed to the relay it implies that the phase sequence of the voltages seen by the relay is reversed Now turn off phase A Again check the measuring va...

Page 670: ...in V2 V1 100 so the first condition V2 V1 2 is always fulfilled Now increase the phase A voltage until the relay is activated Testing the dropout ratio of the threshold values Having tripped the relay...

Page 671: ...e previous test now decrease the phase A voltage The dropout of V2 V1 has to be 1 below the V2 V1 setting Successful test result The measured trip delays threshold values and dropout ratios are within...

Page 672: ...no longer measurable this phase will be excluded from the calculation of the average value The measuring principle of the frequency supervision is based in general on the time measurement of complete...

Page 673: ...Underfrequency This protection element provides a pickup threshold and a tripping delay If the frequency falls below the set pickup threshold an alarm will be issued instantaneously If the frequency r...

Page 674: ...Planning 81U or 81O the evaluated phase voltages are compared to the set pickup threshold for over or under frequency If in any of the phases the frequency exceeds or falls below the set pickup thresh...

Page 675: ...gs 81 1 n 81U Under Or 81O Over Element is not deactivated and no active blocking signals Tripping comm and deactivated or blocked VC VB Name 81 1 n Name Blo by V Name f 81O Over 81U Under 81U Under 8...

Page 676: ...of change of frequency df dt may have a negative or positive sign depending on frequency increase positive sign or decrease negative sign In the frequency parameter sets the User can define the kind o...

Page 677: ...kings Please Refer to Diagram Trip Blockings Element is not deactivated and no active blocking signals Tripping command deactivated or blocked Positive df dt Negative df dt Absolute df dt Name Pickup...

Page 678: ...ent df dt and a tripping delay can be set Whereby Positive df dt the frequency element detects an increase in frequency Negative df dt the frequency element detects a decrease in frequency and Absolut...

Page 679: ...Refer to Diagram Blockings Please Refer to Diagram Trip Blockings Element is not deactivated and no active blocking signals Tripping command deactivated or blocked f Positive df dt Negative df dt Abs...

Page 680: ...evaluated phase voltages are compared to the set frequency pickup threshold and the set frequency decrease or increase threshold DF If in any of the phases the frequency exceeds or falls below the se...

Page 681: ...iagram Trip Blockings Tripping command deactivated or blocked Please Refer to Diagram Blockings Elem ent is not deactivated and no active blocking signals 81 1 n 81UDR Under DF DT Or 81ODR Over DF DT...

Page 682: ...EDR 5000 IM02602007E www eaton com 682 fN f 81U Under DT DT Reset DF DF DF Temporarily Blocking t t1 t2 t3 t4 t6 Trip 81 1 n 81UDR Under DF DT Name 81 1 n t5...

Page 683: ...relays detect a fault only when short circuit type currents exist but cannot avoid their development Power relays are able to pickup within 200 ms but they also cannot prevent the power from rising to...

Page 684: ...at mains parallel operation The rotor displacement angle between stator and rotor is dependent on the mechanical moving torque of the generator shaft The mechanical shaft power is balanced with the el...

Page 685: ...or auto reclosing the generator suddenly feeds a very high load The rotor displacement angle is decreased repeatedly and the voltage vector V1 changes its direction V1 Voltage vectors at mains failur...

Page 686: ...n one of the phases the vector surge exceeds the set threshold and if there are no blocking commands for the frequency element an alarm and a trip command is issued instantaneously Tripping of the vec...

Page 687: ...agram Trip Blockings Element is not deactivated and no active blocking signals Tripping command deactivated or blocked Name Pickup Name Trip 78V vector surge Device Planning Name Mode 78V vector surge...

Page 688: ...ath ExBlo1 External blocking of the module if blocking is activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para...

Page 689: ...1 1 ExBlo TripCmd Fc Activate allow or inactivate disallow blocking of the module element This parameter is only effective if a signal is assigned to the corresponding global protection parameter If t...

Page 690: ...0 0 10 0Hz 1 00Hz Protection Para 1 4 Freq Prot 81 1 DT Time interval of the maximum admissable rate of frequency change Only available if Device Planning 81 Mode 81UDR Under DF DT Or 81ODR Over DF DT...

Page 691: ...ctive Signal Active ExBlo Signal External Blocking Blo by V Signal Module is blocked by undervoltage Blo TripCmd Signal Trip Command blocked ExBlo TripCmd Signal External Blocking of the Trip Command...

Page 692: ...quantity to less than 99 95 of the trip value or 0 05 fn The relay must only fall back at 99 95 of the trip value at the earliest or 0 05 fn Successful test result Permissible deviations tolerances c...

Page 693: ...ate of change of frequency until the respective element is activated and Note the value Testing the trip delay Set the test voltage to nominal frequency Now apply a step change sudden change that is 1...

Page 694: ...test result Permissible deviations tolerances and dropout ratios can be taken from the Technical Data Commissioning 81O and Rate of Change f and df dt Object to be tested All frequency protection stag...

Page 695: ...test result Permissible deviations tolerances and dropout ratios can be taken from the Technical Data Commissioning 81O R Overfrequency and DF DT Object to be tested All frequency protection stages th...

Page 696: ...e source that can generate a definite step sudden change of the voltage pointers phase shift Procedure Testing the threshold values Apply a vector surge sudden change that is 1 5 times the setting val...

Page 697: ...rse Power Pr and Under Reverse Power Pr Each element consists of a Pickup and a Delay setting These elements are based on rated apparent power VAn Definition for VAn is as follows VAn SQRT 3 VT second...

Page 698: ...EDR 5000 IM02602007E 32 Forward Power Over and Under www eaton com 698 Q P Trip Region Pickup P Q P Trip Region Pickup P No Trip No Trip...

Page 699: ...EDR 5000 IM02602007E 32 Reverse Power Over and Under www eaton com 699 Q P Trip Region Pickup Pr Q P Trip Region Pickup Pr No Trip No Trip...

Page 700: ...signals Tripping command deactivated or blocked Name 32 1 n Name Pickup Name Trip 2 3 Name TripCmd 15a 14 Pickup P Pickup P Device Planning Pickup Pr Pickup Pr Name Mode Pickup P Pickup P Pickup Pr P...

Page 701: ...activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para Power Prot 32 1 ExBlo2 External blocking of the module if...

Page 702: ...pCmd Fc Activate allow or inactivate disallow blocking of the module element This parameter is only effective if a signal is assigned to the corresponding global protection parameter If the signal bec...

Page 703: ...nning PQS Mode Pickup Pr 0 003 10 000VAn 0 020VAn Protection Para 1 4 Power Prot 32 1 Pickup Pr Under Reverse Definition for Sn is as follows Sn 1 7321 VT rating CT rating The voltage is the line to l...

Page 704: ...nal Description Active Signal Active ExBlo Signal External Blocking Blo TripCmd Signal Trip Command blocked ExBlo TripCmd Signal External Blocking of the Trip Command Pickup Signal Pickup Power Protec...

Page 705: ...arried out with the tripping values and tripping delays that apply to the User s switchboard If the User is testing greater than thresholds e g P start at 80 of the tripping value and increase the obj...

Page 706: ...y Example Threshold 1 1 Pn Feed rated voltage and 0 9 times rated current in phase to the measuring inputs of the relay PF 1 The measured values for the active power P must show a positive algebraic s...

Page 707: ...xample Threshold 0 3 Pn Feed rated voltage and 0 5 times rated current in phase to the measuring inputs of the relay PF 1 The measured values for the active power P must show a positive algebraic sign...

Page 708: ...ay Example Threshold 1 1 Pn Feed rated voltage and 0 9 times rated current with 180 degree phase shift between voltage and current pointers to the measuring inputs of the relay The measured values for...

Page 709: ...ay Example Threshold 0 3 Pn Feed rated voltage and 0 5 times rated current with 180 degree phase shift between voltage and current pointers to the measuring inputs of the relay The measured values for...

Page 710: ...Q Over Reverse Reactive Power Qr and Under Reverse Reactive Power Qr Each element consists of a Pickup and a Delay setting These elements are based on rated apparent power Van Definition for VAn is a...

Page 711: ...EDR 5000 IM02602007E 32V Forward Reactive Power Over and Under www eaton com 711 Q P P Q Trip Region No Trip Trip Region No Trip Pickup Q Pickup Q...

Page 712: ...EDR 5000 IM02602007E 32V Reverse Reactive Power Over and Under www eaton com 712 Q P Trip Region No Trip Pickup Qr Q P Trip Region No Trip Pickup Qr...

Page 713: ...signals Tripping command deactivated or blocked Name 32V 1 n Name Pickup Name Trip 2 3 Name TripCmd 15a 14 Pickup Q Pickup Q Device Planning Pickup Qr Pickup Qr Name Mode Pickup Q Pickup Q Pickup Qr P...

Page 714: ...ocking is activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para Power Prot 32V 1 ExBlo2 External blocking of the...

Page 715: ...isallow blocking of the module element This parameter is only effective if a signal is assigned to the corresponding global protection parameter If the signal becomes true those modules elements are b...

Page 716: ...on Para 1 4 Power Prot 32V 1 Pickup Qr Overload Reverse Reactive Power Pickup Value Definition for Sn is as follows Sn 1 7321 VT rating CT rating The voltage is the line to line voltage Only available...

Page 717: ...r Prot 32V 1 ExBlo TripCmd I Module Input State External Blocking of the Trip Command Protection Para Global Prot Para Power Prot 32V 1 Signals of the Reactive Power Protection Module States of the Ou...

Page 718: ...carried out with the tripping values and tripping delays that apply to the User s switchboard If the User is testing greater than thresholds e g Q start at 80 of the tripping value and increase the ob...

Page 719: ...ay Example Threshold 1 1 Qn Feed rated voltage and 0 9 times rated current 90 degree phase shift to the measuring inputs of the relay PF 0 The measured values for the active power Q must show a positi...

Page 720: ...y Example Threshold 0 3 Qn Feed rated voltage and 0 5 times rated current 90 degree phase shift to the measuring inputs of the relay PF 0 The measured values for the active power Q must show a positiv...

Page 721: ...ay Example Threshold 1 1 Qn Feed rated voltage and 0 9 times rated current with 90 degree phase shift between voltage and current pointers to the measuring inputs of the relay The measured values for...

Page 722: ...ay Example Threshold 0 3 Qn Feed rated voltage and 0 5 times rated current with 90 degree phase shift between voltage and current pointers to the measuring inputs of the relay The measured values for...

Page 723: ...Watt VA Definition Displacement Power Factor 55D Fundamental The Displacement Power Factor is computed by dividing the fundamental watts by the fundamental volt amperes as shown below This definition...

Page 724: ...o the source Active Power flows into the source Reactive Power flows into the load Quadrant1 Quadrant2 Quadrant3 Quadrant4 P Watts Q Vars PF P Watts Q Vars PF P Watts Q Vars PF P Watts Q Vars PF Rever...

Page 725: ...V Reset PF 0 9 Res Mode I lags V Trigger PF 0 5 Trig Mode I leads V Reset PF 0 9 Res Mode I leads V Trigger PF 0 5 Trig Mode I lags V Reset PF 0 9 Res Mode I leads V Quadrant2 Quadrant1 Quadrant3 Qua...

Page 726: ...ocking signals Tripping command deactivated or blocked Name PF 1 n Name Pickup 2 3 Name TripCmd 14 20 Vn 0 5 In Imax V PF RMS Name Impossible Name Compensator Pickup Delay And Release Delay PF 1 n OR...

Page 727: ...blocking signals Tripping command deactivated or blocked Name PF 1 n Name Pickup 2 3 Name TripCmd 14 20 Vn 0 5 In Imax V PF Fund Name Impossible Name Compensator Pickup Delay And Release Delay PF 1 n...

Page 728: ...ned signal is true 1 n Assignment List Protection Para Global Prot Para Power Factor Prot PF 55D 1 ExBlo2 External blocking of the module if blocking is activated allowed within a parameter set and if...

Page 729: ...g of the module element This parameter is only effective if a signal is assigned to the corresponding global protection parameter If the signal becomes true those modules elements are blocked that are...

Page 730: ...300 00s 5 00s Protection Para 1 4 Power Factor Prot PF 55D 1 t Reset Comp Reset Post trigger time of the Compensation Signal When this timer is elapsed the compensation signal will be deactivated 0 0...

Page 731: ...Signal External Blocking Blo TripCmd Signal Trip Command blocked ExBlo TripCmd Signal External Blocking of the Trip Command Pickup Signal Pickup Power Factor Trip Signal Trip Power Factor TripCmd Sig...

Page 732: ...braic sign check the wiring In this example the PF Trigger is set to 0 86 30 lagging and the PF Reset is set to 0 86 30 leading Carry out the test with the settings trigger and reset that fit the swit...

Page 733: ...nt pointer lagging with an abrupt change to PF 0 707 45 lagging Measure the tripping delay at the output of the relay Compare the measured tripping time to the selected trip time Successful test resul...

Page 734: ...below a certain value This protection is an upstream system protection The Q V protection module with decoupling and auto reconnection function is implemented as an autonomous protection element acco...

Page 735: ...the QV Protection module Protective devices that use the load flow arrow like the EDR 5000 or the ETR 5000 are to be set to Power Trip dir positive Protective devices that are working on the base of...

Page 736: ...00 IM02602007E Trip Direction of the QV Protection www eaton com 736 P Q P Q P Q Grid G G Power Trip dir positive t2 QV 1 5 s t1 QV 0 5s P Q Grid G Power Trip dir negative P Q t1 QV 0 5s EGR 5 000 E D...

Page 737: ...0 5 seconds by the QV protection if all three line to line voltages at the point of common coupling are less than 0 85 times Vn logical AND connected and if the energy resource consumes at the same t...

Page 738: ...EDR 5000 IM02602007E Method 1 Power Angle Supervision www eaton com 738 0 5 Phi Power Grid P Grid P 0 5 Q 1 S P 1 S Phi Power I1 min QV...

Page 739: ...EDR 5000 IM02602007E Method 2 Pure Reactive Power Supervision www eaton com 739 0 5 Grid P Grid P 0 5 Q 1 S P 1 S Q min QV Trigger for the Reactive Power Positive Phase Sequence System...

Page 740: ...t setting 0 05 Sn Optionally select a suitable minimum current I min QV Default setting 0 1 In to prevent false tripping Two timer elements are available t1 QV and t2 QV Both timer elements will be st...

Page 741: ...active I1 Release Power Angle Supervision Pure Reactive Po wer Superv QV Method 2 VL12 VL23 VL31 Q V Q V Decoupling Distributed Generator Q V Decoupling PCC Q V Alarm Q V Reactive Power Thres Q V Powe...

Page 742: ...a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para Q V ExBlo2 External blocking of the module if blocking is activated allowed within...

Page 743: ...cuit e g caused by a fuse failure Inactive Active Inactive Protection Para 1 4 Q V General Settings QV Method Selection of the Q V Method Power Angle or Reactive Power Threshold Power Angle Super visi...

Page 744: ...al will be issued to the local energy resource 0 00 2 00s 0 5s Protection Para 1 4 Q V Decoupling t2 QV Second timer If this timer is elapsed the an trip signal will be issued to the PCC Point of Comm...

Page 745: ...Pickup Reactive Power Undervoltage Protection Decoupling Distributed Generator Signal Decoupling of the local Energy Generator Resource Decoupling PCC Signal Decoupling at the Point of Common Coupling...

Page 746: ...Before connecting different electrical networks synchronism has to be secured After decoupling by the Q V module or other decoupling functions like V V V f the reconnection release signal for reconnec...

Page 747: ...PCC Digital Input 0 Delay Timer t Release B lo Inactive Active PCC Fuse Fail VT AND PCC Fuse Fail VT Digital Input AND VLL Release AND VAB VBC VCA VLL Release AND VAB VBC VCA A ND 1 OR ReCon Mains de...

Page 748: ...ed e g signal via digital input Additionally the parameter Reclosure Release Cond in the menu Protection Para Set x ReCon Release Para Reconnect Release Cond has to be set to V Ext Release PCC Also th...

Page 749: ...sufficiently For this a corresponding remote signal has to be available Set the parameter Reclosure Release Cond in the menu Protection Para Set x ReCon Release Para to V Ext Release PCC The required...

Page 750: ...after 10 minutes A re connection of the DER is only permitted when the mains voltage is 95 of Vn and the frequency is in the range of 47 5 Hz to 50 05 Hz Set the blocking signals in the menu Global P...

Page 751: ...a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para ReCon General Settings V Ext Release PCC Release Signal by the Point of Common Cou...

Page 752: ...t triggers the reclosure Decoupling Functions Protection Para Global Prot Para ReCon Decoupling Decoupling6 Decoupling signal that triggers the reclosure Decoupling Functions Protection Para Global Pr...

Page 753: ...Trip Command 46 2 TripCmd Signal Trip Command 47 1 TripCmd Signal Trip Command 47 2 TripCmd Signal Trip Command 81 1 TripCmd Signal Trip Command 81 2 TripCmd Signal Trip Command 81 3 TripCmd Signal Tr...

Page 754: ...t DNP This corresponds to a virtual binary input of the protective device DNP BinaryOutput3 Virtual Digital Output DNP This corresponds to a virtual binary input of the protective device DNP BinaryOut...

Page 755: ...tual binary input of the protective device DNP BinaryOutput26 Virtual Digital Output DNP This corresponds to a virtual binary input of the protective device DNP BinaryOutput27 Virtual Digital Output D...

Page 756: ...irtual Input IEC61850 GGIO Ind IEC61850 VirtInp23 Signal Virtual Input IEC61850 GGIO Ind IEC61850 VirtInp24 Signal Virtual Input IEC61850 GGIO Ind IEC61850 VirtInp25 Signal Virtual Input IEC61850 GGIO...

Page 757: ...tem Single Point Controllable Status Output IEC61850 SPCSO14 Status bit that can be set by clients like e g the Master Communication System Single Point Controllable Status Output IEC61850 SPCSO15 Sta...

Page 758: ...nverted Signal Negated Latched Output Q NOT Logic LE6 Gate Out Signal Output of the logic gate Logic LE6 Timer Out Signal Timer Output Logic LE6 Out Signal Latched Output Q Logic LE6 Out inverted Sign...

Page 759: ...ate Out Signal Output of the logic gate Logic LE15 Timer Out Signal Timer Output Logic LE15 Out Signal Latched Output Q Logic LE15 Out inverted Signal Negated Latched Output Q NOT Logic LE16 Gate Out...

Page 760: ...LE24 Timer Out Signal Timer Output Logic LE24 Out Signal Latched Output Q Logic LE24 Out inverted Signal Negated Latched Output Q NOT Logic LE25 Gate Out Signal Output of the logic gate Logic LE25 Tim...

Page 761: ...LE33 Out Signal Latched Output Q Logic LE33 Out inverted Signal Negated Latched Output Q NOT Logic LE34 Gate Out Signal Output of the logic gate Logic LE34 Timer Out Signal Timer Output Logic LE34 Ou...

Page 762: ...nverted Signal Negated Latched Output Q NOT Logic LE43 Gate Out Signal Output of the logic gate Logic LE43 Timer Out Signal Timer Output Logic LE43 Out Signal Latched Output Q Logic LE43 Out inverted...

Page 763: ...ate Out Signal Output of the logic gate Logic LE52 Timer Out Signal Timer Output Logic LE52 Out Signal Latched Output Q Logic LE52 Out inverted Signal Negated Latched Output Q NOT Logic LE53 Gate Out...

Page 764: ...LE61 Timer Out Signal Timer Output Logic LE61 Out Signal Latched Output Q Logic LE61 Out inverted Signal Negated Latched Output Q NOT Logic LE62 Gate Out Signal Output of the logic gate Logic LE62 Tim...

Page 765: ...LE70 Out Signal Latched Output Q Logic LE70 Out inverted Signal Negated Latched Output Q NOT Logic LE71 Gate Out Signal Output of the logic gate Logic LE71 Timer Out Signal Timer Output Logic LE71 Ou...

Page 766: ...nverted Signal Negated Latched Output Q NOT Logic LE78 Gate Out Signal Output of the logic gate Logic LE78 Timer Out Signal Timer Output Logic LE78 Out Signal Latched Output Q Logic LE78 Out inverted...

Page 767: ...ive Inactive Protection Para 1 4 ReCon General Settings V Ext Release PCC Fc Activate the release signal of the Point of Common Coupling The line to line voltage is greater than 95 of VN Inactive Acti...

Page 768: ...Protection Para 1 4 ReCon Release Para f Upper freqeuncy limit for the reclosure 40 00 69 90Hz 50 05Hz Protection Para 1 4 ReCon Release Para t Release Blo Time stage delay for the reclosure of the en...

Page 769: ...ings PCC Fuse Fail VT I State of the module input Blocking if the fuse of a voltage transformer has tripped at the PCC Protection Para Global Prot Para ReCon General Settings reconnected I This signal...

Page 770: ...otection Para Global Prot Para ReCon Decoupling Decoupling6 I Decoupling signal that triggers the reclosure Protection Para Global Prot Para ReCon Decoupling Reconnection Module Signals Output States...

Page 771: ...apability was decoupled from the electrical power system The consequence was a dangerous system voltage and frequency instability Based on experiences like that lots of electric utilities and state pu...

Page 772: ...the LVRT borderline In other words a LVRT protection function is a time dependent voltage supervision according to a predefined voltage profile The time dependent voltage supervision will be started...

Page 773: ...disconnected from the electrical power system immediately for a permanent fault This kind of applications can be realized easily using the feature of AR controlled LVRT in LVRT protection function Fi...

Page 774: ...AR runtime In addition to that the number of permitted LVRTs has to be set which is usually the number of auto reclosure attempts The actual LVRT supervision will be controlled to ride through the pr...

Page 775: ...ive Name LVRT 1 n Device Planning Tripping com mand deactivated or blocked 2 3 15a 14 28 29 30 VA VB VC Name Vstart Fundamental True RMS Name Criterion Phase to Ground Name Measuring Mode Phase to Pha...

Page 776: ...blocked that are parameterized ExBlo Fc active Inactive Active Inactive Protection Para 1 4 LVRT 1 General Settings Blo TripCmd Permanent blocking of the Trip Command of the module element Inactive Ac...

Page 777: ...active Protection Para 1 4 LVRT 1 General Settings Number of LVRT Number of LVRT events after that a disconnection of DR is allowed Only available if AR controlled LVRT Active 1 6 1 Protection Para 1...

Page 778: ...file 0 00 20 00s 0 15s Protection Para 1 4 LVRT 1 LVRT Profile V t3 Voltage value of a point V t n These points define the LVRT profile 0 00 1 30Vn 0 70Vn Protection Para 1 4 LVRT 1 LVRT Profile t3 Po...

Page 779: ...30Vn 0 90Vn Protection Para 1 4 LVRT 1 LVRT Profile t7 Point in time for the corresponding voltage value V t n These points define the LVRT profile 0 00 20 00s 3 00s Protection Para 1 4 LVRT 1 LVRT Pr...

Page 780: ...alue of a point V t n These points define the LVRT profile 0 00 1 30Vn 0 90Vn Protection Para 1 4 LVRT 1 LVRT Profile t10 Point in time for the corresponding voltage value V t n These points define th...

Page 781: ...etpoints can be set to the same values as the last set point Set points should be selected in a manner of left to right with time begin at t 0 tk 1 tk The voltage setpoints must be selected in a ascen...

Page 782: ...e 1 n Assignment List Protection Para Global Prot Para LVRT 1 ExBlo TripCmd External blocking of the Trip Command of the module the element if blocking is activated allowed within a parameter set and...

Page 783: ...Pickup Phase C Pickup Signal Pickup Voltage Element Trip Signal Trip TripCmd Signal Trip Command t LVRT is running Signal t LVRT is running Counter Values of the Low Voltage Ride Through Value Descri...

Page 784: ...Erzeugungsanlagen am Mittelspannungsnetz Richtlinie f r Anschluss und Parallelbetrieb von Erzeugungsanlagen am Mittelspannungsnetz Juni 2008 BDEW Berlin 2 IEEE Std 1547 2003 IEEE Standard for Intercon...

Page 785: ...ssical load shedding the Under Frequency Load Shedding will shed only those sub grids that decrease the frequency because they consume active power A shedding of sub grids that have a positive influen...

Page 786: ...Excamples Classical centralized load shedding Classical load shedding of a sub grid from a central connection point The load shedding will be initiated by under frequency www eaton com 786 Grid f 81U...

Page 787: ...hedding can be done by deactivating the power flow direction detection By means of alternating rotation the the sub grids to be shed a non discriminating load shedding of consumers can be established...

Page 788: ...rection detection if activated will block the shedding of sub grids in case of an under frequency situation of those sub grids that stabilize the frequency The sub grid will be shed only if it decreas...

Page 789: ...rection detection if activated will block the shedding of sub grids in case of an under frequency situation of those sub grids that stabilize the frequency Individual consumers that destabilize the fr...

Page 790: ...ant power supply There is no need to use the Under Frequency Load Shedding because on average the sub grid feeds produces more active power than it consumes The sub grid has over all a positive impact...

Page 791: ...ant power supply There is no need to use the Under Frequency Load Shedding because on average the sub grid feeds produces more active power than it consumes The sub grid has over all a positive impact...

Page 792: ...em produced power is to be counted positive greater than zero By means of the parameter P Block dir a sign reversal can be applied to the active power within the UFLS module Protective devices that us...

Page 793: ...eral Settings Call up menu Protection Para Global Prot Para UFLS Within this menu you can Assign signals that activate adaptive parameters Assign a signal that blocks the evaluation of the active powe...

Page 794: ...variant Power Angle Supervision please see section Method 1 2nd variant Pure Active Power Supervision please see section Method 2 3rd variant External please see section Method 4 Method 1 Power Angle...

Page 795: ...5 This diagram shows the blocking area within the generator arrow flow system Method 3 classical load shedding without taking into account the active power flow direction The load shedding will be ini...

Page 796: ...e active power flow direction should not be taken into account Method 3 classical load shedding Set the parameter UFLS method No Pdir Ex Pdir When the active power flow direction indicated by an exter...

Page 797: ...on by an activation signal without switching to another parameter set Assign the signals that should activate the corresponding adaptive parameters within the Global Parameters Protection Para Global...

Page 798: ...ctionallity When this feature is set and active the functionallity of the module turns into conventional only frequency based load shedding 1 n Assignment List Protection Para Global Prot Para UFLS P...

Page 799: ...In this case the module will be blocked if a measuring circuit supervision module e g LOP VTS signals a disturbed measuring circuit e g caused by a fuse failure Inactive Active Inactive Protection Par...

Page 800: ...5 Protection Para 1 4 UFLS LoadShedding P min Minimum Value threshold for the Active Power Only available if UFLS Method Pure Active Power Superv 0 01 0 10VAn 0 05VAn Protection Para 1 4 UFLS LoadShe...

Page 801: ...is set and active the functionallity of the module turns into conventional only frequency based load shedding Protection Para Global Prot Para UFLS AdaptSet1 I Module Input State Adaptive Parameter1 P...

Page 802: ...er Phi Power Positive Phase Sequence System P min Signal Minimum Value threshold for the Active Power P Blo Loadshedding Signal Load shedding blocked based on evaluation of active power f Signal Under...

Page 803: ...ructured By means of these elements the protective device can detect and execute pickups and trips that are issued by other external devices This can be helpful for logging purposes if the other devic...

Page 804: ...AND AND Name Trip Name Alarm Please Refer to Diagram Blockings Please Refer to Diagram Trip Blockings Element is not deactivated and no active blocking signals Tripping command deactivated or blocked...

Page 805: ...ExBlo2 External blocking of the module if blocking is activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para ExP...

Page 806: ...nal becomes true those modules elements are blocked that are parameterized ExBlo Fc active Inactive Active Inactive Protection Para 1 4 ExP ExP 1 Blo TripCmd Permanent blocking of the Trip Command of...

Page 807: ...cking of the Trip Command Protection Para Global Prot Para ExP ExP 1 Alarm I Module Input State Alarm Protection Para Global Prot Para ExP ExP 1 Trip I Module Input State Trip Protection Para Global P...

Page 808: ...sary means Dependent on the application Procedure Simulate the functionality of the External Protection pickup trip and blockings by de energizing the digital inputs Successful test result All externa...

Page 809: ...his trip signal is to be used to trip the upstream breaker backup Stopping the BF The timer will be stopped if the opening of the breaker is detected Depending on the supervision scheme the timer will...

Page 810: ...dged at the HMI Note on devices that offer Wide Frequency Range measurement The supervision scheme 50BF will be blocked as soon as the frequency differs more than 5 from the nominal frequency As long...

Page 811: ...rotective relays This scheme is recommended if Breaker Failures have to be detected while there is no or not much load flow small currents This might e g be the case if overvoltage or overfrequency is...

Page 812: ...User can also select none e g if the User intends to use one of the three additional assignable trigger inputs Those trips can exclusively start the breaker failures that are assigned within the trip...

Page 813: ...the BF module is within the stand by state Who stops the BF Timer Once the timer has been stopped the BF module will switch into the state Rejected The module will switch back into the state Stand by...

Page 814: ...r the threshold the longer the time that is needed to detect that the breaker is in the open position especially if there are transients harmonics Note Tripping delay of the BF module Minimum delay ti...

Page 815: ...ger3 1 n Assignment List BF Trigger2 1 n Assignment List BF Trigger1 BF Name BF Please Refer to Diagram Blockings Element is not deactivated and no active blocking signals 2 11 15 15 IA IB IC BF Locko...

Page 816: ...n Assignment List BF Trigger2 1 n Assignment List BF Trigger1 BF Name BF Please Refer to Diagram Blockings Element is not deactivated and no active blocking signals 2 11 15 BF Lockout Res Lockout BF P...

Page 817: ...signal is true 1 n Assignment List Protection Para Global Prot Para Supervision BF ExBlo2 External blocking of the module if blocking is activated allowed within a parameter set and if the state of t...

Page 818: ...u path Trigger3 Trigger that will start the BF Trigger Protection Para Global Prot Para Supervision BF Direct Commands of the BF Parameter Description Setting range Default Menu path Res Lockout Reset...

Page 819: ...n Para 1 4 Supervision BF ExBlo Fc Activate allow or inactivate disallow blocking of the module element This parameter is only effective if a signal is assigned to the corresponding global protection...

Page 820: ...Para Global Prot Para Supervision BF Trigger2 I Module Input Trigger that will start the BF Protection Para Global Prot Para Supervision BF Trigger3 I Module Input Trigger that will start the BF Prote...

Page 821: ...2 TripCmd Signal Trip Command 51R 1 TripCmd Signal Trip Command 51R 2 TripCmd Signal Trip Command 27M 1 TripCmd Signal Trip Command 27M 2 TripCmd Signal Trip Command 59M 1 TripCmd Signal Trip Command...

Page 822: ...Decoupling of the local Energy Generator Resource UFLS Trip Signal Signal Trip ZI TripCmd Signal Zone Interlocking Trip Command ExP 1 TripCmd Signal Trip Command ExP 2 TripCmd Signal Trip Command ExP...

Page 823: ...nal Negated Latched Output Q NOT Logic LE5 Gate Out Signal Output of the logic gate Logic LE5 Timer Out Signal Timer Output Logic LE5 Out Signal Latched Output Q Logic LE5 Out inverted Signal Negated...

Page 824: ...ate Out Signal Output of the logic gate Logic LE14 Timer Out Signal Timer Output Logic LE14 Out Signal Latched Output Q Logic LE14 Out inverted Signal Negated Latched Output Q NOT Logic LE15 Gate Out...

Page 825: ...LE23 Timer Out Signal Timer Output Logic LE23 Out Signal Latched Output Q Logic LE23 Out inverted Signal Negated Latched Output Q NOT Logic LE24 Gate Out Signal Output of the logic gate Logic LE24 Tim...

Page 826: ...LE32 Out Signal Latched Output Q Logic LE32 Out inverted Signal Negated Latched Output Q NOT Logic LE33 Gate Out Signal Output of the logic gate Logic LE33 Timer Out Signal Timer Output Logic LE33 Ou...

Page 827: ...nverted Signal Negated Latched Output Q NOT Logic LE42 Gate Out Signal Output of the logic gate Logic LE42 Timer Out Signal Timer Output Logic LE42 Out Signal Latched Output Q Logic LE42 Out inverted...

Page 828: ...ate Out Signal Output of the logic gate Logic LE51 Timer Out Signal Timer Output Logic LE51 Out Signal Latched Output Q Logic LE51 Out inverted Signal Negated Latched Output Q NOT Logic LE52 Gate Out...

Page 829: ...LE60 Timer Out Signal Timer Output Logic LE60 Out Signal Latched Output Q Logic LE60 Out inverted Signal Negated Latched Output Q NOT Logic LE61 Gate Out Signal Output of the logic gate Logic LE61 Tim...

Page 830: ...LE69 Out Signal Latched Output Q Logic LE69 Out inverted Signal Negated Latched Output Q NOT Logic LE70 Gate Out Signal Output of the logic gate Logic LE70 Timer Out Signal Timer Output Logic LE70 Ou...

Page 831: ...Logic LE77 Timer Out Signal Timer Output Logic LE77 Out Signal Latched Output Q Logic LE77 Out inverted Signal Negated Latched Output Q NOT Logic LE78 Gate Out Signal Output of the logic gate Logic LE...

Page 832: ...Trip Command 51X 1 TripCmd Signal Trip Command 51X 2 TripCmd Signal Trip Command 50R 1 TripCmd Signal Trip Command 50R 2 TripCmd Signal Trip Command 51R 1 TripCmd Signal Trip Command 51R 2 TripCmd Si...

Page 833: ...protection a test current has to be higher than the threshold value of one of the current protection modules that are assigned to trigger the BF protection The BF trip delay can be measured from the t...

Page 834: ...circuit calibration errors and other is the dynamic error that is proportional to the measured maximum current due to CT transformation characteristics The CTs are assumed to be used in the wye ground...

Page 835: ...If the current is measured in two phases only for example only IA IB or if there is no separate ground current measuring e g normally via a zero sequence CT the supervision function should be deactiva...

Page 836: ...ww eaton com 836 Please Refer to Diagram Blockings IX Calculated IA CTS Pickup CTS Element is not deactivated and no active blocking signals IC IB IX Kd CTS I 2 AND 40 CTS t t 0 Phase or Ground Curren...

Page 837: ...Setting range Default Menu path ExBlo1 External blocking of the module if blocking is activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Prot...

Page 838: ...n CTS I In order to prevent faulty tripping of phase selective protection functions that use the current as tripping criterion If the difference of the measured ground current and the calculated value...

Page 839: ...ion Para Global Prot Para Supervision CTS ExBlo2 I Module Input State External Blocking2 Protection Para Global Prot Para Supervision CTS Current Transformer Supervision Signals Outputs States Signal...

Page 840: ...ee phase symmetrical current system approx nominal current to the secondary side Disconnect the current of one phase from one of the measuring inputs the symmetrical feeding at the secondary side has...

Page 841: ...lowing measured values and information to detect an LOP condition Three phase voltages Ratio of negative to positive sequence voltages Zero sequence voltage Three phase currents Residual current I0 On...

Page 842: ...0 9999 s t Pickup 0 LOP LOP Blo LOP Pickup AND AND AND OR OR LOP Name LOP 38a Please Refer to Diagram Blockings Element is not deactivated and no active blocking signals 2 Phase Voltage Transformer F...

Page 843: ...enu path ExBlo1 External blocking of the module if blocking is activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot...

Page 844: ...nactive Active Inactive Protection Para 1 4 Supervision LOP LOP Blo Enable Activate allow or inactivate disallow blocking by the module LOP Inactive Active Inactive Protection Para 1 4 Supervision LOP...

Page 845: ...obal Prot Para Supervision LOP ExBlo2 I Module Input State External Blocking2 Protection Para Global Prot Para Supervision LOP LOP Module Signals Output States Signal Description Active Signal Active...

Page 846: ...ion I setting and The residual current is less than 0 1 Ipu rated current and The offline detection has not detected a dead busbar No current no voltage measured Successful test result part 1 The outp...

Page 847: ...t be monitored through the other digital inputs Note that the digital inputs used for this purpose must be configured properly based on the trip circuit control voltage and also that the de bouncing t...

Page 848: ...52a and 52b in trip circuit www eaton com 848 Breaker 1 Bkr 1 Control Voltage 1 2 3 4 5 6 7 8 PE 9 10 11 12 COM1 13 14 15 16 17 18 V DI1 COM2 DI2 V X1 TC W1 52a W1 52b DC DC 52a 52b Trip Relay Control...

Page 849: ...a Only in Trip Circuit www eaton com 849 Breaker 1 Bkr 1 Control Voltage 1 2 3 4 5 6 7 8 PE 9 10 11 12 COM1 13 14 15 16 17 18 V DI1 V X1 TC W1 52a W1 52b DC DC 52a 52b Trip Relay Control Voltage AND B...

Page 850: ...the breaker is closed 1 n Dig Inputs DI 8P X1 DI 1 Protection Para Global Prot Para Supervision TCM Input 2 Select the input configured to monitor the trip coil when the breaker is open Only availabl...

Page 851: ...Fc Activate allow or inactivate disallow blocking of the module element This parameter is only effective if a signal is assigned to the corresponding global protection parameter If the signal becomes...

Page 852: ...Global Prot Para Supervision TCM ExBlo1 I Module Input State External Blocking1 Protection Para Global Prot Para Supervision TCM ExBlo2 I Module Input State External Blocking2 Protection Para Global P...

Page 853: ...st of the trip circuit monitoring with 52a and 52b contact Procedure Part 1 Simulate failure of the control voltage in the power circuits Successful Test Result Part 1 After expiration of t TCM the tr...

Page 854: ...he second threshold Monitoring of the communication between Main and Digital Signal Processor DSP The cyclic measured value processing of the DSP is monitored by the main processor The device will be...

Page 855: ...lows the termination of ongoing data writing procedures The module for the supervision of the system utilization will detect repetitive short term sags of the supply voltage Internal data of the devic...

Page 856: ...the Operator Device reboot triggered by the operator via HMI or Smart view 3 Reboot by means of Super Reset Automatic reboot when setting the device back to factory defaults 4 outdated 5 outdated 6 Un...

Page 857: ...lowed by a 6 digit error code e g E01487 In addition to the recorders messages and display information that can be accessed by the user there may exist additional error information accessible by the S...

Page 858: ...l Device Failure SelfSuperVision Contact Signal SelfSuperVision Contact Values of the Self Supvervision Value Description Menu path Last Failure Last Failure Operation Self Supervision System Error Co...

Page 859: ...ctive function pickups protective function states breaker states system alarms and module inputs The User can use the output signals of a logic equation as inputs in higher equations e g the output si...

Page 860: ...are 0 then the output of the gate will be set as follows 0 for an AND gate 1 for a NAND gate 0 for an OR gate 1 for a NOR gate If at least one input signal is assigned to a gate all not assigned input...

Page 861: ...Assignment List LE x IN1 Active Inactive Inverting1 XOR 1 n Assignment List LE x IN2 Active Inactive Inverting2 XOR 1 n Assignment List LE x IN3 Active Inactive Inverting3 XOR 1 n Assignment List LE...

Page 862: ...e output of the gate can be delayed The User has the option to set an On and an Off delay Latching The timer issues two signals an unlatched and a latched signal The latched output can optionally be i...

Page 863: ...utilizes the output signal of Logic Equation n as input of Logic Equation n 1 If the state of Logic Equation n changes the state of the output of Logic Equation n 1 will be updated within the same cyc...

Page 864: ...elay Logic Equation2 LE2 IN2 LE2 IN3 LE2 IN4 Output of Logic Equation 2 Logic Equation1 LE1 IN2 LE1 IN3 LE1 IN4 Output of Logic Equation 1 Logic Equation3 LE3 IN1 LE3 IN2 LE3 IN3 LE3 IN4 Logic Equatio...

Page 865: ...to be set Set the Input Signals where necessary invert them If required configure the timer On delay and Off delay If the latched output signal is used assign a reset signal to the reset input Within...

Page 866: ...ic gate AND OR NAND NOR AND Logic LE 1 LE1 IN1 Assignment of the Input Signal 1 n Assignment List Logic LE 1 LE1 Inverting1 Inverting the input signals Only available if an input signal has been assig...

Page 867: ...nals Only available if an input signal has been assigned Inactive Active Inactive Logic LE 1 LE1 t On Delay Switch On Delay 0 00 36000 00s 0 00s Logic LE 1 LE1 t Off Delay Switch Off Delay 0 00 36000...

Page 868: ...ate of the module input Assignment of the Input Signal Logic LE 1 LE1 Gate In4 I State of the module input Assignment of the Input Signal Logic LE 1 LE1 Reset Latch I State of the module input Reset S...

Page 869: ...omponent connections All locally applicable national and international installation and safety regulations for working at electrical power installations MUST always to be followed Prior to the initial...

Page 870: ...LEDs and relay functions these have to be provided with the relevant pickup alarm and tripping functions of the respective protection functions elements This MUST be tested in practical operation Chec...

Page 871: ...nd that there are no voltages that could lead to injury of personnel Disconnect the terminals at the rear side of the device DO NOT pull any cable pull on the plug If it is stuck use a screw driver Fa...

Page 872: ...ce and Commissioning Support Within the service menu various functions support maintenance and commissioning of the device General Within the Service General menu the User can initiate a reboot of the...

Page 873: ...lt clearing time and lower incident energy levels at energized panels The Maintenance Mode allows the User to switch to more sensitive settings via the HMI panel Communication or via a Digital Input w...

Page 874: ...ensitivity settings either into a setting group or into Adaptive Parameters The Maintenance Mode offers two output signals Maint Mode activated and Maint Mode not activated The Maint Mode ACTIVATED si...

Page 875: ...ctive Sys Maint Mode Mode Activation Manually Activation via Comm Activation via DI Inactive Sys MaintMode Manually Active Comm Cmd Sys Maint Mode Active Sys Maint Mode Inactive Sys MaintMode Manually...

Page 876: ...with a timeout they will keep their Force Position only as long as this timer runs If the timer expires the relay will operate normally If they are set as Permanent they will keep the Force Position c...

Page 877: ...tective device WILL NOT provide protection Zone Interlocking Output and the Supervision Contact cannot be disarmed Within this mode Service Test Mode Prot inhibit WARNING Cont DISARMED entire groups o...

Page 878: ...t contact WILL be disarmed if it is not latched and If there is no running t OFF delay timer hold time of a relay output contact and If the DISARM Control is set to active and If the Direct Command Di...

Page 879: ...t inhibit WARNING Cont URTD RTD temperatures can be set by force Permanent or Via timeout If they are set with a timeout they will keep their Forced Temperature only as long as this timer runs If the...

Page 880: ...ARNING Cont Analog Outputs Analog Outputs can be set by force Permanent or Via timeout If they are set with a timeout they will keep their Forced Value only as long as this timer runs If the timer exp...

Page 881: ...s can be set by force Permanent or Via timeout If they are set with a timeout they will keep their Forced Value only as long as this timer runs If the timer expires the Analog Input will operate norma...

Page 882: ...Prot inhibit WARNING Cont Sine wave gen Configuration sub menu the duration of each phase can be set In addition the measuring quantities to be simulated can be determined e g voltages currents and th...

Page 883: ...EDR 5000 IM02602007E The simulation voltages are always phase to neutral voltages irrespectively of the mains voltage transformers connection method Phase to phase Wey Open Delta www eaton com 883...

Page 884: ...ipCmd Simulation is authorized to trip the breaker How To Call up Service Test Mode Prot inhibit WARNING Cont Sine wave gen Process Trip Cmd Mode With TripCmd Stop by external signal Force Post As soo...

Page 885: ...Fault Duration 0 00 300 00s 0 0s Service Test Mode Prot inhibit WARNING Cont Sgen Configuration Times FaultSimulation Duration of Fault Simulation 0 00 10800 00s 0 0s Service Test Mode Prot inhibit W...

Page 886: ...OSE Service Test Mode Prot inhibit WARNING Cont Sgen Process Ex ForcePost Force Post state Abort simulation 1 n Assignment List Service Test Mode Prot inhibit WARNING Cont Sgen Process Voltage Paramet...

Page 887: ...00 1 30Vn 0 0Vn Service Test Mode Prot inhibit WARNING Cont Sgen Configuration PreFault VT Angle VA Fund Start Position respectively Start Angle of the Voltage Phasor during Pre Phase Phase A 360 360...

Page 888: ...n respectively Start Angle of the Voltage Phasor during Pre Phase VX 360 360 0 Service Test Mode Prot inhibit WARNING Cont Sgen Configuration PreFault VT VA Fund Voltage Fundamental Magnitude in Fault...

Page 889: ...30Vn 0 29Vn Service Test Mode Prot inhibit WARNING Cont Sgen Configuration FaultSimulation VT Angle VA Fund Start Position respectively Start Angle of the Voltage Phasor during Fault Phase Phase A 36...

Page 890: ...tion respectively Start Angle of the Voltage Phasor during Fault Phase VX 360 360 0 Service Test Mode Prot inhibit WARNING Cont Sgen Configuration FaultSimulation VT VA Fund Voltage Fundamental Magnit...

Page 891: ...e VX 0 00 1 30Vn 0 0Vn Service Test Mode Prot inhibit WARNING Cont Sgen Configuration PostFault VT Angle VA Fund Start Position respectively Start Angle of the Voltage Phasor during Post phase Phase A...

Page 892: ...hasor during Post phase Phase VX 360 360 0 Service Test Mode Prot inhibit WARNING Cont Sgen Configuration PostFault VT Current Parameter of the Failure Simulator Parameter Description Setting range De...

Page 893: ...0 00 25 00In 0 0In Service Test Mode Prot inhibit WARNING Cont Sgen Configuration PreFault CT Angle IA Fund Start Position respectively Start Angle of the Current Phasor during Pre Phase Phase A 360...

Page 894: ...n respectively Start Angle of the Current Phasor during Pre Phase IX 360 360 0 Service Test Mode Prot inhibit WARNING Cont Sgen Configuration PreFault CT IA Fund Current Fundamental Magnitude in Fault...

Page 895: ...5 00In 0 0In Service Test Mode Prot inhibit WARNING Cont Sgen Configuration FaultSimulation CT Angle IA Fund Start Position respectively Start Angle of the Current Phasor during Fault Phase Phase A 36...

Page 896: ...tion respectively Start Angle of the Current Phasor during Fault Phase IX 360 360 0 Service Test Mode Prot inhibit WARNING Cont Sgen Configuration FaultSimulation CT IA Fund Current Fundamental Magnit...

Page 897: ...IX 0 00 25 00In 0 0In Service Test Mode Prot inhibit WARNING Cont Sgen Configuration PostFault CT Angle IA Fund Start Position respectively Start Angle of the Current Phasor during Post phase Phase A...

Page 898: ...Current Phasor during Post phase Phase C 360 360 120 Service Test Mode Prot inhibit WARNING Cont Sgen Configuration PostFault CT Angle IX meas Fund Start Position respectively Start Angle of the Curr...

Page 899: ...s ExBlo Module Input State External Blocking Service Test Mode Prot inhibit WARNING Cont Sgen Process Ex ForcePost I State of the module input Force Post state Abort simulation Service Test Mode Prot...

Page 900: ...ARNING Cont Sgen Process Stop Simulation Stop Fault Simulation Using the test parameters Inactive Active Inactive Service Test Mode Prot inhibit WARNING Cont Sgen Process Failure Simulator Values Valu...

Page 901: ...ection EN 60529 HMI Front Panel with Seal IP54 Rear Side Terminals IP20 Routine Test Insulation Test Acc to IEC60255 5 All tests to be carried out against ground and other input and output circuits Au...

Page 902: ...lf wave Power Consumption Phase current inputs At In 1 A S 25 mVA At In 5 A S 90 mVA Ground current input At In 1 A S 25 mVA At In 5 A S 90 mVA Sensitive Ground Current Inputs Nominal Currents 1 A 5 A...

Page 903: ...5 mm 2 x AWG 14 with wire end ferrule 1 x or 2 x 4 0 mm 2 x AWG 12 with ring cable sleeve or cable sleeve 1 x or 2 x 6 mm 2 x AWG 10 with ring cable sleeve or cable sleeve The current measuring board...

Page 904: ...Max Measuring Range 800 Vac Continuous Loading Capacity 800 Vac Power Consumption at Vn 100 V S 22 mVA at Vn 110 V S 25 mVA at Vn 230 V S 110 mVA at Vn 400 V S 330 mVA Frequency Range 50 Hz or 60 Hz...

Page 905: ...value for 1 ms The voltage supply must be protected by a fuse of 2 5 A time lag miniature fuse 5 x 20 mm approx 0 2 x 0 8 in according to IEC 60127 3 5 A time lag miniature fuse 6 3 x 32 mm approx 0 2...

Page 906: ...Display 128 x 64 pixel Large Display Type Option LCD with LED background illumination Resolution Graphics Display 128 x 128 pixel LED Type Two colored red green Number of LEDs Housing B2 15 Front Inte...

Page 907: ...Threshold 1 ON Switching Threshold 1 OFF Min 19 2 Vdc Max 9 6 Vdc Un 48 V 60Vdc Switching Threshold 2 ON Switching Threshold 2 OFF Min 42 6 Vdc Max 21 3 Vdc Un 110 120 Vac dc Switching Threshold 3 ON...

Page 908: ...s Max Switching Voltage 250 Vac 250 Vdc Switching Capacity 3 000 VA Contact Type Form C or normally open contact Terminals Screw type terminals Supervision Contact SC Continuous Current 5 A ac dc Max...

Page 909: ...3 5 mm 138 MIL terminating resistors internal The RS485 interface is realized via terminals The communication cable has to be shielded The shielding has to be fixed at the screw that is marked with t...

Page 910: ...ith 50 125 m Fiber 19 0 dBm with 62 5 125 m Fiber URTD Interface Connector Versatile Link Compatible Fiber 1 mm Wavelength 660 nm Minimum Optical Input Power 39 0 dBm availability depends on device Bo...

Page 911: ...EC 60255 22 1 IEEE C37 90 1 IEC 61000 4 18 class 3 Within one circuit Circuit to ground Circuit to circuit 1 kV 2 s 2 5 kV 2 s 2 5 kV 2 s Insulation Voltage Test IEC 60255 27 10 5 3 2 IEC 60255 5 EN 5...

Page 912: ...4 ANSI C37 90 1 class 4 Power supply mains inputs Other in and outputs 4 kV 2 5 kHz 2 kV 5 kHz coupling network 4 kV 2 5 kHz coupling clamp Surge Immunity Test Surge IEC 60255 22 5 IEC 61000 4 5 clas...

Page 913: ...V m 35 V m 10 V m Immunity to Conducted Disturbances Induced by Radio Frequency Fields IEC 61000 4 6 class 3 150kHz 80MHz 10 V Power Frequency Magnetic Field Immunity Test IEC 61000 4 8 class 4 contin...

Page 914: ...of ambient conditions Stationary use at weather protected locations 3K6 3B1 3C1 3S1 3M2 but min 20 C 4 F max 60 C 140 F Test Ad Cold IEC 60068 2 1 Temperature Test duration 20 C 4 F 16 h Test Bd Dry H...

Page 915: ...ature cycle test duration 60 C 20 C 5 1 C 5min Test BD Dry Heat Transport and storage test IEC 60255 6 12 3 3 IEC 60068 2 2 Temperature test duration 70 C 16 h Test AB Cold Transport and storage test...

Page 916: ...Test IEC 60068 2 27 IEC 60255 21 2 class 1 Shock response test 5 gn 11 ms 3 impulses in each direction Shock resistance test 15 gn 11 ms 3 impulses in each direction Test Eb Shock Endurance Test IEC...

Page 917: ...tocol Time drift over one month Deviation to time generator Without time synchronization 1 min 20 C Time drifts IRIG B Dependent on the time drift of the time generator 1 ms SNTP Dependent on the time...

Page 918: ...100 mA with In 1 A respectively 500 mA with In 5 A Phase to ground and Residual Voltage Measurement Frequency Range 50 Hz 60 Hz 10 Accuracy for measured values Class 0 5 Amplitude error for V Vn 0 5...

Page 919: ...easured value or 0 1 Sn for fundamental 2 of the measured value or 0 1 Sn for RMS W 1 Var 1 pos sequence 2 of the measured value or 0 2 Sn Power Factor Measurement PF 0 01 of measured power factor or...

Page 920: ...cy 2 Pickup 1 5 of the setting value or 1 In Dropout Ratio 97 or 0 5 In t DEFT 1 or 10 ms Operating Time At testing current 2 times pickup value 36ms directional elements 40ms Disengaging Time 55 ms O...

Page 921: ...67X x 67R x Accuracy 2 3 Pickup measured ground current Pickup calculated ground current 1 5 of the setting value or 1 In 2 0 of the setting value or 1 5 In Dropout Ratio 97 or 0 5 In Operating Time S...

Page 922: ...value or 1 In I2 I1 1 t DEFT 1 or 10 ms Operating Time 70 ms Disengaging Time 50 ms 1 Negative sequence current I2 must be 0 01 x In I1 must be 0 1 x In Undervoltage and Overvoltage Phase Auxiliary a...

Page 923: ...otection 81O x Accuracy 1 Threshold 10 mHz at fn Dropout 0 05 fn t 1 or 10 ms Operating time Starting from f higher than f 0 02 Hz 0 1 Hz 2 0 Hz 100 ms typically 70 ms typically 50 ms Disengaging time...

Page 924: ...frequency fn e g at 45Hz tolerance is 0 15Hz s Rate of Change of Frequency DF DT Accuracy DF 20 mHz at fn DT 1 or 10 ms Vector surge 78V Accuracy Threshold 0 5 1 30 at Vn and fn Operating time 40 ms P...

Page 925: ...ditions at PF 0 5 symmetrically fed at fn and 0 8 1 3 x Vn Vn 100V Auto Reclosing AR Accuracy t all timers 1 or 20 ms Sync Check Sync Accuracy Voltage measurement 1 5 of the setting value or 1 Vn Slip...

Page 926: ...n Dropout 0 05 fn t UFLS 1 or 10 ms Operating time Starting from f lower than f 0 02 Hz 0 1 Hz 2 0 Hz 100 ms typically 70 ms typically 50 ms Disengaging time 120 ms Switch onto Fault SOTF Accuracy Ope...

Page 927: ...t Monitoring TCM Accuracy t TCM 1 or 10 ms Current Transformer Supervision CTS Accuracy I 2 of the setting value or 1 5 In Dropout Ratio 94 Pickup delay 1 or 10 ms Loss of Potential LOP Accuracy t Pic...

Page 928: ...ate The output becomes true if all Input signals are true ANG Angle ANSI American National Standards Institute AR Automatic reclosure AUX Auxiliary AVG avg Average AWG American wire gauge BF Breaker f...

Page 929: ...nt DEFT Definite time characteristic Tripping time does not depend on the height of the current DFLT Default DGNST Diagnostics DI Digital Input Diagn Diagnosis Diagn Cr Diagnosis counter s DIFF Differ...

Page 930: ...cceleration of the earth in vertical direction 9 81 m s2 GND Ground GPS Global positioning system h Hour HARM Harmonic harmonics HMI Human machine interface Front of the protective relay HTL Manufactu...

Page 931: ...armonic IINV Inverse in Inch incl Include including Info Information Interl Interlocking INV Inverse characteristic The tripping time will be calculated depending on the height of the current I O Inpu...

Page 932: ...pping characteristic LV Low voltage m Meter M Machine mA Milliampere s Milliamp s MAG Magnitude MAN man Manual manually MAX max Maximum meas Measured MIN min Minimum min Minute MINV Moderately Inverse...

Page 933: ...W A Megawatt s phase A MW B Megawatt s phase B MW C Megawatt s phase C MWH Megawatt Hour s N Neutral N A n a Not applicable N C Not connected NEG Negative NINV Normal inverse tripping characteristic N...

Page 934: ...aster Module protection PS1 Parameter set 1 PS2 Parameter set 2 PS3 Parameter set 3 PS4 Parameter set 4 PSet Parameter set PSS Parameter set switch Switching from one parameter set to another pu Per u...

Page 935: ...SEC sec Secondary SENS Sensitive SEQ Sequence Sig Signal SNTP Simple network time protocol SRC Source StartFct Start function STATS Statistics Sum Summation SUPERV Supervision SW Software SYNC Sync c...

Page 936: ...o sequence voltage V1 Positive sequence voltage V2 Negative sequence voltage VA Phase A voltage VAB Phase A to B voltage Vac V ac Volts alternating current VAG Phase A to ground voltage VARH Var hour...

Page 937: ...ge transformer supervision W Watt s WDC Watch dog contact supervision contact WDG Winding WH Watthour www World wide web X Reactance XCT 4th current measuring input ground or neutral current XInv Inve...

Page 938: ...anation www eaton com 938 t Tripping delay I Fault current Pickup If the pickup value is exceeded the module element starts to time out to trip t s Pickup I 1 10 0 01 0 1 1 10 100 1 10 0 01 0 1 1 10 1...

Page 939: ...nv VINV ANSI XInv EINV ANSI XInv Thermal Flat Therm Flat IT Therm Flat I2T and Therm Flat I4T Explanation www eaton com 939 t Tripping delay t multiplier Time multiplier tripping characteristic factor...

Page 940: ...0 t multiplier x Pickup Multiples of Pickup Trip Reset t 0 14 t multiplier s Pickup 1 I 2 t 0 14 t multiplier s Pickup 1 I 0 02 t s Notice Various Reset Modes are available Resetting via characteristi...

Page 941: ...941 t s t multiplier t 13 5 t multiplier s Pickup 1 I t 13 5 t multiplier s Pickup 1 I 2 Trip Reset x Pickup Multiples of Pickup Notice Various Reset Modes are available Resetting via characteristic...

Page 942: ...m 942 t s t multiplier t 120 t multiplier s Pickup 1 I 2 t 120 t multiplier s Pickup 1 I Trip Reset x Pickup Multiples of Pickup Notice Various Reset Modes are available Resetting via characteristic d...

Page 943: ...m 943 t s t multiplier t 80 t multiplier s Pickup 1 I 2 t 80 t multiplier s Pickup 1 I 2 Trip Reset x Pickup Multiples of Pickup Notice Various Reset Modes are available Resetting via characteristic d...

Page 944: ...t multiplier t 4 85 t multiplier s Pickup 1 I 2 t 0 0515 t multiplier s Pickup 1 I 0 02 0 1140 Trip Reset x Pickup Multiples of Pickup Notice Various Reset Modes are available Resetting via character...

Page 945: ...t s t multiplier Trip Reset x Pickup Multiples of Pickup t 19 61 t multiplier s Pickup 1 I 2 0 491 t 21 6 t multiplier s Pickup 1 I 2 Notice Various Reset Modes are available Resetting via characteris...

Page 946: ...t s t multiplier t 29 1 t multiplier s Pickup 1 I 2 Trip Reset x Pickup Multiples of Pickup t 28 2 t multiplier s Pickup 1 I 2 0 1217 Notice Various Reset Modes are available Resetting via characteris...

Page 947: ...al Current Trip Reset t 5 3 t multiplier s 2 In I 0 t 5 1 t multiplier s In I 0 2 Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous Therm Flat t 45 t mult...

Page 948: ...s of the Nominal Current Trip Reset t 5 3 t multiplier s 2 In I 0 Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous IT t 5 3 t multiplier s 1 In I 1 0 01...

Page 949: ...100 1 10 3 1 10 4 TM s 10 5 2 1 0 0 5 0 05 t s t multiplier x In Multiples of the Nominal Current Trip Reset t 5 3 t multiplier s 2 In I 0 Notice Various Reset Modes are available Resetting via chara...

Page 950: ...of the Nominal Current Trip Reset t 5 3 t multiplier s 2 In I 0 Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous I4T t 5 3 t multiplier s In I 4 4 0 01...

Page 951: ...easured either directly via a zero sequence transformer or detected by a residual connection The ground current can alternatively be calculated from the phase currents but this is only possible if the...

Page 952: ...EDR 5000 IM02602007E www eaton com 952 t s 1 10 0 01 0 1 1 10 100 1 10 0 01 0 1 1 10 100 I I t t 40 20 300 s 300 s 0 0 s 0 0 s 0 01 0 01 Pickup IR calc Pickup IR calc DEFT...

Page 953: ...asured either directly via a zero sequence transformer or detected by a residual connection The ground current can alternatively be calculated from the phase currents but this is only possible if the...

Page 954: ...EDR 5000 IM02602007E www eaton com 954 t s 1 10 0 01 0 1 1 10 100 1 10 0 01 0 1 1 10 100 I I t t 40 20 300 s 300 s 0 0 s 0 0 s 0 01 0 01 Pickup IX Pickup IX DEFT...

Page 955: ...be measured either directly via a zero sequence transformer or detected by a residual connection The ground current can alternatively be calculated from the phase currents but this is only possible if...

Page 956: ...t multiplier t 0 14 t multiplier s Pickup 1 IG 0 02 Trip Reset t 0 14 t multiplier s Pickup 1 IG 2 x Pickup Multiples of Pickup t s Notice Various Reset Modes are available Resetting via characterist...

Page 957: ...957 t s t multiplier Trip Reset x Pickup Multiples of Pickup t 13 5 t multiplier s Pickup 1 IG 2 t 13 5 t multiplier s Pickup 1 IG Notice Various Reset Modes are available Resetting via characteristic...

Page 958: ...958 t s t multiplier x Pickup Multiples of Pickup Trip Reset t 120 t multiplier s Pickup 1 IG t 120 t multiplier s 1 IG 2 Pickup Notice Various Reset Modes are available Resetting via characteristic...

Page 959: ...959 t s t multiplier x Pickup Multiples of Pickup Trip Reset t 80 t multiplier s Pickup 1 IG 2 t 80 t multiplier s Pickup 1 IG 2 Notice Various Reset Modes are available Resetting via characteristic...

Page 960: ...t multiplier x Pickup Multiples of Pickup t 0 0515 t multiplier s Pickup 1 IG 0 02 0 1140 t 4 85 t multiplier s 1 IG 2 Pickup Trip Reset Notice Various Reset Modes are available Resetting via characte...

Page 961: ...s t multiplier x Pickup Multiples of Pickup Trip Reset t 21 6 t multiplier s 1 IG 2 Pickup t 19 61 t multiplier s Pickup 1 IG 2 0 491 Notice Various Reset Modes are available Resetting via characteri...

Page 962: ...s t multiplier x Pickup Multiples of Pickup Trip Reset t 28 2 t multiplier s Pickup 1 IG 2 0 1217 t 29 1 t multiplier s 1 IG 2 Pickup Notice Various Reset Modes are available Resetting via characteri...

Page 963: ...s 2 IG 0 IGnom x In Multiples of the Nominal Current Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous Therm Flat t 5 t multiplier s IGnom IG 0 t 5 t mul...

Page 964: ...tiples of the Nominal Current t 5 1 t multiplier s 2 IG 0 IGnom Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous IT t 5 1 t multiplier s IGnom IG 1 1 0 0...

Page 965: ...ltiples of the Nominal Current t 5 1 t multiplier s 2 IG 0 IGnom Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous I2T t 5 1 t multiplier s IGnom IG 2 2 0...

Page 966: ...ltiples of the Nominal Current t Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous I4T t 5 1 t multiplier s IGnom IG 4 4 5 1 t multiplier s 2 IGnom IG 0 0...

Page 967: ...Phase current failure reverse direction Prot I dir n poss Signal Phase fault missing reference voltage Prot IR dir fwd Signal IR Ground fault calculated forward Prot IR dir rev Signal IR Ground fault...

Page 968: ...Signal Command Execution Supervision Switching Command not executed because of field interlocking Bkr CES SyncTimeout Signal Command Execution Supervision Switching Command not executed No Synchroniz...

Page 969: ...ignal Maximum permissible Summation of the interrupting tripping currents exceeded in at least one phase Bkr Res TripCmdCr Signal Resetting of the Counter total number of trip commands Bkr Res Isum tr...

Page 970: ...p IC 50P 2 Pickup Signal Pickup 50P 2 Trip Signal Trip 50P 2 TripCmd Signal Trip Command 50P 2 DefaultSet Signal Default Parameter Set 50P 2 AdaptSet 1 Signal Adaptive Parameter 1 50P 2 AdaptSet 2 Sig...

Page 971: ...Parameter1 50P 3 AdaptSet2 I Module Input State Adaptive Parameter2 50P 3 AdaptSet3 I Module Input State Adaptive Parameter3 50P 3 AdaptSet4 I Module Input State Adaptive Parameter4 51P 1 Active Sign...

Page 972: ...nd 51P 2 DefaultSet Signal Default Parameter Set 51P 2 AdaptSet 1 Signal Adaptive Parameter 1 51P 2 AdaptSet 2 Signal Adaptive Parameter 2 51P 2 AdaptSet 3 Signal Adaptive Parameter 3 51P 2 AdaptSet 4...

Page 973: ...t4 I Module Input State Adaptive Parameter4 50X 1 Active Signal Active 50X 1 ExBlo Signal External Blocking 50X 1 Rvs Blo Signal Reverse Blocking 50X 1 Blo TripCmd Signal Trip Command blocked 50X 1 Ex...

Page 974: ...External Blocking of the Trip Command 50X 2 Rvs Blo I Module Input State Reverse Blocking 50X 2 AdaptSet1 I Module Input State Adaptive Parameter1 50X 2 AdaptSet2 I Module Input State Adaptive Paramet...

Page 975: ...tSet 2 Signal Adaptive Parameter 2 51X 2 AdaptSet 3 Signal Adaptive Parameter 3 51X 2 AdaptSet 4 Signal Adaptive Parameter 4 51X 2 ExBlo1 I Module Input State External Blocking1 51X 2 ExBlo2 I Module...

Page 976: ...the Trip Command 50R 2 Pickup Signal Pickup IX or IR 50R 2 Trip Signal Trip 50R 2 TripCmd Signal Trip Command 50R 2 DefaultSet Signal Default Parameter Set 50R 2 AdaptSet 1 Signal Adaptive Parameter...

Page 977: ...er4 51R 2 Active Signal Active 51R 2 ExBlo Signal External Blocking 51R 2 Rvs Blo Signal Reverse Blocking 51R 2 Blo TripCmd Signal Trip Command blocked 51R 2 ExBlo TripCmd Signal External Blocking of...

Page 978: ...Blo TripCmd Signal External Blocking of the Trip Command 27M 2 Pickup Phase A Signal Pickup Phase A 27M 2 Pickup Phase B Signal Pickup Phase B 27M 2 Pickup Phase C Signal Pickup Phase C 27M 2 Pickup S...

Page 979: ...nal External Blocking 27A 1 Blo TripCmd Signal Trip Command blocked 27A 1 ExBlo TripCmd Signal External Blocking of the Trip Command 27A 1 Pickup Signal Pickup Residual Voltage Supervision Element 27A...

Page 980: ...Module Input State External Blocking2 59A 2 ExBlo TripCmd I Module Input State External Blocking of the Trip Command 59N 1 Active Signal Active 59N 1 ExBlo Signal External Blocking 59N 1 Blo TripCmd...

Page 981: ...ve Signal Active LVRT 2 ExBlo Signal External Blocking LVRT 2 Blo TripCmd Signal Trip Command blocked LVRT 2 ExBlo TripCmd Signal External Blocking of the Trip Command LVRT 2 Pickup Phase A Signal Pic...

Page 982: ...ommand 47 1 Pickup Signal Pickup Voltage Asymmetry 47 1 Trip Signal Trip 47 1 TripCmd Signal Trip Command 47 1 ExBlo1 I Module Input State External Blocking1 47 1 ExBlo2 I Module Input State External...

Page 983: ...rip Command 81 2 Pickup 81 Signal Pickup Frequency Protection 81 2 Pickup df dt DF DT Pickup instantaneous or average value of the rate of frequency change 81 2 Pickup Vector Surge Signal Pickup Vecto...

Page 984: ...Signal Pickup Vector Surge 81 4 Pickup Signal Pickup Frequency Protection collective signal 81 4 Trip 81 Signal Frequency has exceeded the limit 81 4 Trip df dt DF DT Signal Trip df dt or DF DT 81 4 T...

Page 985: ...nal Frequency has exceeded the limit 81 6 Trip df dt DF DT Signal Trip df dt or DF DT 81 6 Trip Vector Surge Signal Trip delta phi 81 6 Trip Signal Trip Frequency Protection collective signal 81 6 Tri...

Page 986: ...32V 1 Active Signal Active 32V 1 ExBlo Signal External Blocking 32V 1 Blo TripCmd Signal Trip Command blocked 32V 1 ExBlo TripCmd Signal External Blocking of the Trip Command 32V 1 Pickup Signal Pick...

Page 987: ...Impossible Signal Pickup Power Factor Impossible PF 55D 1 ExBlo1 I Module Input State External Blocking PF 55D 1 ExBlo2 I Module Input State External Blocking PF 55D 1 ExBlo TripCmd I Module Input Sta...

Page 988: ...ossible PF 55A 2 ExBlo1 I Module Input State External Blocking PF 55A 2 ExBlo2 I Module Input State External Blocking PF 55A 2 ExBlo TripCmd I Module Input State External Blocking of the Trip Command...

Page 989: ...the current exceeds this value UFLS VLL min Signal Minimum Voltage UFLS Power Angle Signal Trigger Phi Power Positive Phase Sequence System UFLS P min Signal Minimum Value threshold for the Active Pow...

Page 990: ...ng OUT ZI IN Signal Zone Interlocking IN ZI ExBlo1 I Module Input State External Blocking1 ZI ExBlo2 I Module Input State External Blocking2 ZI ExBlo TripCmd I Module Input State External Blocking of...

Page 991: ...arm I Module Input State Alarm ExP 1 Trip I Module Input State Trip ExP 2 Active Signal Active ExP 2 ExBlo Signal External Blocking ExP 2 Blo TripCmd Signal Trip Command blocked ExP 2 ExBlo TripCmd Si...

Page 992: ...ignal Active BF ExBlo Signal External Blocking BF Waiting for Trigger Waiting for Trigger BF Pickup Signal BF Module Started Pickup BF Trip Signal Breaker Failure Trip BF Lockout Signal Lockout BF Res...

Page 993: ...tempt AR Bkr CLOSE Cmd Signal Bkr Switch ON CLOSE Command AR t Run2Ready Signal Examination Time If the Breaker remains after a reclosure attempt shot for the duration of this timer in the Closed posi...

Page 994: ...s true the AR will be aborted AR Abort 3 Abort the AR cycle if the state of the assigned signal is true If the state of this function is true the AR will be aborted AR Abort 4 Abort the AR cycle if th...

Page 995: ...ignal Wh Rev Reset Counter ECr VArh Net Res Cr Signal VArh Net Reset Counter ECr VArh Lag Res Cr Signal VArh Lag Reset Counter ECr VArh Lead Res Cr Signal VArh Lead Reset Counter ECr Res all Energy Cr...

Page 996: ...Inputs 52a M2 I State of the module input Main 2 Breaker Closed Wired Inputs 52b M2 I State of the module input Main 2 Breaker Open Wired Inputs TOCa M2 I State of the module input Main 2 Breaker Con...

Page 997: ...RO 4 Signal Relay Output RO 6 X5 RO 5 Signal Relay Output RO 6 X5 RO 6 Signal Relay Output RO 6 X5 DISARMED Signal CAUTION RELAYS DISARMED in order to safely perform maintenance while eliminating the...

Page 998: ...BinaryOutput7 Virtual Digital Output DNP This corresponds to a virtual binary input of the protective device DNP BinaryOutput8 Virtual Digital Output DNP This corresponds to a virtual binary input of...

Page 999: ...tual binary output of the protective device DNP BinaryInput10 I Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device DNP BinaryInput11 I Virtual Digital Input...

Page 1000: ...device DNP BinaryInput46 I Virtual Digital Input DNP This corresponds to a virtual binary output of the protective device DNP BinaryInput47 I Virtual Digital Input DNP This corresponds to a virtual b...

Page 1001: ...ig Bin Inp Modbus Config Bin Inp6 I State of the module input Config Bin Inp Modbus Config Bin Inp7 I State of the module input Config Bin Inp Modbus Config Bin Inp8 I State of the module input Config...

Page 1002: ...IO Ind IEC61850 VirtInp4 Signal Virtual Input IEC61850 GGIO Ind IEC61850 VirtInp5 Signal Virtual Input IEC61850 GGIO Ind IEC61850 VirtInp6 Signal Virtual Input IEC61850 GGIO Ind IEC61850 VirtInp7 Sign...

Page 1003: ...GGIO In10 Self Supervision of the GGIO Input IEC61850 Quality of GGIO In11 Self Supervision of the GGIO Input IEC61850 Quality of GGIO In12 Self Supervision of the GGIO Input IEC61850 Quality of GGIO...

Page 1004: ...aster Communication System Single Point Controllable Status Output IEC61850 SPCSO10 Status bit that can be set by clients like e g the Master Communication System Single Point Controllable Status Outp...

Page 1005: ...s bit that can be set by clients like e g the Master Communication System Single Point Controllable Status Output IEC61850 SPCSO32 Status bit that can be set by clients like e g the Master Communicati...

Page 1006: ...input state Binary state of the Virtual Output GGIO IEC61850 VirtOut32 I Module input state Binary state of the Virtual Output GGIO Profibus Data OK Data within the input field are OK Yes 1 Profibus S...

Page 1007: ...trol Signal11 Signal IRIG B Control Signal The external IRIG B generator can set these signals They can be used for further control procedures inside the device e g logic funtions IRIG B Control Signa...

Page 1008: ...al Logic LE2 Gate In4 I State of the module input Assignment of the Input Signal Logic LE2 Reset Latch I State of the module input Reset Signal for the Latching Logic LE3 Gate Out Signal Output of the...

Page 1009: ...nal Logic LE6 Reset Latch I State of the module input Reset Signal for the Latching Logic LE7 Gate Out Signal Output of the logic gate Logic LE7 Timer Out Signal Timer Output Logic LE7 Out Signal Latc...

Page 1010: ...ut Reset Signal for the Latching Logic LE11 Gate Out Signal Output of the logic gate Logic LE11 Timer Out Signal Timer Output Logic LE11 Out Signal Latched Output Q Logic LE11 Out inverted Signal Nega...

Page 1011: ...ic LE15 Gate Out Signal Output of the logic gate Logic LE15 Timer Out Signal Timer Output Logic LE15 Out Signal Latched Output Q Logic LE15 Out inverted Signal Negated Latched Output Q NOT Logic LE15...

Page 1012: ...Logic LE19 Timer Out Signal Timer Output Logic LE19 Out Signal Latched Output Q Logic LE19 Out inverted Signal Negated Latched Output Q NOT Logic LE19 Gate In1 I State of the module input Assignment o...

Page 1013: ...Output Q Logic LE23 Out inverted Signal Negated Latched Output Q NOT Logic LE23 Gate In1 I State of the module input Assignment of the Input Signal Logic LE23 Gate In2 I State of the module input Ass...

Page 1014: ...7 Gate In1 I State of the module input Assignment of the Input Signal Logic LE27 Gate In2 I State of the module input Assignment of the Input Signal Logic LE27 Gate In3 I State of the module input Ass...

Page 1015: ...1 Gate In2 I State of the module input Assignment of the Input Signal Logic LE31 Gate In3 I State of the module input Assignment of the Input Signal Logic LE31 Gate In4 I State of the module input Ass...

Page 1016: ...5 Gate In3 I State of the module input Assignment of the Input Signal Logic LE35 Gate In4 I State of the module input Assignment of the Input Signal Logic LE35 Reset Latch I State of the module input...

Page 1017: ...Gate In4 I State of the module input Assignment of the Input Signal Logic LE39 Reset Latch I State of the module input Reset Signal for the Latching Logic LE40 Gate Out Signal Output of the logic gat...

Page 1018: ...al Logic LE43 Reset Latch I State of the module input Reset Signal for the Latching Logic LE44 Gate Out Signal Output of the logic gate Logic LE44 Timer Out Signal Timer Output Logic LE44 Out Signal L...

Page 1019: ...input Reset Signal for the Latching Logic LE48 Gate Out Signal Output of the logic gate Logic LE48 Timer Out Signal Timer Output Logic LE48 Out Signal Latched Output Q Logic LE48 Out inverted Signal...

Page 1020: ...ic LE52 Gate Out Signal Output of the logic gate Logic LE52 Timer Out Signal Timer Output Logic LE52 Out Signal Latched Output Q Logic LE52 Out inverted Signal Negated Latched Output Q NOT Logic LE52...

Page 1021: ...Logic LE56 Timer Out Signal Timer Output Logic LE56 Out Signal Latched Output Q Logic LE56 Out inverted Signal Negated Latched Output Q NOT Logic LE56 Gate In1 I State of the module input Assignment o...

Page 1022: ...Output Q Logic LE60 Out inverted Signal Negated Latched Output Q NOT Logic LE60 Gate In1 I State of the module input Assignment of the Input Signal Logic LE60 Gate In2 I State of the module input Ass...

Page 1023: ...4 Gate In1 I State of the module input Assignment of the Input Signal Logic LE64 Gate In2 I State of the module input Assignment of the Input Signal Logic LE64 Gate In3 I State of the module input Ass...

Page 1024: ...8 Gate In2 I State of the module input Assignment of the Input Signal Logic LE68 Gate In3 I State of the module input Assignment of the Input Signal Logic LE68 Gate In4 I State of the module input Ass...

Page 1025: ...2 Gate In3 I State of the module input Assignment of the Input Signal Logic LE72 Gate In4 I State of the module input Assignment of the Input Signal Logic LE72 Reset Latch I State of the module input...

Page 1026: ...Gate In4 I State of the module input Assignment of the Input Signal Logic LE76 Reset Latch I State of the module input Reset Signal for the Latching Logic LE77 Gate Out Signal Output of the logic gat...

Page 1027: ...l Logic LE80 Reset Latch I State of the module input Reset Signal for the Latching Sgen Running Signal Measuring value simulation is running Sgen Ex Start Simulation I State of the module input Extern...

Page 1028: ...Ack TripCmd Comm Signal Reset Trip Command Communication Sys Ack LED I Module Input State LEDs Acknowledgment by Digital Input Sys Ack RO I Module Input State Acknowledgment of the Relay Outputs Sys...

Page 1029: ...al Input Logic LE1 Gate Out Signal Output of the logic gate Logic LE1 Timer Out Signal Timer Output Logic LE1 Out Signal Latched Output Q Logic LE1 Out inverted Signal Negated Latched Output Q NOT Log...

Page 1030: ...Signal Latched Output Q Logic LE9 Out inverted Signal Negated Latched Output Q NOT Logic LE10 Gate Out Signal Output of the logic gate Logic LE10 Timer Out Signal Timer Output Logic LE10 Out Signal L...

Page 1031: ...nverted Signal Negated Latched Output Q NOT Logic LE19 Gate Out Signal Output of the logic gate Logic LE19 Timer Out Signal Timer Output Logic LE19 Out Signal Latched Output Q Logic LE19 Out inverted...

Page 1032: ...ate Out Signal Output of the logic gate Logic LE28 Timer Out Signal Timer Output Logic LE28 Out Signal Latched Output Q Logic LE28 Out inverted Signal Negated Latched Output Q NOT Logic LE29 Gate Out...

Page 1033: ...E37 Timer Out Signal Timer Output Logic LE37 Out Signal Latched Output Q Logic LE37 Out inverted Signal Negated Latched Output Q NOT Logic LE38 Gate Out Signal Output of the logic gate Logic LE38 Time...

Page 1034: ...LE46 Out Signal Latched Output Q Logic LE46 Out inverted Signal Negated Latched Output Q NOT Logic LE47 Gate Out Signal Output of the logic gate Logic LE47 Timer Out Signal Timer Output Logic LE47 Out...

Page 1035: ...nverted Signal Negated Latched Output Q NOT Logic LE56 Gate Out Signal Output of the logic gate Logic LE56 Timer Out Signal Timer Output Logic LE56 Out Signal Latched Output Q Logic LE56 Out inverted...

Page 1036: ...ate Out Signal Output of the logic gate Logic LE65 Timer Out Signal Timer Output Logic LE65 Out Signal Latched Output Q Logic LE65 Out inverted Signal Negated Latched Output Q NOT Logic LE66 Gate Out...

Page 1037: ...E74 Timer Out Signal Timer Output Logic LE74 Out Signal Latched Output Q Logic LE74 Out inverted Signal Negated Latched Output Q NOT Logic LE75 Gate Out Signal Output of the logic gate Logic LE75 Time...

Page 1038: ...ilability and the number of entries depends on the type of device Name Description No assignment DI 8P X1 DI 1 Signal Digital Input DI 8P X1 DI 2 Signal Digital Input DI 8P X1 DI 3 Signal Digital Inpu...

Page 1039: ...ced Generator Current Protection 47 Unbalanced Voltage Protection 48 Incomplete Sequence Start up time Supervison 49 Thermal Protection 49M Thermal Motor Protection 49R Thermal Rotor Protection 49S Th...

Page 1040: ...74TC Trip Circuit Supervision 78V Vector Surge Protection 79 Auto Reclosure 81 Frequency Protection 81U Underfrequency Protection 81O Overfrequency Protection 81R ROCOF df dt 86 Lock Out 87 Different...

Page 1041: ...RANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAI...

Reviews: